Huawei UPS returns impossible values

    XMLWordPrintable

Details

    • Improvement
    • Resolution: Fixed
    • Major
    • None
    • Community Edition
    • None
    • None

    Description

      My Huawei UPS2000-G-3KRTS returns impossible values:

      UPS-MIB::upsBatteryCurrent.0 = INTEGER: 2147483647 0.1 Amp DC
      UPS-MIB::upsBatteryTemperature.0 = INTEGER: 2147483647 degrees Centigrade
      

      Huawei says this is normal:

      The reason why you have incorrect values for the UPS Battery Current and UPS Battery temperature is the following :

      1. The battery current is available only during discharging.

      2.Battery temperature. An optional component is required, such as temperature sensor installed in the SNMP Card T/H slot.

      Please implement a workaround to hide those impossible values and if there is an RFC that renders this SNMP behaviour invalid, please let me know what I can throw at Huawei so they can fix it.