Huawei UPS reporting wrong battery runtime remaining

Details

    • Vendor Bug
    • Resolution: Fixed
    • Minor
    • None
    • Professional Edition
    • Poller
    • None

    Description

      We have recently installed a new UPS from Huawei: UPS5000-E.

      The device was discovered without any problems. However I have just noticed that the remaining battery life is reported too high by a factor of 60. So I assume that the SNMP provides the value in seconds and Observium incorrectly gives the value in minutes.

      snmpwalk is attached.

      Attachments

        Activity

          [OBS-4112] Huawei UPS reporting wrong battery runtime remaining

          Everything looks allright now. Thanks again!

          swfeldkirch Siegfried Gumilar added a comment - Everything looks allright now. Thanks again!

          Fixed in r12023.

          Incorrect scales in mib descriptions.

          landy Mike Stupalov added a comment - Fixed in r12023. Incorrect scales in mib descriptions.

          Hi Mike,

          we now have all the values we need - thank you! However the power values are still too large by a power of ten. Observium, for example, shows 34 kW or kVA while in reality it is 3.4 kW or kVA.

          swfeldkirch Siegfried Gumilar added a comment - Hi Mike, we now have all the values we need - thank you! However the power values are still too large by a power of ten. Observium, for example, shows 34 kW or kVA while in reality it is 3.4 kW or kVA.

          Improved in r12022.

          landy Mike Stupalov added a comment - Improved in r12022.

          Will see

          landy Mike Stupalov added a comment - Will see

          Hi Mike,

          as always thank you for your quick support! It seems that I should have taken a closer look at all the values right at the beginning. The frequency of our UPS is currently also displayed at approx. 500Hz. In addition, the values for current, voltage, power, frequency and load are only displayed for phase 1, although it is a 3-phase UPS. Could you please also fix this?

          swfeldkirch Siegfried Gumilar added a comment - Hi Mike, as always thank you for your quick support! It seems that I should have taken a closer look at all the values right at the beginning. The frequency of our UPS is currently also displayed at approx. 500Hz. In addition, the values for current, voltage, power, frequency and load are only displayed for phase 1, although it is a 3-phase UPS. Could you please also fix this?

          Should be fixed in r12019.

          landy Mike Stupalov added a comment - Should be fixed in r12019.
          landy Mike Stupalov added a comment - swfeldkirch Can you get and attach latest UPS MIB by this instruction? https://support.huawei.com/enterprise/en/doc/EDOC1100207210/5bad1c22/installing-the-ups-mib-library

          As I see it's show in dump it incorrectly report time as seconds (but here should be minutes):

          UPS-MIB::upsEstimatedMinutesRemaining.0 = INTEGER: 8760 minutes
          

          in own mib seconds:

          HUAWEI-UPS-MIB::hwUpsBatteryBackupTime.1 = Gauge32: 8820 S
          

          I will switch to Huawei own MIB.

          landy Mike Stupalov added a comment - As I see it's show in dump it incorrectly report time as seconds (but here should be minutes): UPS-MIB::upsEstimatedMinutesRemaining.0 = INTEGER: 8760 minutes in own mib seconds: HUAWEI-UPS-MIB::hwUpsBatteryBackupTime.1 = Gauge32: 8820 S I will switch to Huawei own MIB.