Details
-
Improvement
-
Resolution: Fixed
-
Major
-
None
-
CE-22.5
-
None
Description
Hello,
ServerTech Sentry PDU 8.0x are currently polled but only report current, voltage and power by phase
Vendor/Hardware: ServerTech C2S48TE-5PAE2M99
They are missing total Watts and VA.
From ServerTech's support:
Following is from the Sentry4OID Tree:
Full OID, active power (W): .1.3.6.1.4.1.1718.4.1.3.3.1.3.1.1
DESCRIPTION: "The measured active power of the input cord in Watts."
Full OID, apparent power (VA): .1.3.6.1.4.1.1718.4.1.3.3.1.5.1.1
DESCRIPTION: "The measured apparent power of the input cord in Volt-Amps."
Regards,
Attachments
Activity
Resolution | New: Fixed [ 1 ] | |
Status | Original: In Progress [ 3 ] | New: Resolved [ 5 ] |
Attachment | Original: myagent2.snmpwalk [ 20836 ] |
Attachment | Original: myagent.snmpwalk [ 20835 ] |
Priority | Original: Blocker [ 1 ] | New: Major [ 3 ] |
Issue Type | Original: Library Bug [ 10100 ] | New: Improvement [ 4 ] |
Status | Original: In Review [ 10101 ] | New: In Progress [ 3 ] |
Status | Original: Pending Response [ 10000 ] | New: In Review [ 10101 ] |
Attachment | New: myagent.snmpwalk [ 20835 ] | |
Attachment | New: myagent2.snmpwalk [ 20836 ] |
Status | Original: Open [ 1 ] | New: Pending Response [ 10000 ] |