Hello,
We received a new CyberPower PDU81005, and this one has a different sysObjectID.0.
In cyberpower.inc.php, it states that .1.3.6.1.4.1.3808.1.1.3 is for PDU, but when I change it to .1.3.6.1.4.1.3808.1.1.6, it appears that everything is polled correctly so you can add this improvement.
.1.3.6.1.2.1.1.1.0 = STRING: "CPS Power Distributed Unit"
.1.3.6.1.2.1.1.2.0 = OID: .1.3.6.1.4.1.3808.1.1.6
.1.3.6.1.2.1.1.3.0 = Timeticks: (1711600) 4:45:16.00
.1.3.6.1.2.1.1.4.0 = STRING: "Administrator"
.1.3.6.1.2.1.1.5.0 = STRING: "PDU81005"
.1.3.6.1.2.1.1.6.0 = STRING: "Server Room"
.1.3.6.1.2.1.1.7.0 = INTEGER: 72
.1.3.6.1.2.1.2.1.0 = INTEGER: 1