Details

    • Bug
    • Resolution: Fixed
    • Minor
    • None
    • Professional Edition
    • Discovery, Poller

    Description

      Hi,

      I've got Eltek WebPower devices. Observium show wrong Amper values on battery or rectifiers.

      Recitfier 1 should be 2,1A but is 21A

      Rectifier 2 should be 1,9A but is 19A etc.

      Attachments

        1. eltek_after_update.txt
          42 kB
        2. eltek_battery_current.png
          eltek_battery_current.png
          18 kB
        3. eltek_discovery.txt
          43 kB
        4. eltek.png
          eltek.png
          18 kB
        5. megatec_discovery.txt
          51 kB

        Activity

          [OBS-3019] Eltek WebPower wrong Amper values

          Ok now megatec and eltek is fine.
          Thank you

          tkarczewski Tomasz Karczewski added a comment - Ok now megatec and eltek is fine. Thank you

          Ok, now issue complete fixed in r9915.

          landy Mike Stupalov added a comment - Ok, now issue complete fixed in r9915.

          Still wrong battery voltage value.

          tkarczewski Tomasz Karczewski added a comment - Still wrong battery voltage value.

          True, battery voltage fixed in r9914.

          landy Mike Stupalov added a comment - True, battery voltage fixed in r9914.

          I updated and rediscover but battery current has still wrong value

          tkarczewski Tomasz Karczewski added a comment - I updated and rediscover but battery current has still wrong value

          I think should be fixed in r9914 (rediscovery required).

          landy Mike Stupalov added a comment - I think should be fixed in r9914 (rediscovery required).

          tkarczewski Rectifier scale fixed in r9913.

          Battery no real way for detect correct scale, in MIB description written:
          "Note that the units measured may be in Amperes or in Deciamperes depending on global system settings", but snmp output not have attribute for detect scale.

          I added additional change for Battery, please do debug discovery one more time after update (svn up).

          landy Mike Stupalov added a comment - tkarczewski Rectifier scale fixed in r9913. Battery no real way for detect correct scale, in MIB description written: "Note that the units measured may be in Amperes or in Deciamperes depending on global system settings", but snmp output not have attribute for detect scale. I added additional change for Battery, please do debug discovery one more time after update (svn up).

          Attach same debug for MegaTec pls

          landy Mike Stupalov added a comment - Attach same debug for MegaTec pls

          People

            landy Mike Stupalov
            tkarczewski Tomasz Karczewski
            Votes:
            0 Vote for this issue
            Watchers:
            2 Start watching this issue

            Dates

              Created:
              Updated:
              Resolved: