Details

    • Add New Device / OS
    • Resolution: Fixed
    • Minor
    • None
    • None
    • Discovery
    • None

    Description

      Hello Observium!

      We have been trailing some PDU's from INOVA but nothing is matching up other than the APC mib.

      I have been supplied a copy of the MIB but the instructions on the doc's was a bit beyond my capabilities so I was wondering if someone more experience could give it a shot?

      Attachments

        Issue Links

          Activity

            [OBS-4867] Request to add INOVA PDU

            They released some new firmware and an updated MIB.
            Observium now no longer detects these.

            [^PowerNet-Inova_v01.zip]

            chrisbish92 Chris Bishop added a comment - They released some new firmware and an updated MIB. Observium now no longer detects these. [^PowerNet-Inova_v01.zip]

            Added support in r13663.

            landy Mike Stupalov added a comment - Added support in r13663.

            This is not APC, but seems as clone of APC PDU.
            Need separate os/vendor.

            landy Mike Stupalov added a comment - This is not APC, but seems as clone of APC PDU. Need separate os/vendor.

            Attached new SNMP Walk as requested with some devices on the ports to generate data.

            SNMP errors

               
             1 PowerNet-Discovery-MIB
             apcDiscoveryFirmwareRevision.1 2m 50s ago Failed response 4 1/poll  
             3 PowerNet-MIB
             atsIdentModelNumber 2m 50s ago GETNEXT empty response 4 1/poll  
             rPDUIdentModelNumber 2m 49s ago GETNEXT empty response 4 1/poll  
             upsBasicIdentModel 2m 50s ago GETNEXT empty response 4 1/poll  
            chrisbish92 Chris Bishop added a comment - Attached new SNMP Walk as requested with some devices on the ports to generate data. SNMP errors      1 PowerNet-Discovery-MIB   apcDiscoveryFirmwareRevision.1 2m 50s ago Failed response 4 1/poll    3 PowerNet-MIB   atsIdentModelNumber 2m 50s ago GETNEXT empty response 4 1/poll     rPDUIdentModelNumber 2m 49s ago GETNEXT empty response 4 1/poll     upsBasicIdentModel 2m 50s ago GETNEXT empty response 4 1/poll  

            Improved in r13630.

            These are just populating the APC rPDU2 table. We already had support for these, but the detection code was behind an if() checking for the rPDU table being populated. which doesn't seem to be on these devices.

            adama Adam Armstrong added a comment - Improved in r13630. These are just populating the APC rPDU2 table. We already had support for these, but the detection code was behind an if() checking for the rPDU table being populated. which doesn't seem to be on these devices.