      Hello,

      ServerTech Sentry PDU 8.0x are currently polled but only report current, voltage and power by phase

      Vendor/Hardware: ServerTech C2S48TE-5PAE2M99

      They are missing total Watts and VA.
      From ServerTech's support:

      Following is from the Sentry4OID Tree:
      Full OID, active power (W): .1.3.6.1.4.1.1718.4.1.3.3.1.3.1.1
      DESCRIPTION: "The measured active power of the input cord in Watts."

      Full OID, apparent power (VA): .1.3.6.1.4.1.1718.4.1.3.3.1.5.1.1
      DESCRIPTION: "The measured apparent power of the input cord in Volt-Amps."