Rittal CMC-III-PU

    XMLWordPrintable

Details

    Description

      Hi,

      we got a Rittal CMC-III-PU monitoring device (latest firemware version  V 3.15.20_10 is installed) here with a Smoke Detector and Water Leakage Sensor Device.
      Observium is reading the current temperature value fine, but not using the high,low alarm,warning values from the device that it provides and for the "event state"
      it's also not using the provided event state from the device.
      Attached are the OIDs for the limits.

      Temperature High Alarm:   .1.3.6.1.4.1.2606.7.4.2.2.1.11.1.4 (45.00°C = 4500 INT)
      Temperature High Warning: .1.3.6.1.4.1.2606.7.4.2.2.1.11.1.5 (30.00°C = 3000 INT)
      Temperature Low Warning:  .1.3.6.1.4.1.2606.7.4.2.2.1.11.1.6 (10.00°C = 1000 INT)
      Temperature Low Warning:  .1.3.6.1.4.1.2606.7.4.2.2.1.11.1.7 ( 5.00°C = 500 INT)

      Event State of Temperature Sensor: .1.3.6.1.4.1.2606.7.4.2.2.1.11.1.9

      Possible INTEGER Values:
      8 = High Alarm
      6 = High Warning
      9 = Low Warning
      7 = Low Alarm
      4 = OK

      everything else: error i.e. 1,2,3,21 (see RITTAL-CMC-III-MIB cmcIIIMsgStatus)

      The Water Leakage Sensor has following OID for water/dry

      .1.3.6.1.4.1.2606.7.4.2.2.1.11.3.4 = INTEGER

      4 = OK (dry)
      5 = ERROR (water detected)

      Smoke Detector

      .1.3.6.1.4.1.2606.7.4.2.2.1.11.2.4 = INTEGER

      4 = OK (clear air)
      5 = ERROR (smoke detected)

      Of course it would be a must to be able to create custom alerts for all these sensors. If you need snmp access to this device I should be able to arrange a session.