-- -- PowerNet-PDU.mib -- MIB generated by MG-SOFT Visual MIB Builder Version 6.0 Build 88 -- Tuesday, June 15, 2021 at 17:32:01 -- -- PowerNet-PDU.mib -- MIB generated by MG-SOFT Visual MIB Builder Version 6.0 Build 88 -- Monday, June 14, 2021 at 17:18:32 -- -- ******************************************************************************************** -- ******************************************************************************************** -- PowerNet-MIB { iso org(3) dod(6) internet(1) private(4) -- enterprises(1) PDU(318) } PowerNet-PDU DEFINITIONS ::= BEGIN IMPORTS OBJECT-TYPE FROM RFC-1212 TRAP-TYPE FROM RFC-1215 enterprises, TimeTicks, IpAddress, Gauge, Opaque FROM RFC1155-SMI DisplayString FROM RFC1213-MIB; -- -- Type definitions -- -- Common rPDU2 values Rpdu2OutletPhaseLayoutType ::= INTEGER { seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6) } -- Type definitions -- AirIRSCFanSpeedPreference ::= INTEGER { low(1), med-low(2), med(3), med-high(4), high(5) } -- airIRSC AIR CONDITIONER Defines AirIRSCConfigType ::= INTEGER { racs(1), spot(2), in-row(3) } AirIRSCCapacityControlType ::= INTEGER { discrete(1), proportional(2) } AirIRSCFanSpeedControl ::= INTEGER { automatic(1), manual(2) } -- *************************************** -- airIRG2RDType2 AIR CONDITIONER Defines -- *************************************** AirIRG2RDType2IOState ::= INTEGER { open(1), closed(2) } -- Beginning of AC InRoom -- common InRoom values AirIRmAlarmState ::= INTEGER { ok(1), alarm(2) } AirIRmStopState ::= INTEGER { maybeOn(1), unitOff(2) } AirIRmActivityState ::= INTEGER { inactive(1), active(2) } AirIRmControlState ::= INTEGER { off(1), on(2) } -- -- Node definitions -- -- Node definitions -- -- IMPORTS End -- 1.3.6.1.4.1.318 -- 1.3.6.1.4.1.318 PDU OBJECT IDENTIFIER ::= { enterprises 318 } -- 1.3.6.1.4.1.318.1 -- 1.3.6.1.4.1.318.1 products OBJECT IDENTIFIER ::= { PDU 1 } -- 1.3.6.1.4.1.318.1.1 -- 1.3.6.1.4.1.318.1.1 hardware OBJECT IDENTIFIER ::= { products 1 } -- 1.3.6.1.4.1.318.1.1.26 -- 1.3.6.1.4.1.318.1.1.26 rPDU2 OBJECT IDENTIFIER ::= { hardware 26 } -- rPDU2 Ident Table -- 1.3.6.1.4.1.318.1.1.26.1 -- 1.3.6.1.4.1.318.1.1.26.1 rPDU2IdentTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The total number of Rack PDUs" ::= { rPDU2 1 } -- 1.3.6.1.4.1.318.1.1.26.2 -- 1.3.6.1.4.1.318.1.1.26.2 rPDU2IdentTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2IdentEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU identification data" ::= { rPDU2 2 } -- 1.3.6.1.4.1.318.1.1.26.2.1 -- 1.3.6.1.4.1.318.1.1.26.2.1 rPDU2IdentEntry OBJECT-TYPE SYNTAX RPDU2IdentEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Identification data from Rack PDU being queried" INDEX { rPDU2IdentIndex } ::= { rPDU2IdentTable 1 } RPDU2IdentEntry ::= SEQUENCE { rPDU2IdentIndex INTEGER, rPDU2IdentModule INTEGER, rPDU2IdentName DisplayString, rPDU2IdentLocation DisplayString, rPDU2IdentHardwareRev DisplayString, rPDU2IdentFirmwareRev DisplayString, rPDU2IdentDateOfManufacture DisplayString, rPDU2IdentModelNumber DisplayString, rPDU2IdentSerialNumber DisplayString, rPDU2IdentContact DisplayString, rPDU2IdentBootMonitorRev DisplayString, rPDU2IdentLongDescription DisplayString, rPDU2IdentNMCSerialNumber DisplayString } -- 1.3.6.1.4.1.318.1.1.26.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.2.1.1 rPDU2IdentIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU identification table entry" ::= { rPDU2IdentEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.2.1.2 rPDU2IdentModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2IdentEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.2.1.3 rPDU2IdentName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A user-defined string identifying the Rack PDU" ::= { rPDU2IdentEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.2.1.4 -- 1.3.6.1.4.1.318.1.1.26.2.1.4 rPDU2IdentLocation OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A user-defined string identifying the location of the Rack PDU" ::= { rPDU2IdentEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.2.1.5 -- 1.3.6.1.4.1.318.1.1.26.2.1.5 rPDU2IdentHardwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Rack PDU hardware version" ::= { rPDU2IdentEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.2.1.6 -- 1.3.6.1.4.1.318.1.1.26.2.1.6 rPDU2IdentFirmwareRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Rack PDU firmware version" ::= { rPDU2IdentEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.2.1.7 -- 1.3.6.1.4.1.318.1.1.26.2.1.7 rPDU2IdentDateOfManufacture OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The date the Rack PDU was manufactured in mm/dd/yyyy format" ::= { rPDU2IdentEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.2.1.8 -- 1.3.6.1.4.1.318.1.1.26.2.1.8 rPDU2IdentModelNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Rack PDU model number" ::= { rPDU2IdentEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.2.1.9 -- 1.3.6.1.4.1.318.1.1.26.2.1.9 rPDU2IdentSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Rack PDU serial number" ::= { rPDU2IdentEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.2.1.10 -- 1.3.6.1.4.1.318.1.1.26.2.1.10 rPDU2IdentContact OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A user-defined string identifying the person to contact regarding the Rack PDU" ::= { rPDU2IdentEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.2.1.11 -- 1.3.6.1.4.1.318.1.1.26.2.1.11 rPDU2IdentBootMonitorRev OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Rack PDU Boot Monitor version" ::= { rPDU2IdentEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.2.1.12 -- 1.3.6.1.4.1.318.1.1.26.2.1.12 rPDU2IdentLongDescription OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Rack PDU Long Description name" ::= { rPDU2IdentEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.2.1.13 -- 1.3.6.1.4.1.318.1.1.26.2.1.13 rPDU2IdentNMCSerialNumber OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The Rack PDU Network Management Card (NMC) serial number" ::= { rPDU2IdentEntry 13 } -- rPDU2 Device Data -- 1.3.6.1.4.1.318.1.1.26.3 -- 1.3.6.1.4.1.318.1.1.26.3 rPDU2DeviceTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The total number of Rack PDUs" ::= { rPDU2 3 } -- 1.3.6.1.4.1.318.1.1.26.4 -- 1.3.6.1.4.1.318.1.1.26.4 rPDU2Device OBJECT IDENTIFIER ::= { rPDU2 4 } -- rPDU2 Device Config -- 1.3.6.1.4.1.318.1.1.26.4.1 -- 1.3.6.1.4.1.318.1.1.26.4.1 rPDU2DeviceConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2DeviceConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU configuration data" ::= { rPDU2Device 1 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1 -- 1.3.6.1.4.1.318.1.1.26.4.1.1 rPDU2DeviceConfigEntry OBJECT-TYPE SYNTAX RPDU2DeviceConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from Rack PDU being queried" INDEX { rPDU2DeviceConfigIndex } ::= { rPDU2DeviceConfigTable 1 } RPDU2DeviceConfigEntry ::= SEQUENCE { rPDU2DeviceConfigIndex INTEGER, rPDU2DeviceConfigModule INTEGER, rPDU2DeviceConfigName DisplayString, rPDU2DeviceConfigLocation DisplayString, rPDU2DeviceConfigDisplayOrientation INTEGER, rPDU2DeviceConfigColdstartDelay INTEGER, rPDU2DeviceConfigLowLoadPowerThreshold INTEGER, rPDU2DeviceConfigNearOverloadPowerThreshold INTEGER, rPDU2DeviceConfigOverloadPowerThreshold INTEGER, rPDU2DeviceConfigDevicePeakPowerReset INTEGER, rPDU2DeviceConfigDeviceEnergyReset INTEGER, rPDU2DeviceConfigOutletsEnergyReset INTEGER, rPDU2DeviceConfigOutletsPeakLoadReset INTEGER, rPDU2DeviceConfigContact DisplayString } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.1 rPDU2DeviceConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU table entry" ::= { rPDU2DeviceConfigEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.2 rPDU2DeviceConfigModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2DeviceConfigEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.3 rPDU2DeviceConfigName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A user-defined string identifying the Rack PDU" ::= { rPDU2DeviceConfigEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.4 rPDU2DeviceConfigLocation OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A user-defined string identifying the location of the Rack PDU" ::= { rPDU2DeviceConfigEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.5 rPDU2DeviceConfigDisplayOrientation OBJECT-TYPE SYNTAX INTEGER { displayNormal(1), displayReverse(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Indicates the intended physical orientation of the display. displayNormal(1) indicates normal orientation displayReverse(2) indicates upside down orientation" ::= { rPDU2DeviceConfigEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.6 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.6 rPDU2DeviceConfigColdstartDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes)." ::= { rPDU2DeviceConfigEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.7 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.7 rPDU2DeviceConfigLowLoadPowerThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined low power draw alarm threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceConfigEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.8 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.8 rPDU2DeviceConfigNearOverloadPowerThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceConfigEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.9 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.9 rPDU2DeviceConfigOverloadPowerThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceConfigEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.10 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.10 rPDU2DeviceConfigDevicePeakPowerReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2), notSupported(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of not supported (3). Attempts to set this OID in these models will fail." ::= { rPDU2DeviceConfigEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.11 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.11 rPDU2DeviceConfigDeviceEnergyReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2), notSupported(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail." ::= { rPDU2DeviceConfigEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.12 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.12 rPDU2DeviceConfigOutletsEnergyReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2), notSupported(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the all outlet energy meter values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail." ::= { rPDU2DeviceConfigEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.13 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.13 rPDU2DeviceConfigOutletsPeakLoadReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2), notSupported(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail." ::= { rPDU2DeviceConfigEntry 13 } -- 1.3.6.1.4.1.318.1.1.26.4.1.1.14 -- 1.3.6.1.4.1.318.1.1.26.4.1.1.14 rPDU2DeviceConfigContact OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A user-defined string identifying the person to contact regarding the Rack PDU" ::= { rPDU2DeviceConfigEntry 14 } -- rPDU2 Device Properties -- 1.3.6.1.4.1.318.1.1.26.4.2 -- 1.3.6.1.4.1.318.1.1.26.4.2 rPDU2DevicePropertiesTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2DevicePropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU properties" ::= { rPDU2Device 2 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1 -- 1.3.6.1.4.1.318.1.1.26.4.2.1 rPDU2DevicePropertiesEntry OBJECT-TYPE SYNTAX RPDU2DevicePropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Properties of the Rack PDU being queried" INDEX { rPDU2DevicePropertiesIndex } ::= { rPDU2DevicePropertiesTable 1 } RPDU2DevicePropertiesEntry ::= SEQUENCE { rPDU2DevicePropertiesIndex INTEGER, rPDU2DevicePropertiesModule INTEGER, rPDU2DevicePropertiesName DisplayString, rPDU2DevicePropertiesNumOutlets INTEGER, rPDU2DevicePropertiesNumSwitchedOutlets INTEGER, rPDU2DevicePropertiesNumMeteredOutlets INTEGER, rPDU2DevicePropertiesNumPhases INTEGER, rPDU2DevicePropertiesNumMeteredBanks INTEGER, rPDU2DevicePropertiesMaxCurrentRating INTEGER, rPDU2DevicePropertiesOrientation INTEGER, rPDU2DevicePropertiesOutletLayout INTEGER, rPDU2DevicePropertiesMaxPhaseCurrentRating INTEGER, rPDU2DevicePropertiesDevicePowerRating INTEGER } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.1 rPDU2DevicePropertiesIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU properties table entry" ::= { rPDU2DevicePropertiesEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.2 rPDU2DevicePropertiesModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2DevicePropertiesEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.3 rPDU2DevicePropertiesName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A user-defined string identifying the Rack PDU" ::= { rPDU2DevicePropertiesEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.4 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.4 rPDU2DevicePropertiesNumOutlets OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of outlets on the Rack PDU" ::= { rPDU2DevicePropertiesEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.5 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.5 rPDU2DevicePropertiesNumSwitchedOutlets OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of switched outlets on the Rack PDU" ::= { rPDU2DevicePropertiesEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.6 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.6 rPDU2DevicePropertiesNumMeteredOutlets OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of metered outlets on the Rack PDU" ::= { rPDU2DevicePropertiesEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.7 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.7 rPDU2DevicePropertiesNumPhases OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of phases present in the Rack PDU" ::= { rPDU2DevicePropertiesEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.8 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.8 rPDU2DevicePropertiesNumMeteredBanks OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of metered banks present in the Rack PDU" ::= { rPDU2DevicePropertiesEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.9 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.9 rPDU2DevicePropertiesMaxCurrentRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum current rating, measured in Amps, for the Rack PDU" ::= { rPDU2DevicePropertiesEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.10 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.10 rPDU2DevicePropertiesOrientation OBJECT-TYPE SYNTAX INTEGER { horizontal(1), vertical(2), verticalISXv2(3), verticalISXv3(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Rack PDU orientation" ::= { rPDU2DevicePropertiesEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.11 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.11 rPDU2DevicePropertiesOutletLayout OBJECT-TYPE SYNTAX INTEGER { seqPhaseToNeutral(1), seqPhaseToPhase(2), seqPhToNeu21PhToPh(3), seqPhToPhGrouped(4), seqPhToNGrouped(5), seqPToN1516PToPGrouped(6), seqPhToPh2xGrouped(7), seqPhToN2xGrouped(8), seqNotApplicable(9), seqPhToNPhToPhPhToN(10) } ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... or for single phase SKUs, all outlets 1-N seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: For AP8xxx SKU's Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9): Outlet layout does not affect any of the user interfaces for AP88XX SKUs. These SKUs may report seqNotApplicable(9) if there is not an exact outlet layout match available. seqPhToNPhToPhPhToN(10) indicates outlet layout as follows: Group 1:1-N, Group 2:1-2, Group 3:2-N. Only AP7xxx, AP8xxx SKUs support this feature. Product which does not support this feature will respond with -1" ::= { rPDU2DevicePropertiesEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.12 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.12 rPDU2DevicePropertiesMaxPhaseCurrentRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum current rating, measured in Amps, for the Rack PDU" ::= { rPDU2DevicePropertiesEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.4.2.1.13 -- 1.3.6.1.4.1.318.1.1.26.4.2.1.13 rPDU2DevicePropertiesDevicePowerRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The maximum power rating, measured in tenths of kilowatts, for the Rack PDU" ::= { rPDU2DevicePropertiesEntry 13 } -- rPDU2 Device Status -- 1.3.6.1.4.1.318.1.1.26.4.3 -- 1.3.6.1.4.1.318.1.1.26.4.3 rPDU2DeviceStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2DeviceStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU status information" ::= { rPDU2Device 3 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1 -- 1.3.6.1.4.1.318.1.1.26.4.3.1 rPDU2DeviceStatusEntry OBJECT-TYPE SYNTAX RPDU2DeviceStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status information from the Rack PDU being queried" INDEX { rPDU2DeviceStatusIndex } ::= { rPDU2DeviceStatusTable 1 } RPDU2DeviceStatusEntry ::= SEQUENCE { rPDU2DeviceStatusIndex INTEGER, rPDU2DeviceStatusModule INTEGER, rPDU2DeviceStatusName DisplayString, rPDU2DeviceStatusLoadState INTEGER, rPDU2DeviceStatusPower INTEGER, rPDU2DeviceStatusPeakPower INTEGER, rPDU2DeviceStatusPeakPowerTimestamp DisplayString, rPDU2DeviceStatusPeakPowerStartTime DisplayString, rPDU2DeviceStatusEnergy INTEGER, rPDU2DeviceStatusEnergyStartTime DisplayString, rPDU2DeviceStatusCommandPending INTEGER, rPDU2DeviceStatusPowerSupplyAlarm INTEGER, rPDU2DeviceStatusPowerSupply1Status INTEGER, rPDU2DeviceStatusPowerSupply2Status INTEGER, rPDU2DeviceStatusOutletsEnergyStartTime DisplayString, rPDU2DeviceStatusApparentPower INTEGER, rPDU2DeviceStatusPowerFactor INTEGER, rPDU2DeviceStatusNPSType INTEGER, rPDU2DeviceStatusResidualPower INTEGER, rPDU2DeviceStatusFrequency INTEGER } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.1 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.1 rPDU2DeviceStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU status table entry" ::= { rPDU2DeviceStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.2 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.2 rPDU2DeviceStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2DeviceStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.3 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.3 rPDU2DeviceStatusName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A user-defined string identifying the Rack PDU" ::= { rPDU2DeviceStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.4 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.4 rPDU2DeviceStatusLoadState OBJECT-TYPE SYNTAX INTEGER { lowLoad(1), normal(2), nearOverload(3), overload(4), notsupported(5) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the present load status of the Rack PDU. Models that do not support this feature will respond to this OID with a value of notsupported (5)." ::= { rPDU2DeviceStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.5 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.5 rPDU2DeviceStatusPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceStatusEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.6 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.6 rPDU2DeviceStatusPeakPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The peak power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceStatusEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.7 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.7 rPDU2DeviceStatusPeakPowerTimestamp OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time that peak power consumption occurred. Models that do not support this feature will respond to this OID with string 'notsupported'." ::= { rPDU2DeviceStatusEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.8 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.8 rPDU2DeviceStatusPeakPowerStartTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time of the last device peak power reset. Models that do not support this feature will respond to this OID with string 'notsupported'." ::= { rPDU2DeviceStatusEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.9 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.9 rPDU2DeviceStatusEnergy OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceStatusEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.10 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.10 rPDU2DeviceStatusEnergyStartTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time of the last device energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'." ::= { rPDU2DeviceStatusEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.11 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.11 rPDU2DeviceStatusCommandPending OBJECT-TYPE SYNTAX INTEGER { commandPending(1), noCommandPending(2), commandPendingUnknown(3) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition." ::= { rPDU2DeviceStatusEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.12 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.12 rPDU2DeviceStatusPowerSupplyAlarm OBJECT-TYPE SYNTAX INTEGER { normal(1), alarm(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates a power supply alarm is active when value equals alarm (2)" ::= { rPDU2DeviceStatusEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.13 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.13 rPDU2DeviceStatusPowerSupply1Status OBJECT-TYPE SYNTAX INTEGER { normal(1), alarm(2), notInstalled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not an alarm is active in Power Supply 1" ::= { rPDU2DeviceStatusEntry 13 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.14 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.14 rPDU2DeviceStatusPowerSupply2Status OBJECT-TYPE SYNTAX INTEGER { normal(1), alarm(2), notInstalled(3) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not an alarm is active in Power Supply 2" ::= { rPDU2DeviceStatusEntry 14 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.15 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.15 rPDU2DeviceStatusOutletsEnergyStartTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time of the last outlets energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'." ::= { rPDU2DeviceStatusEntry 15 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.16 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.16 rPDU2DeviceStatusApparentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA). Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceStatusEntry 16 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.17 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.17 rPDU2DeviceStatusPowerFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of the Rack PDU load in hundredths. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2DeviceStatusEntry 17 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.18 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.18 rPDU2DeviceStatusNPSType OBJECT-TYPE SYNTAX INTEGER { notNPS(1), host(2), guest(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The device NPS status: notNPS (1) indicates the Rack PDU is not in an NPS group. host (2) indicates the Rack PDU has been designated as a host in an NPS group. Only one Rack PDU in an NPS group is allowed to be the host. guest (3) indicates the Rack PDU has been designated as a guest in an NPS group." ::= { rPDU2DeviceStatusEntry 18 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.19 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.19 rPDU2DeviceStatusResidualPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The measured device residual power from the PDU meters in hundredths of kiloVoltAmps." ::= { rPDU2DeviceStatusEntry 19 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.20 -- 1.3.6.1.4.1.318.1.1.26.4.3.1.20 rPDU2DeviceStatusFrequency OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The measured device frequency from the PDU meters in tenths of Hz." ::= { rPDU2DeviceStatusEntry 20 } -- rPDU2 Device Control -- 1.3.6.1.4.1.318.1.1.26.4.4 -- 1.3.6.1.4.1.318.1.1.26.4.4 rPDU2DeviceControlTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2DeviceControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU control data" ::= { rPDU2Device 4 } -- 1.3.6.1.4.1.318.1.1.26.4.4.1 -- 1.3.6.1.4.1.318.1.1.26.4.4.1 rPDU2DeviceControlEntry OBJECT-TYPE SYNTAX RPDU2DeviceControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Control data from Rack PDU being queried" INDEX { rPDU2DeviceControlIndex } ::= { rPDU2DeviceControlTable 1 } RPDU2DeviceControlEntry ::= SEQUENCE { rPDU2DeviceControlIndex INTEGER, rPDU2DeviceControlModule INTEGER, rPDU2DeviceControlName DisplayString, rPDU2DeviceControlCommand INTEGER } -- 1.3.6.1.4.1.318.1.1.26.4.4.1.1 -- 1.3.6.1.4.1.318.1.1.26.4.4.1.1 rPDU2DeviceControlIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU control table entry" ::= { rPDU2DeviceControlEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.4.4.1.2 -- 1.3.6.1.4.1.318.1.1.26.4.4.1.2 rPDU2DeviceControlModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2DeviceControlEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.4.4.1.3 -- 1.3.6.1.4.1.318.1.1.26.4.4.1.3 rPDU2DeviceControlName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "A user-defined string identifying the Rack PDU" ::= { rPDU2DeviceControlEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.4.4.1.4 -- 1.3.6.1.4.1.318.1.1.26.4.4.1.4 rPDU2DeviceControlCommand OBJECT-TYPE SYNTAX INTEGER { immediateAllOn(1), delayedAllOn(2), immediateAllOff(3), immediateAllReboot(4), delayedAllReboot(5), noCommandAll(6), delayedAllOff(7), cancelAllPendingCommands(8) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllReboot (5) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to noCommandAll (6) will have no effect. Setting this OID to delayedAllOff (7) will turn all outlets off as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be cancelled. Getting this OID will return the noCommandAll (6) value." ::= { rPDU2DeviceControlEntry 4 } -- rPDU2 Phase Data -- 1.3.6.1.4.1.318.1.1.26.5 -- 1.3.6.1.4.1.318.1.1.26.5 rPDU2PhaseTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of connected Rack PDU phases" ::= { rPDU2 5 } -- 1.3.6.1.4.1.318.1.1.26.6 -- 1.3.6.1.4.1.318.1.1.26.6 rPDU2Phase OBJECT IDENTIFIER ::= { rPDU2 6 } -- rPDU2 Phase Config -- 1.3.6.1.4.1.318.1.1.26.6.1 -- 1.3.6.1.4.1.318.1.1.26.6.1 rPDU2PhaseConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2PhaseConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU phase configuration data" ::= { rPDU2Phase 1 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1 -- 1.3.6.1.4.1.318.1.1.26.6.1.1 rPDU2PhaseConfigEntry OBJECT-TYPE SYNTAX RPDU2PhaseConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from currently queried Rack PDU phase" INDEX { rPDU2PhaseConfigIndex } ::= { rPDU2PhaseConfigTable 1 } RPDU2PhaseConfigEntry ::= SEQUENCE { rPDU2PhaseConfigIndex INTEGER, rPDU2PhaseConfigModule INTEGER, rPDU2PhaseConfigNumber INTEGER, rPDU2PhaseConfigOverloadRestriction INTEGER, rPDU2PhaseConfigLowLoadCurrentThreshold INTEGER, rPDU2PhaseConfigNearOverloadCurrentThreshold INTEGER, rPDU2PhaseConfigOverloadCurrentThreshold INTEGER, rPDU2PhaseConfigPhasePeakCurrentReset INTEGER } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.1 rPDU2PhaseConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU phase configuration table entry" ::= { rPDU2PhaseConfigEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.2 rPDU2PhaseConfigModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2PhaseConfigEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.3 rPDU2PhaseConfigNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric phase ID" ::= { rPDU2PhaseConfigEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.4 rPDU2PhaseConfigOverloadRestriction OBJECT-TYPE SYNTAX INTEGER { alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3), notSupported(4) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail." ::= { rPDU2PhaseConfigEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.5 rPDU2PhaseConfigLowLoadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined low load phase current threshold in Amps" ::= { rPDU2PhaseConfigEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.6 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.6 rPDU2PhaseConfigNearOverloadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined near phase overload warning threshold in Amps" ::= { rPDU2PhaseConfigEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.7 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.7 rPDU2PhaseConfigOverloadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined phase overload current threshold in Amps" ::= { rPDU2PhaseConfigEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.6.1.1.8 -- 1.3.6.1.4.1.318.1.1.26.6.1.1.8 rPDU2PhaseConfigPhasePeakCurrentReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value." ::= { rPDU2PhaseConfigEntry 8 } -- rPDU2 Phase Properties -- 1.3.6.1.4.1.318.1.1.26.6.2 -- 1.3.6.1.4.1.318.1.1.26.6.2 rPDU2PhasePropertiesTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2PhasePropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU phase properties" ::= { rPDU2Phase 2 } -- 1.3.6.1.4.1.318.1.1.26.6.2.1 -- 1.3.6.1.4.1.318.1.1.26.6.2.1 rPDU2PhasePropertiesEntry OBJECT-TYPE SYNTAX RPDU2PhasePropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Properties of the currently queried Rack PDU phase" INDEX { rPDU2PhasePropertiesIndex } ::= { rPDU2PhasePropertiesTable 1 } RPDU2PhasePropertiesEntry ::= SEQUENCE { rPDU2PhasePropertiesIndex INTEGER, rPDU2PhasePropertiesModule INTEGER, rPDU2PhasePropertiesNumber INTEGER } -- 1.3.6.1.4.1.318.1.1.26.6.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.6.2.1.1 rPDU2PhasePropertiesIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU phase properties table entry" ::= { rPDU2PhasePropertiesEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.6.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.6.2.1.2 rPDU2PhasePropertiesModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2PhasePropertiesEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.6.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.6.2.1.3 rPDU2PhasePropertiesNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric phase ID" ::= { rPDU2PhasePropertiesEntry 3 } -- rPDU2 Phase Status -- 1.3.6.1.4.1.318.1.1.26.6.3 -- 1.3.6.1.4.1.318.1.1.26.6.3 rPDU2PhaseStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2PhaseStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU phase status data" ::= { rPDU2Phase 3 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1 -- 1.3.6.1.4.1.318.1.1.26.6.3.1 rPDU2PhaseStatusEntry OBJECT-TYPE SYNTAX RPDU2PhaseStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status data from currently queried Rack PDU phase" INDEX { rPDU2PhaseStatusIndex } ::= { rPDU2PhaseStatusTable 1 } RPDU2PhaseStatusEntry ::= SEQUENCE { rPDU2PhaseStatusIndex INTEGER, rPDU2PhaseStatusModule INTEGER, rPDU2PhaseStatusNumber INTEGER, rPDU2PhaseStatusLoadState INTEGER, rPDU2PhaseStatusCurrent INTEGER, rPDU2PhaseStatusVoltage INTEGER, rPDU2PhaseStatusPower INTEGER, rPDU2PhaseStatusApparentPower INTEGER, rPDU2PhaseStatusPowerFactor INTEGER, rPDU2PhaseStatusPeakCurrent INTEGER, rPDU2PhaseStatusPeakCurrentTimestamp DisplayString, rPDU2PhaseStatusPeakCurrentStartTime DisplayString, rPDU2PhaseStatusEnergy INTEGER } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.1 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.1 rPDU2PhaseStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU phase status table entry" ::= { rPDU2PhaseStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.2 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.2 rPDU2PhaseStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2PhaseStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.3 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.3 rPDU2PhaseStatusNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric phase ID" ::= { rPDU2PhaseStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.4 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.4 rPDU2PhaseStatusLoadState OBJECT-TYPE SYNTAX INTEGER { lowLoad(1), normal(2), nearOverload(3), overload(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the present load status of the Rack PDU phase being queried" ::= { rPDU2PhaseStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.5 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.5 rPDU2PhaseStatusCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried" ::= { rPDU2PhaseStatusEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.6 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.6 rPDU2PhaseStatusVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the Voltage, in Volts, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2PhaseStatusEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.7 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.7 rPDU2PhaseStatusPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the load power, in hundredths of kilowatts (kW), consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2PhaseStatusEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.8 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.8 rPDU2PhaseStatusApparentPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA), consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2PhaseStatusEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.9 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.9 rPDU2PhaseStatusPowerFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the load power factor, in hundredths, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2PhaseStatusEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.10 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.10 rPDU2PhaseStatusPeakCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The peak current of the Rack PDU phase load in tenths of Amps" ::= { rPDU2PhaseStatusEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.11 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.11 rPDU2PhaseStatusPeakCurrentTimestamp OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time that the peak current occurred" ::= { rPDU2PhaseStatusEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.12 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.12 rPDU2PhaseStatusPeakCurrentStartTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time of the last phase peak current reset" ::= { rPDU2PhaseStatusEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.13 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.13 rPDU2PhaseStatusEnergy OBJECT-TYPE SYNTAX INTEGER -- UNITS 0.1 kilowatt-hours ACCESS read-only STATUS mandatory DESCRIPTION "A user resettable energy meter measuring Rack PDU phase load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2PhaseStatusEntry 13 } -- rPDU2 Bank Data -- 1.3.6.1.4.1.318.1.1.26.7 -- 1.3.6.1.4.1.318.1.1.26.7 rPDU2BankTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of connected Rack PDU banks" ::= { rPDU2 7 } -- 1.3.6.1.4.1.318.1.1.26.8 -- 1.3.6.1.4.1.318.1.1.26.8 rPDU2Bank OBJECT IDENTIFIER ::= { rPDU2 8 } -- rPDU2 Bank Config -- 1.3.6.1.4.1.318.1.1.26.8.1 -- 1.3.6.1.4.1.318.1.1.26.8.1 rPDU2BankConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2BankConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU bank configuration data" ::= { rPDU2Bank 1 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1 -- 1.3.6.1.4.1.318.1.1.26.8.1.1 rPDU2BankConfigEntry OBJECT-TYPE SYNTAX RPDU2BankConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from currently queried Rack PDU bank" INDEX { rPDU2BankConfigIndex } ::= { rPDU2BankConfigTable 1 } RPDU2BankConfigEntry ::= SEQUENCE { rPDU2BankConfigIndex INTEGER, rPDU2BankConfigModule INTEGER, rPDU2BankConfigNumber INTEGER, rPDU2BankConfigOverloadRestriction INTEGER, rPDU2BankConfigLowLoadCurrentThreshold INTEGER, rPDU2BankConfigNearOverloadCurrentThreshold INTEGER, rPDU2BankConfigOverloadCurrentThreshold INTEGER, rPDU2BankConfigBankPeakCurrentReset INTEGER } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.1 rPDU2BankConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU bank configuration table entry" ::= { rPDU2BankConfigEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.2 rPDU2BankConfigModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2BankConfigEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.3 rPDU2BankConfigNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric bank ID" ::= { rPDU2BankConfigEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.4 rPDU2BankConfigOverloadRestriction OBJECT-TYPE SYNTAX INTEGER { alwaysAllowTurnON(1), restrictOnNearOverload(2), restrictOnOverload(3), notSupported(4) } ACCESS read-write STATUS mandatory DESCRIPTION "This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the rPDU2BankConfigNearOverloadCurrentThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the rPDU2BankConfigOverloadCurrentThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail." ::= { rPDU2BankConfigEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.5 rPDU2BankConfigLowLoadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined low load bank current threshold in Amps" ::= { rPDU2BankConfigEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.6 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.6 rPDU2BankConfigNearOverloadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined near bank overload current warning threshold in Amps" ::= { rPDU2BankConfigEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.7 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.7 rPDU2BankConfigOverloadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined bank overload current threshold in Amps" ::= { rPDU2BankConfigEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.8.1.1.8 -- 1.3.6.1.4.1.318.1.1.26.8.1.1.8 rPDU2BankConfigBankPeakCurrentReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value." ::= { rPDU2BankConfigEntry 8 } -- rPDU2 Bank Properties -- 1.3.6.1.4.1.318.1.1.26.8.2 -- 1.3.6.1.4.1.318.1.1.26.8.2 rPDU2BankPropertiesTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2BankPropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU bank properties" ::= { rPDU2Bank 2 } -- 1.3.6.1.4.1.318.1.1.26.8.2.1 -- 1.3.6.1.4.1.318.1.1.26.8.2.1 rPDU2BankPropertiesEntry OBJECT-TYPE SYNTAX RPDU2BankPropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Properties of the currently queried Rack PDU bank" INDEX { rPDU2BankPropertiesIndex } ::= { rPDU2BankPropertiesTable 1 } RPDU2BankPropertiesEntry ::= SEQUENCE { rPDU2BankPropertiesIndex INTEGER, rPDU2BankPropertiesModule INTEGER, rPDU2BankPropertiesNumber INTEGER, rPDU2BankPropertiesPhaseLayout Rpdu2OutletPhaseLayoutType, rPDU2BankPropertiesBreakerRating INTEGER } -- 1.3.6.1.4.1.318.1.1.26.8.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.8.2.1.1 rPDU2BankPropertiesIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU bank properties table entry" ::= { rPDU2BankPropertiesEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.8.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.8.2.1.2 rPDU2BankPropertiesModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2BankPropertiesEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.8.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.8.2.1.3 rPDU2BankPropertiesNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric bank ID" ::= { rPDU2BankPropertiesEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.8.2.1.4 -- 1.3.6.1.4.1.318.1.1.26.8.2.1.4 rPDU2BankPropertiesPhaseLayout OBJECT-TYPE SYNTAX Rpdu2OutletPhaseLayoutType ACCESS read-only STATUS mandatory DESCRIPTION "This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that bank outlets are wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that bank outlets are wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that bank outlets are wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that bank outlets are wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that bank outlets are wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that bank outlets are wired from Phase 3 to Phase 1." ::= { rPDU2BankPropertiesEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.8.2.1.5 -- 1.3.6.1.4.1.318.1.1.26.8.2.1.5 rPDU2BankPropertiesBreakerRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "If bank circuit breakers are present on the device, this OID will return the rating of the breaker in Amps." ::= { rPDU2BankPropertiesEntry 5 } -- rPDU2 Bank Status -- 1.3.6.1.4.1.318.1.1.26.8.3 -- 1.3.6.1.4.1.318.1.1.26.8.3 rPDU2BankStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2BankStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU bank status data" ::= { rPDU2Bank 3 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1 -- 1.3.6.1.4.1.318.1.1.26.8.3.1 rPDU2BankStatusEntry OBJECT-TYPE SYNTAX RPDU2BankStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status data from currently queried Rack PDU bank" INDEX { rPDU2BankStatusIndex } ::= { rPDU2BankStatusTable 1 } RPDU2BankStatusEntry ::= SEQUENCE { rPDU2BankStatusIndex INTEGER, rPDU2BankStatusModule INTEGER, rPDU2BankStatusNumber INTEGER, rPDU2BankStatusLoadState INTEGER, rPDU2BankStatusCurrent INTEGER, rPDU2BankStatusPeakCurrent INTEGER, rPDU2BankStatusPeakCurrentTimestamp DisplayString, rPDU2BankStatusPeakCurrentStartTime DisplayString, rPDU2BankStatusVoltage INTEGER, rPDU2BankStatusPower INTEGER, rPDU2BankStatusEnergy INTEGER } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.1 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.1 rPDU2BankStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU bank status table entry" ::= { rPDU2BankStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.2 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.2 rPDU2BankStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2BankStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.3 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.3 rPDU2BankStatusNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric bank ID" ::= { rPDU2BankStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.4 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.4 rPDU2BankStatusLoadState OBJECT-TYPE SYNTAX INTEGER { lowLoad(1), normal(2), nearOverload(3), overload(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the present load status of the Rack PDU bank being queried" ::= { rPDU2BankStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.5 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.5 rPDU2BankStatusCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried" ::= { rPDU2BankStatusEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.6 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.6 rPDU2BankStatusPeakCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The peak current of the Rack PDU bank load in tenths of Amps" ::= { rPDU2BankStatusEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.7 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.7 rPDU2BankStatusPeakCurrentTimestamp OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time the bank peak current occurred" ::= { rPDU2BankStatusEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.8.3.1.8 -- 1.3.6.1.4.1.318.1.1.26.8.3.1.8 rPDU2BankStatusPeakCurrentStartTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time of the last bank peak current reset" ::= { rPDU2BankStatusEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.9 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.9 rPDU2BankStatusVoltage OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the Voltage, in Volts, of the Rack PDU bank being queried. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2BankStatusEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.10 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.10 rPDU2BankStatusPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the load power, in hundredths of kilowatts (kW), consumed on the RackPDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2BankStatusEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.6.3.1.11 -- 1.3.6.1.4.1.318.1.1.26.6.3.1.11 rPDU2BankStatusEnergy OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A user resettable energy meter measuring Rack PDU phase load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2BankStatusEntry 11 } -- rPDU2 Outlet Data -- 1.3.6.1.4.1.318.1.1.26.9 -- 1.3.6.1.4.1.318.1.1.26.9 rPDU2Outlet OBJECT IDENTIFIER ::= { rPDU2 9 } -- rPDU2 Switched Outlet Data -- 1.3.6.1.4.1.318.1.1.26.9.1 -- 1.3.6.1.4.1.318.1.1.26.9.1 rPDU2OutletSwitchedTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of switched outlets on connected Rack PDUs" ::= { rPDU2Outlet 1 } -- 1.3.6.1.4.1.318.1.1.26.9.2 -- 1.3.6.1.4.1.318.1.1.26.9.2 rPDU2OutletSwitched OBJECT IDENTIFIER ::= { rPDU2Outlet 2 } -- rPDU2 Switched Outlet Config -- 1.3.6.1.4.1.318.1.1.26.9.2.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.1 rPDU2OutletSwitchedConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2OutletSwitchedConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU switched outlet configuration data" ::= { rPDU2OutletSwitched 1 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1 rPDU2OutletSwitchedConfigEntry OBJECT-TYPE SYNTAX RPDU2OutletSwitchedConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from currently queried Rack PDU switched outlet" INDEX { rPDU2OutletSwitchedConfigIndex } ::= { rPDU2OutletSwitchedConfigTable 1 } RPDU2OutletSwitchedConfigEntry ::= SEQUENCE { rPDU2OutletSwitchedConfigIndex INTEGER, rPDU2OutletSwitchedConfigModule INTEGER, rPDU2OutletSwitchedConfigName DisplayString, rPDU2OutletSwitchedConfigNumber INTEGER, rPDU2OutletSwitchedConfigPowerOnTime INTEGER, rPDU2OutletSwitchedConfigPowerOffTime INTEGER, rPDU2OutletSwitchedConfigRebootDuration INTEGER, rPDU2OutletSwitchedConfigExternalLink DisplayString } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.1 rPDU2OutletSwitchedConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU switched outlet configuration table entry" ::= { rPDU2OutletSwitchedConfigEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.2 rPDU2OutletSwitchedConfigModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2OutletSwitchedConfigEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.3 rPDU2OutletSwitchedConfigName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The user-defined switched outlet ID string" ::= { rPDU2OutletSwitchedConfigEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.4 rPDU2OutletSwitchedConfigNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric switched outlet ID" ::= { rPDU2OutletSwitchedConfigEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.5 rPDU2OutletSwitchedConfigPowerOnTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of delay, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. Range -1...7200 where -1 = Never power on, 0 = immediate power on, and 1-7200 = seconds to delay." ::= { rPDU2OutletSwitchedConfigEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.6 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.6 rPDU2OutletSwitchedConfigPowerOffTime OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "The amount of time, in seconds, this outlet will delay powering off. Range -1...7200 where -1 = Never power off, 0 = immediate power off, and 1-7200 = seconds to delay." ::= { rPDU2OutletSwitchedConfigEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.7 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.7 rPDU2OutletSwitchedConfigRebootDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "After turning power off during a reboot sequence, the amount of time to wait before turning power to this outlet back on. Range 5-60 seconds delay." ::= { rPDU2OutletSwitchedConfigEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.8 -- 1.3.6.1.4.1.318.1.1.26.9.2.1.1.8 rPDU2OutletSwitchedConfigExternalLink OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications, drivers, etc." ::= { rPDU2OutletSwitchedConfigEntry 8 } -- rPDU2 Switched Outlet Config -- 1.3.6.1.4.1.318.1.1.26.9.2.2 -- 1.3.6.1.4.1.318.1.1.26.9.2.2 rPDU2OutletSwitchedPropertiesTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2OutletSwitchedPropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU switched outlet properties" ::= { rPDU2OutletSwitched 2 } -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1 rPDU2OutletSwitchedPropertiesEntry OBJECT-TYPE SYNTAX RPDU2OutletSwitchedPropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Properties of the currently queried Rack PDU switched outlet" INDEX { rPDU2OutletSwitchedPropertiesIndex } ::= { rPDU2OutletSwitchedPropertiesTable 1 } RPDU2OutletSwitchedPropertiesEntry ::= SEQUENCE { rPDU2OutletSwitchedPropertiesIndex INTEGER, rPDU2OutletSwitchedPropertiesModule INTEGER, rPDU2OutletSwitchedPropertiesName DisplayString, rPDU2OutletSwitchedPropertiesNumber INTEGER, rPDU2OutletSwitchedPropertiesPhaseLayout Rpdu2OutletPhaseLayoutType, rPDU2OutletSwitchedPropertiesBank INTEGER } -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.1 rPDU2OutletSwitchedPropertiesIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU switched outlet properties table entry" ::= { rPDU2OutletSwitchedPropertiesEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.2 rPDU2OutletSwitchedPropertiesModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2OutletSwitchedPropertiesEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.3 rPDU2OutletSwitchedPropertiesName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined switched outlet ID string" ::= { rPDU2OutletSwitchedPropertiesEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.4 -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.4 rPDU2OutletSwitchedPropertiesNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric switched outlet ID" ::= { rPDU2OutletSwitchedPropertiesEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.5 -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.5 rPDU2OutletSwitchedPropertiesPhaseLayout OBJECT-TYPE SYNTAX Rpdu2OutletPhaseLayoutType ACCESS read-only STATUS mandatory DESCRIPTION "This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1." ::= { rPDU2OutletSwitchedPropertiesEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.6 -- 1.3.6.1.4.1.318.1.1.26.9.2.2.1.6 rPDU2OutletSwitchedPropertiesBank OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric bank ID" ::= { rPDU2OutletSwitchedPropertiesEntry 6 } -- rPDU2 Switched Outlet Status -- 1.3.6.1.4.1.318.1.1.26.9.2.3 -- 1.3.6.1.4.1.318.1.1.26.9.2.3 rPDU2OutletSwitchedStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2OutletSwitchedStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU switched outlet status information" ::= { rPDU2OutletSwitched 3 } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1 rPDU2OutletSwitchedStatusEntry OBJECT-TYPE SYNTAX RPDU2OutletSwitchedStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status information for currently queried Rack PDU switched outlet" INDEX { rPDU2OutletSwitchedStatusIndex } ::= { rPDU2OutletSwitchedStatusTable 1 } RPDU2OutletSwitchedStatusEntry ::= SEQUENCE { rPDU2OutletSwitchedStatusIndex INTEGER, rPDU2OutletSwitchedStatusModule INTEGER, rPDU2OutletSwitchedStatusName DisplayString, rPDU2OutletSwitchedStatusNumber INTEGER, rPDU2OutletSwitchedStatusState INTEGER, rPDU2OutletSwitchedStatusCommandPending INTEGER, rPDU2OutletSwitchedStatusExternalLink DisplayString } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.1 rPDU2OutletSwitchedStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU switched outlet status information table entry" ::= { rPDU2OutletSwitchedStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.2 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.2 rPDU2OutletSwitchedStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2OutletSwitchedStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.3 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.3 rPDU2OutletSwitchedStatusName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined switched outlet ID string" ::= { rPDU2OutletSwitchedStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.4 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.4 rPDU2OutletSwitchedStatusNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric switched outlet ID" ::= { rPDU2OutletSwitchedStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.5 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.5 rPDU2OutletSwitchedStatusState OBJECT-TYPE SYNTAX INTEGER { off(1), on(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the present switch state of the Rack PDU switched outlet being queried" ::= { rPDU2OutletSwitchedStatusEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.6 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.6 rPDU2OutletSwitchedStatusCommandPending OBJECT-TYPE SYNTAX INTEGER { commandPending(1), noCommandPending(2), commandPendingUnknown(3) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates whether or not the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition." ::= { rPDU2OutletSwitchedStatusEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.7 -- 1.3.6.1.4.1.318.1.1.26.9.2.3.1.7 rPDU2OutletSwitchedStatusExternalLink OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web browser." ::= { rPDU2OutletSwitchedStatusEntry 7 } -- rPDU2 Switched Outlet Control -- 1.3.6.1.4.1.318.1.1.26.9.2.4 -- 1.3.6.1.4.1.318.1.1.26.9.2.4 rPDU2OutletSwitchedControlTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2OutletSwitchedControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU switched outlet control data" ::= { rPDU2OutletSwitched 4 } -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1 rPDU2OutletSwitchedControlEntry OBJECT-TYPE SYNTAX RPDU2OutletSwitchedControlEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Control data for currently queried Rack PDU switched outlet" INDEX { rPDU2OutletSwitchedControlIndex } ::= { rPDU2OutletSwitchedControlTable 1 } RPDU2OutletSwitchedControlEntry ::= SEQUENCE { rPDU2OutletSwitchedControlIndex INTEGER, rPDU2OutletSwitchedControlModule INTEGER, rPDU2OutletSwitchedControlName DisplayString, rPDU2OutletSwitchedControlNumber INTEGER, rPDU2OutletSwitchedControlCommand INTEGER } -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.1 rPDU2OutletSwitchedControlIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU switched outlet control data table entry" ::= { rPDU2OutletSwitchedControlEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.2 -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.2 rPDU2OutletSwitchedControlModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2OutletSwitchedControlEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.3 -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.3 rPDU2OutletSwitchedControlName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined switched outlet ID string" ::= { rPDU2OutletSwitchedControlEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.4 -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.4 rPDU2OutletSwitchedControlNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric switched outlet ID" ::= { rPDU2OutletSwitchedControlEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.5 -- 1.3.6.1.4.1.318.1.1.26.9.2.4.1.5 rPDU2OutletSwitchedControlCommand OBJECT-TYPE SYNTAX INTEGER { immediateOn(1), immediateOff(2), immediateReboot(3), outletUnknown(4), delayedOn(5), delayedOff(6), delayedReboot(7), cancelPendingCommand(8) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will cause the Switched Rack PDU to perform an immediateOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (5) will turn the outlet on after the rPDU2OutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (6) will turn the outlet off after the rPDU2OutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (7) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (8) will cause any pending command to this outlet to be cancelled." ::= { rPDU2OutletSwitchedControlEntry 5 } -- rPDU2 Metered Outlet Data -- 1.3.6.1.4.1.318.1.1.26.9.3 -- 1.3.6.1.4.1.318.1.1.26.9.3 rPDU2OutletMeteredTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of metered outlets on connect Rack PDUs" ::= { rPDU2Outlet 3 } -- 1.3.6.1.4.1.318.1.1.26.9.4 -- 1.3.6.1.4.1.318.1.1.26.9.4 rPDU2OutletMetered OBJECT IDENTIFIER ::= { rPDU2Outlet 4 } -- rPDU2 Metered Outlet Config -- 1.3.6.1.4.1.318.1.1.26.9.4.1 -- 1.3.6.1.4.1.318.1.1.26.9.4.1 rPDU2OutletMeteredConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2OutletMeteredConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU metered outlet configuration data" ::= { rPDU2OutletMetered 1 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1 rPDU2OutletMeteredConfigEntry OBJECT-TYPE SYNTAX RPDU2OutletMeteredConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from currently queried Rack PDU metered outlet" INDEX { rPDU2OutletMeteredConfigIndex } ::= { rPDU2OutletMeteredConfigTable 1 } RPDU2OutletMeteredConfigEntry ::= SEQUENCE { rPDU2OutletMeteredConfigIndex INTEGER, rPDU2OutletMeteredConfigModule INTEGER, rPDU2OutletMeteredConfigName DisplayString, rPDU2OutletMeteredConfigNumber INTEGER, rPDU2OutletMeteredConfigLowLoadCurrentThreshold INTEGER, rPDU2OutletMeteredConfigNearOverloadCurrentThreshold INTEGER, rPDU2OutletMeteredConfigOverloadCurrentThreshold INTEGER, rPDU2OutletMeteredConfigExternalLink DisplayString } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.1 rPDU2OutletMeteredConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU metered outlet configuration table entry" ::= { rPDU2OutletMeteredConfigEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.2 rPDU2OutletMeteredConfigModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2OutletMeteredConfigEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.3 rPDU2OutletMeteredConfigName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The user-defined metered outlet ID string" ::= { rPDU2OutletMeteredConfigEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.4 rPDU2OutletMeteredConfigNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric switched outlet ID" ::= { rPDU2OutletMeteredConfigEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.5 rPDU2OutletMeteredConfigLowLoadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined low load outlet current threshold in Watts" ::= { rPDU2OutletMeteredConfigEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.6 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.6 rPDU2OutletMeteredConfigNearOverloadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined near outlet overload warning threshold in Watts" ::= { rPDU2OutletMeteredConfigEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.7 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.7 rPDU2OutletMeteredConfigOverloadCurrentThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "User-defined outlet overload current threshold in Watts" ::= { rPDU2OutletMeteredConfigEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.8 -- 1.3.6.1.4.1.318.1.1.26.9.4.1.1.8 rPDU2OutletMeteredConfigExternalLink OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications, drivers, etc." ::= { rPDU2OutletMeteredConfigEntry 8 } -- rPDU2 Metered Outlet Properties -- 1.3.6.1.4.1.318.1.1.26.9.4.2 -- 1.3.6.1.4.1.318.1.1.26.9.4.2 rPDU2OutletMeteredPropertiesTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2OutletMeteredPropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU metered outlet properties" ::= { rPDU2OutletMetered 2 } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1 rPDU2OutletMeteredPropertiesEntry OBJECT-TYPE SYNTAX RPDU2OutletMeteredPropertiesEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Properties of currently queried Rack PDU metered outlet" INDEX { rPDU2OutletMeteredPropertiesIndex } ::= { rPDU2OutletMeteredPropertiesTable 1 } RPDU2OutletMeteredPropertiesEntry ::= SEQUENCE { rPDU2OutletMeteredPropertiesIndex INTEGER, rPDU2OutletMeteredPropertiesModule INTEGER, rPDU2OutletMeteredPropertiesName DisplayString, rPDU2OutletMeteredPropertiesNumber INTEGER, rPDU2OutletMeteredPropertiesLayout Rpdu2OutletPhaseLayoutType, rPDU2OutletMeteredPropertiesPowerRating INTEGER, rPDU2OutletMeteredPropertiesBank INTEGER } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.1 rPDU2OutletMeteredPropertiesIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU metered properties table entry" ::= { rPDU2OutletMeteredPropertiesEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.2 rPDU2OutletMeteredPropertiesModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2OutletMeteredPropertiesEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.3 rPDU2OutletMeteredPropertiesName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined metered outlet ID string" ::= { rPDU2OutletMeteredPropertiesEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.4 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.4 rPDU2OutletMeteredPropertiesNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric metered outlet ID" ::= { rPDU2OutletMeteredPropertiesEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.5 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.5 rPDU2OutletMeteredPropertiesLayout OBJECT-TYPE SYNTAX Rpdu2OutletPhaseLayoutType ACCESS read-only STATUS mandatory DESCRIPTION "This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1." ::= { rPDU2OutletMeteredPropertiesEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.6 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.6 rPDU2OutletMeteredPropertiesPowerRating OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Maximum power rating of Rack PDU metered outlet" ::= { rPDU2OutletMeteredPropertiesEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.7 -- 1.3.6.1.4.1.318.1.1.26.9.4.2.1.7 rPDU2OutletMeteredPropertiesBank OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "This outlet's numeric bank ID" ::= { rPDU2OutletMeteredPropertiesEntry 7 } -- rPDU2 Metered Outlet Status -- 1.3.6.1.4.1.318.1.1.26.9.4.3 -- 1.3.6.1.4.1.318.1.1.26.9.4.3 rPDU2OutletMeteredStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2OutletMeteredStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU metered outlet status data" ::= { rPDU2OutletMetered 3 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1 rPDU2OutletMeteredStatusEntry OBJECT-TYPE SYNTAX RPDU2OutletMeteredStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status data from currently queried Rack PDU metered outlet" INDEX { rPDU2OutletMeteredStatusIndex } ::= { rPDU2OutletMeteredStatusTable 1 } RPDU2OutletMeteredStatusEntry ::= SEQUENCE { rPDU2OutletMeteredStatusIndex INTEGER, rPDU2OutletMeteredStatusModule INTEGER, rPDU2OutletMeteredStatusName DisplayString, rPDU2OutletMeteredStatusNumber INTEGER, rPDU2OutletMeteredStatusState INTEGER, rPDU2OutletMeteredStatusCurrent INTEGER, rPDU2OutletMeteredStatusPower INTEGER, rPDU2OutletMeteredStatusPeakPower INTEGER, rPDU2OutletMeteredStatusPeakPowerTimestamp DisplayString, rPDU2OutletMeteredStatusPeakPowerStartTime DisplayString, rPDU2OutletMeteredStatusEnergy INTEGER, rPDU2OutletMeteredStatusReceptacleType DisplayString, rPDU2OutletMeteredStatusExternalLink DisplayString, rPDU2OutletMeteredStatusPowerFactor INTEGER } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.1 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.1 rPDU2OutletMeteredStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU metered status table entry" ::= { rPDU2OutletMeteredStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.2 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.2 rPDU2OutletMeteredStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2OutletMeteredStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.3 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.3 rPDU2OutletMeteredStatusName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined metered outlet ID string" ::= { rPDU2OutletMeteredStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.4 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.4 rPDU2OutletMeteredStatusNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The numeric metered outlet ID" ::= { rPDU2OutletMeteredStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.5 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.5 rPDU2OutletMeteredStatusState OBJECT-TYPE SYNTAX INTEGER { lowLoad(1), normal(2), nearOverload(3), overload(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the present load status of the Rack PDU metered outlet being queried" ::= { rPDU2OutletMeteredStatusEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.6 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.6 rPDU2OutletMeteredStatusCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the current draw, in tenths of Amps, of the load on the Rack PDU outlet being queried" ::= { rPDU2OutletMeteredStatusEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.7 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.7 rPDU2OutletMeteredStatusPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the power draw of the load on the Rack PDU outlet being queried" ::= { rPDU2OutletMeteredStatusEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.8 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.8 rPDU2OutletMeteredStatusPeakPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the peak power load draw on the Rack PDU outlet being queried" ::= { rPDU2OutletMeteredStatusEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.9 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.9 rPDU2OutletMeteredStatusPeakPowerTimestamp OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time that this metered outlet's peak power consumption occurred" ::= { rPDU2OutletMeteredStatusEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.10 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.10 rPDU2OutletMeteredStatusPeakPowerStartTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the start date and time that this metered outlet began recording peak power observations" ::= { rPDU2OutletMeteredStatusEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.11 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.11 rPDU2OutletMeteredStatusEnergy OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours" ::= { rPDU2OutletMeteredStatusEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.12 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.12 rPDU2OutletMeteredStatusReceptacleType OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates receptacle type for the outlet." ::= { rPDU2OutletMeteredStatusEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.13 -- 1.3.6.1.4.1.318.1.1.26.9.4.3.1.13 rPDU2OutletMeteredStatusExternalLink OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletMeteredConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web browser." ::= { rPDU2OutletMeteredStatusEntry 13 } -- 1.3.6.1.4.1.318.1.1.26.4.3.1.14 rPDU2OutletMeteredStatusPowerFactor OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The power factor of the Rack PDU outlet in hundredths. Models that do not support this feature will respond to this OID with a value of -1." ::= { rPDU2OutletMeteredStatusEntry 14 } -- rPDU2 Sensor Data -- 1.3.6.1.4.1.318.1.1.26.10 -- 1.3.6.1.4.1.318.1.1.26.10 rPDU2Sensor OBJECT IDENTIFIER ::= { rPDU2 10 } -- rPDU2 Temperature and Humidity Sensor Data -- 1.3.6.1.4.1.318.1.1.26.10.1 -- 1.3.6.1.4.1.318.1.1.26.10.1 rPDU2SensorTempHumidityTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of connected temperature-humidity sensors" ::= { rPDU2Sensor 1 } -- 1.3.6.1.4.1.318.1.1.26.10.2 -- 1.3.6.1.4.1.318.1.1.26.10.2 rPDU2SensorTempHumidity OBJECT IDENTIFIER ::= { rPDU2Sensor 2 } -- rPDU2 Temperature and Humidity Sensor Config -- 1.3.6.1.4.1.318.1.1.26.10.2.1 -- 1.3.6.1.4.1.318.1.1.26.10.2.1 rPDU2SensorTempHumidityConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2SensorTempHumidityConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of temperature-humidity sensor configuration data" ::= { rPDU2SensorTempHumidity 1 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1 rPDU2SensorTempHumidityConfigEntry OBJECT-TYPE SYNTAX RPDU2SensorTempHumidityConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from temperature-humidity sensor being queried" INDEX { rPDU2SensorTempHumidityConfigIndex } ::= { rPDU2SensorTempHumidityConfigTable 1 } RPDU2SensorTempHumidityConfigEntry ::= SEQUENCE { rPDU2SensorTempHumidityConfigIndex INTEGER, rPDU2SensorTempHumidityConfigModule INTEGER, rPDU2SensorTempHumidityConfigName DisplayString, rPDU2SensorTempHumidityConfigNumber INTEGER, rPDU2SensorTempHumidityConfigTemperatureAlarmEnable INTEGER, rPDU2SensorTempHumidityConfigHumidityAlarmEnable INTEGER, rPDU2SensorTempHumidityConfigTempMaxThreshF INTEGER, rPDU2SensorTempHumidityConfigTempHighThreshF INTEGER, rPDU2SensorTempHumidityConfigTempHysteresisF INTEGER, rPDU2SensorTempHumidityConfigTempMaxThreshC INTEGER, rPDU2SensorTempHumidityConfigTempHighThreshC INTEGER, rPDU2SensorTempHumidityConfigTempHysteresisC INTEGER, rPDU2SensorTempHumidityConfigHumidityLowThresh INTEGER, rPDU2SensorTempHumidityConfigHumidityMinThresh INTEGER, rPDU2SensorTempHumidityConfigHumidityHysteresis INTEGER, rPDU2SensorTempHumidityConfigTempPeakReset INTEGER } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.1 rPDU2SensorTempHumidityConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the temperature-humidity sensor configuration data table entry" ::= { rPDU2SensorTempHumidityConfigEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.2 rPDU2SensorTempHumidityConfigModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2SensorTempHumidityConfigEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.3 rPDU2SensorTempHumidityConfigName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The user-defined temperature-humidity sensor ID string" ::= { rPDU2SensorTempHumidityConfigEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.4 rPDU2SensorTempHumidityConfigNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The temperature-humidity sensor numeric ID" ::= { rPDU2SensorTempHumidityConfigEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.5 rPDU2SensorTempHumidityConfigTemperatureAlarmEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the temperature alarm enable." ::= { rPDU2SensorTempHumidityConfigEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.6 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.6 rPDU2SensorTempHumidityConfigHumidityAlarmEnable OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidity alarm enable." ::= { rPDU2SensorTempHumidityConfigEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.7 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.7 rPDU2SensorTempHumidityConfigTempMaxThreshF OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshF will result in an error." ::= { rPDU2SensorTempHumidityConfigEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.8 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.8 rPDU2SensorTempHumidityConfigTempHighThreshF OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor high temperature warning alarm threshold in Fahrenheit. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshF will result in an error." ::= { rPDU2SensorTempHumidityConfigEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.9 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.9 rPDU2SensorTempHumidityConfigTempHysteresisF OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor temperature hysteresis setting in Fahrenheit" ::= { rPDU2SensorTempHumidityConfigEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.10 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.10 rPDU2SensorTempHumidityConfigTempMaxThreshC OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshC will result in an error." ::= { rPDU2SensorTempHumidityConfigEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.11 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.11 rPDU2SensorTempHumidityConfigTempHighThreshC OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor high temperature warning alarm threshold in Celsius. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshC will result in an error." ::= { rPDU2SensorTempHumidityConfigEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.12 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.12 rPDU2SensorTempHumidityConfigTempHysteresisC OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor temperature hysteresis setting in Celsius" ::= { rPDU2SensorTempHumidityConfigEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.13 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.13 rPDU2SensorTempHumidityConfigHumidityLowThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor low humidity warning alarm threshold in percent relative humidity. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigHumidityMinThresh will result in an error. Must be between 15% and 90%" ::= { rPDU2SensorTempHumidityConfigEntry 13 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.14 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.14 rPDU2SensorTempHumidityConfigHumidityMinThresh OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor minimum humidity alarm threshold in percent relative humidity. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigHumidityLowThresh will result in an error. Must be between 15% and 90%" ::= { rPDU2SensorTempHumidityConfigEntry 14 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.15 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.15 rPDU2SensorTempHumidityConfigHumidityHysteresis OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Sensor humidity hysteresis setting in percent relative humidity" ::= { rPDU2SensorTempHumidityConfigEntry 15 } -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.16 -- 1.3.6.1.4.1.318.1.1.26.10.2.1.1.16 rPDU2SensorTempHumidityConfigTempPeakReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the existing peak temperature to be replaced by the present temperature reading. Getting this OID will do nothing and return the noOperation(1) value." ::= { rPDU2SensorTempHumidityConfigEntry 16 } -- rPDU2 Temperature and Humidity Sensor Status -- 1.3.6.1.4.1.318.1.1.26.10.2.2 -- 1.3.6.1.4.1.318.1.1.26.10.2.2 rPDU2SensorTempHumidityStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2SensorTempHumidityStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of temperature-humidity sensor status data" ::= { rPDU2SensorTempHumidity 2 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1 rPDU2SensorTempHumidityStatusEntry OBJECT-TYPE SYNTAX RPDU2SensorTempHumidityStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status information from temperature-humidity sensor being queried" INDEX { rPDU2SensorTempHumidityStatusIndex } ::= { rPDU2SensorTempHumidityStatusTable 1 } RPDU2SensorTempHumidityStatusEntry ::= SEQUENCE { rPDU2SensorTempHumidityStatusIndex INTEGER, rPDU2SensorTempHumidityStatusModule INTEGER, rPDU2SensorTempHumidityStatusName DisplayString, rPDU2SensorTempHumidityStatusNumber INTEGER, rPDU2SensorTempHumidityStatusType INTEGER, rPDU2SensorTempHumidityStatusCommStatus INTEGER, rPDU2SensorTempHumidityStatusTempF INTEGER, rPDU2SensorTempHumidityStatusTempC INTEGER, rPDU2SensorTempHumidityStatusTempStatus INTEGER, rPDU2SensorTempHumidityStatusRelativeHumidity INTEGER, rPDU2SensorTempHumidityStatusHumidityStatus INTEGER, rPDU2SensorTempHumidityStatusTempPeakF INTEGER, rPDU2SensorTempHumidityStatusTempPeakC INTEGER, rPDU2SensorTempHumidityStatusTempPeakTimestamp DisplayString, rPDU2SensorTempHumidityStatusTempPeakStartTime DisplayString } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1 rPDU2SensorTempHumidityStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the temperature-humidity status data table entry" ::= { rPDU2SensorTempHumidityStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2 rPDU2SensorTempHumidityStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2SensorTempHumidityStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3 rPDU2SensorTempHumidityStatusName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined temperature-humidity sensor ID string" ::= { rPDU2SensorTempHumidityStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4 rPDU2SensorTempHumidityStatusNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The temperature-humidity sensor numeric ID" ::= { rPDU2SensorTempHumidityStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5 rPDU2SensorTempHumidityStatusType OBJECT-TYPE SYNTAX INTEGER { temperatureOnly(1), temperatureHumidity(2), commsLost(3), notInstalled(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The type of the sensor" ::= { rPDU2SensorTempHumidityStatusEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6 rPDU2SensorTempHumidityStatusCommStatus OBJECT-TYPE SYNTAX INTEGER { notInstalled(1), commsOK(2), commsLost(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The communications status of the sensor" ::= { rPDU2SensorTempHumidityStatusEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7 rPDU2SensorTempHumidityStatusTempF OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Sensor temperature reading in tenths of degrees Fahrenheit" ::= { rPDU2SensorTempHumidityStatusEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8 rPDU2SensorTempHumidityStatusTempC OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Sensor temperature reading in tenths of degrees Celsius" ::= { rPDU2SensorTempHumidityStatusEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9 rPDU2SensorTempHumidityStatusTempStatus OBJECT-TYPE SYNTAX INTEGER { notPresent(1), belowMin(2), belowLow(3), normal(4), aboveHigh(5), aboveMax(6) } ACCESS read-only STATUS mandatory DESCRIPTION "This OID reports the current state of the temperature probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured temperature lies below the minimum threshold. A belowLow (3) response indicates that the probe is present and its measured temperature lies below the low threshold. A normal (4) response indicates that the probe is present and its measured temperature lies within all temperature thresholds. An aboveHigh (5) response indicates that the probe is present and is measuring a temperature above the high threshold. An aboveMax (6) response indicates that the probe is present and is measuring a temperature above the max threshold." ::= { rPDU2SensorTempHumidityStatusEntry 9 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10 rPDU2SensorTempHumidityStatusRelativeHumidity OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Sensor humidity reading in percent relative humidity" ::= { rPDU2SensorTempHumidityStatusEntry 10 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11 rPDU2SensorTempHumidityStatusHumidityStatus OBJECT-TYPE SYNTAX INTEGER { notPresent(1), belowMin(2), belowLow(3), normal(4), aboveHigh(5), aboveMax(6) } ACCESS read-only STATUS mandatory DESCRIPTION "This OID reports the current state of the humidity probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured humidity lies below the minimum threshold. A belowLow (3) response indicates that the probe is present and its measured humidity lies below the low threshold. A normal (4) response indicates that the probe is present and its measured humidity lies within all humidity thresholds. An aboveHigh (5) response indicates that the probe is present and is measuring a humidity above the high threshold. An aboveMax (6) response indicates that the probe is present and is measuring a humidity above the max threshold." ::= { rPDU2SensorTempHumidityStatusEntry 11 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12 rPDU2SensorTempHumidityStatusTempPeakF OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Sensor peak temperature in tenths of degrees Fahrenheit" ::= { rPDU2SensorTempHumidityStatusEntry 12 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13 rPDU2SensorTempHumidityStatusTempPeakC OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Sensor peak temperature in tenths of degrees Celsius" ::= { rPDU2SensorTempHumidityStatusEntry 13 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14 rPDU2SensorTempHumidityStatusTempPeakTimestamp OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time that the peak temperature occurred" ::= { rPDU2SensorTempHumidityStatusEntry 14 } -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15 -- 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15 rPDU2SensorTempHumidityStatusTempPeakStartTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the date and time of the last temperature peak reset" ::= { rPDU2SensorTempHumidityStatusEntry 15 } -- rPDU2 Discrete Sensor Data -- 1.3.6.1.4.1.318.1.1.26.10.3 -- 1.3.6.1.4.1.318.1.1.26.10.3 rPDU2SensorDiscreteTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of connected discrete sensors" ::= { rPDU2Sensor 3 } -- 1.3.6.1.4.1.318.1.1.26.10.4 -- 1.3.6.1.4.1.318.1.1.26.10.4 rPDU2SensorDiscrete OBJECT IDENTIFIER ::= { rPDU2Sensor 4 } -- rPDU2 Discrete Sensor Config -- 1.3.6.1.4.1.318.1.1.26.10.4.1 -- 1.3.6.1.4.1.318.1.1.26.10.4.1 rPDU2SensorDiscreteConfigTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2SensorDiscreteConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of discrete sensor configuration data" ::= { rPDU2SensorDiscrete 1 } -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1 -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1 rPDU2SensorDiscreteConfigEntry OBJECT-TYPE SYNTAX RPDU2SensorDiscreteConfigEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Configuration data from discreste sensor being queried" INDEX { rPDU2SensorDiscreteConfigIndex } ::= { rPDU2SensorDiscreteConfigTable 1 } RPDU2SensorDiscreteConfigEntry ::= SEQUENCE { rPDU2SensorDiscreteConfigIndex INTEGER, rPDU2SensorDiscreteConfigModule INTEGER, rPDU2SensorDiscreteConfigName DisplayString, rPDU2SensorDiscreteConfigNumber INTEGER, rPDU2SensorDiscreteConfigNormalState INTEGER, rPDU2SensorDiscreteConfigAbnormalSeverity INTEGER } -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.1 rPDU2SensorDiscreteConfigIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the discrete sensor configuration data table entry" ::= { rPDU2SensorDiscreteConfigEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.2 rPDU2SensorDiscreteConfigModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2SensorDiscreteConfigEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.3 rPDU2SensorDiscreteConfigName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "The user-defined discrete sensor ID string" ::= { rPDU2SensorDiscreteConfigEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.4 rPDU2SensorDiscreteConfigNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The discrete sensor numeric ID" ::= { rPDU2SensorDiscreteConfigEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.5 rPDU2SensorDiscreteConfigNormalState OBJECT-TYPE SYNTAX INTEGER { normallyOpen(1), normallyClosed(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Indicates the normal state of the discrete input contact" ::= { rPDU2SensorDiscreteConfigEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.6 -- 1.3.6.1.4.1.318.1.1.26.10.4.1.1.6 rPDU2SensorDiscreteConfigAbnormalSeverity OBJECT-TYPE SYNTAX INTEGER { informational(1), warning(2), critical(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Indicates the severity of alarm triggered by abnormal discrete input contact state" ::= { rPDU2SensorDiscreteConfigEntry 6 } -- rPDU2 Discrete Sensor Status -- 1.3.6.1.4.1.318.1.1.26.10.4.2 -- 1.3.6.1.4.1.318.1.1.26.10.4.2 rPDU2SensorDiscreteStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2SensorDiscreteStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of discrete sensor status data" ::= { rPDU2SensorDiscrete 2 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1 rPDU2SensorDiscreteStatusEntry OBJECT-TYPE SYNTAX RPDU2SensorDiscreteStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status information from discrete sensor being queried" INDEX { rPDU2SensorDiscreteStatusIndex } ::= { rPDU2SensorDiscreteStatusTable 1 } RPDU2SensorDiscreteStatusEntry ::= SEQUENCE { rPDU2SensorDiscreteStatusIndex INTEGER, rPDU2SensorDiscreteStatusModule INTEGER, rPDU2SensorDiscreteStatusName DisplayString, rPDU2SensorDiscreteStatusNumber INTEGER, rPDU2SensorDiscreteStatusType INTEGER, rPDU2SensorDiscreteStatusCommStatus INTEGER, rPDU2SensorDiscreteStatusCurrentState INTEGER, rPDU2SensorDiscreteStatusAlarmState INTEGER } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.1 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.1 rPDU2SensorDiscreteStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the discrete sensor status data table entry" ::= { rPDU2SensorDiscreteStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.2 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.2 rPDU2SensorDiscreteStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2SensorDiscreteStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.3 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.3 rPDU2SensorDiscreteStatusName OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined discrete sensor ID string" ::= { rPDU2SensorDiscreteStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.4 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.4 rPDU2SensorDiscreteStatusNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The discrete sensor numeric ID" ::= { rPDU2SensorDiscreteStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.5 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.5 rPDU2SensorDiscreteStatusType OBJECT-TYPE SYNTAX INTEGER { notConnected(1), doorContactSensor(2), smokeSensor(3), motionDetector(4), vibrationSensor(5), dryContactSensor(6), spotLeakSensor(7) } ACCESS read-only STATUS mandatory DESCRIPTION "The type of discrete sensor currently being queried" ::= { rPDU2SensorDiscreteStatusEntry 5 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.6 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.6 rPDU2SensorDiscreteStatusCommStatus OBJECT-TYPE SYNTAX INTEGER { notInstalled(1), commsOK(2), commsLost(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The communications status of the sensor" ::= { rPDU2SensorDiscreteStatusEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.7 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.7 rPDU2SensorDiscreteStatusCurrentState OBJECT-TYPE SYNTAX INTEGER { open(1), closed(2), unknown(3) } ACCESS read-only STATUS mandatory DESCRIPTION "The current open/close state of the discrete sensor" ::= { rPDU2SensorDiscreteStatusEntry 7 } -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.8 -- 1.3.6.1.4.1.318.1.1.26.10.4.2.1.8 rPDU2SensorDiscreteStatusAlarmState OBJECT-TYPE SYNTAX INTEGER { normal(1), alarm(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Indicates alarm status of discrete sensor input" ::= { rPDU2SensorDiscreteStatusEntry 8 } -- 1.3.6.1.4.1.318.1.1.26.11 -- 1.3.6.1.4.1.318.1.1.26.11 rPDU2Group OBJECT IDENTIFIER ::= { rPDU2 11 } -- rPDU2 Total Rack PDU Network Port Sharing (NPS) group power and energy -- 1.3.6.1.4.1.318.1.1.26.11.1 -- 1.3.6.1.4.1.318.1.1.26.11.1 rPDU2GroupNumberOfDevices OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the number of Rack PDU devices contributing to the Network Port Sharing (NPS) group power and energy values. Queries to guest units in an NPS group are not applicable and will return 0." ::= { rPDU2Group 1 } -- 1.3.6.1.4.1.318.1.1.26.11.2 -- 1.3.6.1.4.1.318.1.1.26.11.2 rPDU2GroupTotalPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the total power consumption of the Rack PDU Network Port Sharing (NPS) group devices in hundredths of kilowatts. Queries to guest units in an NPS group are not applicable and will return 0." ::= { rPDU2Group 2 } -- 1.3.6.1.4.1.318.1.1.26.11.3 -- 1.3.6.1.4.1.318.1.1.26.11.3 rPDU2GroupTotalEnergy OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Getting this OID will return the total energy consumption of the Rack PDU Network Port Sharing (NPS) group devices in tenths of kilowatt-hours. To reset the energy meters for each of the Rack PDU devices that contribute to this value, see the rPDU2GroupEnergyReset OID. To view the start time for each of the Rack PDU device energy meters that contribute to this value, see the rPDU2DeviceStatusEnergyStartTime OID. Queries to guest units in an NPS group are not applicable and will return 0." ::= { rPDU2Group 3 } -- 1.3.6.1.4.1.318.1.1.26.11.4 -- 1.3.6.1.4.1.318.1.1.26.11.4 rPDU2GroupEnergyReset OBJECT-TYPE SYNTAX INTEGER { noOperation(1), reset(2), notSupported(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Network Port Sharing (NPS) group to be reset to zero. Each device in the Rack PDU group will also have its corresponding rPDU2DeviceStatusEnergyStartTime OID value updated. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature, as well as guest units in an NPS group, will respond to this OID with a value of notSupported (3). Attempts to set this OID in these units will fail." ::= { rPDU2Group 4 } -- rPDU2 Phase To Phase Status -- 1.3.6.1.4.1.318.1.1.26.12 -- 1.3.6.1.4.1.318.1.1.26.12 rPDU2PhaseToPhaseStatusTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of connected Rack PDU banks" ::= { rPDU2 12 } -- 1.3.6.1.4.1.318.1.1.26.13 -- 1.3.6.1.4.1.318.1.1.26.13 rPDU2PhaseToPhase OBJECT IDENTIFIER ::= { rPDU2 13 } -- 1.3.6.1.4.1.318.1.1.26.13.1 -- 1.3.6.1.4.1.318.1.1.26.13.1 rPDU2PhaseToPhaseStatusTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2PhaseToPhaseStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU phase to phase status data. This table is only applicable to SKUs that have phase to phase outputs." ::= { rPDU2PhaseToPhase 1 } -- 1.3.6.1.4.1.318.1.1.26.13.1.1 -- 1.3.6.1.4.1.318.1.1.26.13.1.1 rPDU2PhaseToPhaseStatusEntry OBJECT-TYPE SYNTAX RPDU2PhaseToPhaseStatusEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Status data from currently queried Rack PDU phase to phase outputs" INDEX { rPDU2PhaseToPhaseStatusIndex } ::= { rPDU2PhaseToPhaseStatusTable 1 } RPDU2PhaseToPhaseStatusEntry ::= SEQUENCE { rPDU2PhaseToPhaseStatusIndex INTEGER, rPDU2PhaseToPhaseStatusModule INTEGER, rPDU2PhaseToPhaseStatusVoltage1to2 INTEGER, rPDU2PhaseToPhaseStatusVoltage2to3 INTEGER, rPDU2PhaseToPhaseStatusVoltage3to1 INTEGER } -- 1.3.6.1.4.1.318.1.1.26.13.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.13.1.1.1 rPDU2PhaseToPhaseStatusIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU phase to phase status table entry" ::= { rPDU2PhaseToPhaseStatusEntry 1 } -- 1.3.6.1.4.1.318.1.1.26.13.1.1.2 -- 1.3.6.1.4.1.318.1.1.26.13.1.1.2 rPDU2PhaseToPhaseStatusModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2PhaseToPhaseStatusEntry 2 } -- 1.3.6.1.4.1.318.1.1.26.13.1.1.3 -- 1.3.6.1.4.1.318.1.1.26.13.1.1.3 rPDU2PhaseToPhaseStatusVoltage1to2 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the Voltage, in Volts, of the Rack PDU phase 1 to phase 2 output being queried" ::= { rPDU2PhaseToPhaseStatusEntry 3 } -- 1.3.6.1.4.1.318.1.1.26.13.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.13.1.1.4 rPDU2PhaseToPhaseStatusVoltage2to3 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the Voltage, in Volts, of the Rack PDU phase 2 to phase 3 output being queried" ::= { rPDU2PhaseToPhaseStatusEntry 4 } -- 1.3.6.1.4.1.318.1.1.26.13.1.1.5 -- 1.3.6.1.4.1.318.1.1.26.13.1.1.5 rPDU2PhaseToPhaseStatusVoltage3to1 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "Indicates the Voltage, in Volts, of the Rack PDU phase 3 to phase 2 output being queried" ::= { rPDU2PhaseToPhaseStatusEntry 5 } -- rPDU2 RCM -- 1.3.6.1.4.1.318.1.1.26.14 -- 1.3.6.1.4.1.318.1.1.26.14 rPDU2RCMTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of RCM" ::= { rPDU2 14 } -- 1.3.6.1.4.1.318.1.1.26.15 -- 1.3.6.1.4.1.318.1.1.26.15 rPDU2RCM OBJECT IDENTIFIER ::= { rPDU2 15 } -- 1.3.6.1.4.1.318.1.1.26.15.1 -- 1.3.6.1.4.1.318.1.1.26.15.1 rPDU2RCMTable OBJECT-TYPE SYNTAX SEQUENCE OF RPDU2RCMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A table of Rack PDU RCM." ::= { rPDU2RCM 1 } -- 1.3.6.1.4.1.318.1.1.26.15.1.1 -- 1.3.6.1.4.1.318.1.1.26.15.1.1 rPDU2RCMEntry OBJECT-TYPE SYNTAX RPDU2RCMEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "RCM data from currently queried Rack PDU" INDEX { rPDU2RCMIndex } ::= { rPDU2RCMTable 1 } RPDU2RCMEntry ::= SEQUENCE { rPDU2RCMIndex INTEGER, rPDU2RCMModule INTEGER, rPDU2RCMAlarmStatus INTEGER, rPDU2RCMCurrent INTEGER, rPDU2RCMSelfCheckCommand INTEGER, rPDU2RCMWarningThreshold INTEGER, rPDU2RCMAlarmThreshold INTEGER, rPDU2RCMSelfCheckPeriod INTEGER } -- 1.3.6.1.4.1.318.1.1.26.15.1.1.1 -- 1.3.6.1.4.1.318.1.1.26.15.1.1.1 rPDU2RCMIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index to the Rack PDU RCM table entry" ::= { rPDU2RCMEntry 1 } rPDU2RCMModule OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The user-defined Rack PDU numeric ID" ::= { rPDU2RCMEntry 2 } rPDU2RCMCurrent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "RCM RMS current. (mA)" ::= { rPDU2RCMEntry 3 } rPDU2RCMAlarmStatus OBJECT-TYPE SYNTAX INTEGER { abnormal(-1), normal(1), warning(2), alarm(3) } ACCESS read-write STATUS mandatory DESCRIPTION "RCM alarm status. Setting the selected variable to 1, will clear the over alarm. " ::= { rPDU2RCMEntry 4 } rPDU2RCMSelfCheckCommand OBJECT-TYPE SYNTAX INTEGER { featureNotAvailable(-1), success(1), failed(2), pending(3) } ACCESS read-write STATUS mandatory DESCRIPTION "Getting this variable will return the RCM self checking status, 1: featureNotAvailable(-1) 2: success(1) 3: failed(2) 4: pending(3). Setting any of the selected pdu's rcm's variable to 1, will immediately start RCM Self Checking for all rcm of this pdu. " ::= { rPDU2RCMEntry 5 } rPDU2RCMWarningThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Over Warning threshold of RCM current. (mA), threshold can be set in the range of 15-300mA, and must be lower or equal than Alarm threshold. " ::= { rPDU2RCMEntry 6 } -- 1.3.6.1.4.1.318.1.1.26.15.1.1.4 -- 1.3.6.1.4.1.318.1.1.26.15.1.1.4 rPDU2RCMAlarmThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Over Alarm threshold of RCM current. (mA), threshold can be set in the range of 15~300 mA, and must be higher or equal than Warning threshold. " ::= { rPDU2RCMEntry 7 } rPDU2RCMSelfCheckPeriod OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "RCM Self-Checking Period. (day) period can be set in the range of 1~365 days, the rcm period on a single pdu is the same, setting one of the selected pdu's rcm's period, will change all rcm's period of this pdu. " ::= { rPDU2RCMEntry 8 } -- 1.3.6.1.4.1.318.1.2 -- 1.3.6.1.4.1.318.1.2 software OBJECT IDENTIFIER ::= { products 2 } -- 1.3.6.1.4.1.318.1.2.1 -- 1.3.6.1.4.1.318.1.2.1 powerNetSubAgent OBJECT IDENTIFIER ::= { software 1 } -- 1.3.6.1.4.1.318.1.2.1.1 -- 1.3.6.1.4.1.318.1.2.1.1 powerNetSoftwareSystem OBJECT IDENTIFIER ::= { powerNetSubAgent 1 } -- the software group -- the powerNetSubAgent group -- the powerNetSoftwareSystem group -- 1.3.6.1.4.1.318.1.2.1.1.1 -- 1.3.6.1.4.1.318.1.2.1.1.1 powerNetSoftwareSystemDescription OBJECT-TYPE SYNTAX DisplayString (SIZE (0..79)) ACCESS read-only STATUS mandatory DESCRIPTION "A brief description of the PowerNet sub-agent." ::= { powerNetSoftwareSystem 1 } -- 1.3.6.1.4.1.318.1.2.1.1.2 -- 1.3.6.1.4.1.318.1.2.1.1.2 powerNetSoftwareOid OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-only STATUS mandatory DESCRIPTION "The object identifier of the PowerNet sub-agent." ::= { powerNetSoftwareSystem 2 } -- powerNetSmuxPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 1 } -- powerNetDPIPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 2 } -- 1.3.6.1.4.1.318.1.2.1.1.3 -- 1.3.6.1.4.1.318.1.2.1.1.3 powerNetSoftwareSystemUpTime OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS mandatory DESCRIPTION "The time that the sub-agent has been running." ::= { powerNetSoftwareSystem 3 } -- 1.3.6.1.4.1.318.1.2.1.2 -- 1.3.6.1.4.1.318.1.2.1.2 powerNetSoftwareConfig OBJECT IDENTIFIER ::= { powerNetSubAgent 2 } -- powerNetSoftwareConfig group -- 1.3.6.1.4.1.318.1.2.1.2.1 -- 1.3.6.1.4.1.318.1.2.1.2.1 powerNetSoftwareTableSize OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The number of software modules supporting the UPS." ::= { powerNetSoftwareConfig 1 } -- 1.3.6.1.4.1.318.1.2.1.2.2 -- 1.3.6.1.4.1.318.1.2.1.2.2 powerNetSoftwareTable OBJECT-TYPE SYNTAX SEQUENCE OF PowerNetSoftwareEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of the software monitoring the UPS." ::= { powerNetSoftwareConfig 2 } -- 1.3.6.1.4.1.318.1.2.1.2.2.1 -- 1.3.6.1.4.1.318.1.2.1.2.2.1 powerNetSoftwareEntry OBJECT-TYPE SYNTAX PowerNetSoftwareEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information on a software module." INDEX { moduleNumber } ::= { powerNetSoftwareTable 1 } PowerNetSoftwareEntry ::= SEQUENCE { moduleNumber INTEGER, moduleName DisplayString, moduleVersion DisplayString, moduleDate DisplayString } -- 1.3.6.1.4.1.318.1.2.1.2.2.1.1 -- 1.3.6.1.4.1.318.1.2.1.2.2.1.1 moduleNumber OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The index into the Software Entry Table" ::= { powerNetSoftwareEntry 1 } -- 1.3.6.1.4.1.318.1.2.1.2.2.1.2 -- 1.3.6.1.4.1.318.1.2.1.2.2.1.2 moduleName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..79)) ACCESS read-only STATUS mandatory DESCRIPTION "The name of the software module." ::= { powerNetSoftwareEntry 2 } -- 1.3.6.1.4.1.318.1.2.1.2.2.1.3 -- 1.3.6.1.4.1.318.1.2.1.2.2.1.3 moduleVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..8)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of the software module." ::= { powerNetSoftwareEntry 3 } -- 1.3.6.1.4.1.318.1.2.1.2.2.1.4 -- 1.3.6.1.4.1.318.1.2.1.2.2.1.4 moduleDate OBJECT-TYPE SYNTAX DisplayString (SIZE (0..9)) ACCESS read-only STATUS mandatory DESCRIPTION "The date of the software module represented as mm-dd-yy." ::= { powerNetSoftwareEntry 4 } -- 1.3.6.1.4.1.318.1.2.2 -- 1.3.6.1.4.1.318.1.2.2 struxureWareOperations OBJECT IDENTIFIER ::= { software 2 } -- 1.3.6.1.4.1.318.1.2.2.1 -- 1.3.6.1.4.1.318.1.2.2.1 struxureWareOperationsStatus OBJECT IDENTIFIER ::= { struxureWareOperations 1 } -- the StruxureWare Operations group -- 1.3.6.1.4.1.318.1.2.2.1.1 -- 1.3.6.1.4.1.318.1.2.2.1.1 serverStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), stopped(2), running(3), running-missing(4), initializing(5), starting(6), disaster-recovery(7), postoffice-inconsistent(8), missing-jgroups(9) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the StruxureWare Operations server: 1: The status of the application server is unknown. Check Webmin and if the problem persists, contact Technical Support. 2: Restart the StruxureWare DC Operation server. If the server was part of a cluster, see the StruxureWare DC Operation User Assistance about rejoining the cluster. If the problem persists, contact Technical Support. 3: No problem. 4: High availability is lost. The StruxureWare DC Operation Application server is running but one or more nodes are not available. If the StruxureWare DC Operation server is part of a cluster, ensure all nodes are running and there is a network connection between the nodes. If the problem persists, contact Technical Support. 5: Wait for the StruxureWare DC Operation Application server to initialize. If the problem persists, contact Technical Support. 6: Wait for the StruxureWare DC Operation Application server to finish starting. If the problem persists, contact Technical Support. 7: This node is running in Disaster Recovery mode. 8: The JBoss postoffice is currently inconsistent. This may be a temporary issue. If the problem persists for more than 10 minutes, contact Technical Support. 9: The JBoss is missing jgroups. This may be a temporary issue. If the problem persists for more than 10 minutes, contact Technical Support." ::= { struxureWareOperationsStatus 1 } -- 1.3.6.1.4.1.318.1.2.2.1.2 -- 1.3.6.1.4.1.318.1.2.2.1.2 databaseStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), stopped(2), running(3), detached(4), catching-up(5), attaching(6), running-master(7), running-primary-slave(8), running-slave(9), running-alone(10) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the StruxureWare Operations database: 1: The status of the database is unknown. Check Webmin and if the problem persists, contact Technical Support. 2: Restart the StruxureWare DC Operation server. If the server was part of a cluster, see the StruxureWare DC Operation User Assistance about rejoining the cluster. If the problem persists, contact Technical Support. 3: No problem. 4: High availability is lost. The database is detached from the cluster and does not receive updates. See the StruxureWare DC Operation User Assistance about reattaching the database node to the StruxureWare DC Operation cluster. If the problem persists, contact Technical Support. 5: The database is catching up with the cluster. Wait for the StruxureWare DC Operation database to retrieve all updates from the master node. If the problem persists, contact Technical Support. 6: The database is attaching to the cluster. Wait for the StruxureWare Operation database to attach to the cluster. If the problem persists, contact Technical Support. 7: The database is the master in a cluster. 8: The database is the primary slave in the cluster. All changes on master are synchronously replicated to this node. 9: The database is a secondary slave in the cluster. All changes on master are asynchronously replicated to this node. 10: The database does not replicate its changes to other nodes." ::= { struxureWareOperationsStatus 2 } -- 1.3.6.1.4.1.318.1.2.2.1.3 -- 1.3.6.1.4.1.318.1.2.2.1.3 loadBalancerStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), stopped(2), running(3), running-missing(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the StruxureWare Operations load balancer: 1: Load Balancer status is unknown. Check Webmin and if the problem persists, contact Technical Support. 2: Load Balancer stopped. Restart the StruxureWare DC Operation server. If the problem persists, contact Technical Support. 3: Normal status 4: High availability is lost. The StruxureWare DC Operation Load Balancer is running but one or more nodes are not available. If the StruxureWare DC Operation server is part of a cluster, ensure all nodes are running and there is a network connection between the nodes. If the problem persists, contact Technical Support." ::= { struxureWareOperationsStatus 3 } -- 1.3.6.1.4.1.318.1.2.2.1.4 -- 1.3.6.1.4.1.318.1.2.2.1.4 essentialServicesStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), stopped(2), running(3), time-sync-problems(4), backup-problems(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the StruxureWare Operations essential services: 1: Unknown status. Check Webmin and if the problem persists, contact Technical Support. 2: Essential services are not running on the StruxureWare DC Operation server. Reboot the node and monitor the status page in Webmin. If the problem persists, contact Technical Support. 3: Normal status 4: The time difference between the StruxureWare DC Operation slave and the master node is too big. Correct the time on the slave to match the time on the master. Consider using an NTP server. If the problem persists, contact Technical Support. 5: The last backup that was attempted on the StruxureWare DC Operation server has failed. Make certain that the system can write to the location specified as backup location. This is particularly relevant for network attached storage. If the problem persists, contact Technical Support." ::= { struxureWareOperationsStatus 4 } -- 1.3.6.1.4.1.318.1.2.2.1.5 -- 1.3.6.1.4.1.318.1.2.2.1.5 etlStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), running(2), failed(3), paused(4), stopped(5) } ACCESS read-only STATUS mandatory DESCRIPTION "The status of the StruxureWare Operations ETL services: 1: Unknown status. Check the network configuration and the server network settings. 2: Normal status, 3: ETL Transformations have failed and are subsequently stopped. Investigate the cause of the failure. 4: ETL Transformations are currently paused. 5: ETL Transformations are currently stopped." ::= { struxureWareOperationsStatus 5 } -- 1.3.6.1.4.1.318.1.2.3 -- 1.3.6.1.4.1.318.1.2.3 powerChuteNetworkShutdown OBJECT IDENTIFIER ::= { software 3 } -- 1.3.6.1.4.1.318.1.2.3.1 -- 1.3.6.1.4.1.318.1.2.3.1 pcnsIdent OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 1 } -- the software group -- the powerChuteNetworkShutdown group -- the pcnsIdent group -- 1.3.6.1.4.1.318.1.2.3.1.1 -- 1.3.6.1.4.1.318.1.2.3.1.1 pcnshostname OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The hostname of the PCNS instance." ::= { pcnsIdent 1 } -- 1.3.6.1.4.1.318.1.2.3.1.2 -- 1.3.6.1.4.1.318.1.2.3.1.2 pcnsVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..9)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of PCNS installed. x.x.x" ::= { pcnsIdent 2 } -- 1.3.6.1.4.1.318.1.2.3.1.3 -- 1.3.6.1.4.1.318.1.2.3.1.3 pcnsOS OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of OS PCNS is Installed on." ::= { pcnsIdent 3 } -- 1.3.6.1.4.1.318.1.2.3.1.4 -- 1.3.6.1.4.1.318.1.2.3.1.4 pcnsJavaVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of Java PCNS is running on." ::= { pcnsIdent 4 } -- 1.3.6.1.4.1.318.1.2.3.2 -- 1.3.6.1.4.1.318.1.2.3.2 pcnsNetworking OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 2 } -- the software group -- the powerChuteNetworkShutdown group -- the pcnsNetworking group -- 1.3.6.1.4.1.318.1.2.3.2.1 -- 1.3.6.1.4.1.318.1.2.3.2.1 pcnsUIProtocol OBJECT-TYPE SYNTAX INTEGER { http(1), https(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Web Protocol used to connect to the PCNS UI." ::= { pcnsNetworking 1 } -- 1.3.6.1.4.1.318.1.2.3.2.2 -- 1.3.6.1.4.1.318.1.2.3.2.2 pcnsHttpPort OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Port used for PCNS http UI." ::= { pcnsNetworking 2 } -- 1.3.6.1.4.1.318.1.2.3.2.3 -- 1.3.6.1.4.1.318.1.2.3.2.3 pcnsHttpsPort OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Port used for PCNS https UI." ::= { pcnsNetworking 3 } -- 1.3.6.1.4.1.318.1.2.3.2.4 -- 1.3.6.1.4.1.318.1.2.3.2.4 pcnsNetworkConfig OBJECT-TYPE SYNTAX INTEGER { ipV4(1), ipV6(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Configuration of the TCP Network." ::= { pcnsNetworking 4 } -- 1.3.6.1.4.1.318.1.2.3.2.5 -- 1.3.6.1.4.1.318.1.2.3.2.5 pcnsVirtualInstall OBJECT-TYPE SYNTAX INTEGER { none(1), hyper-V(2), vmWare(3), nutanixAHV(4), nutanixESXi(5), simpliVity(6), hyperFlex(7) } ACCESS read-only STATUS mandatory DESCRIPTION "Virtualization technology in use by PCNS." ::= { pcnsNetworking 5 } -- 1.3.6.1.4.1.318.1.2.3.3 -- 1.3.6.1.4.1.318.1.2.3.3 pcnsNMC OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 3 } -- the software group -- the powerChuteNetworkShutdown group -- the pcnsNMC group -- 1.3.6.1.4.1.318.1.2.3.3.1 -- 1.3.6.1.4.1.318.1.2.3.3.1 pcnsMode OBJECT-TYPE SYNTAX INTEGER { single(1), redundant(2), parallel(3), advanced(4) } ACCESS read-only STATUS mandatory DESCRIPTION "Configuration mode of the UPS(s) which PCNS is monitoring." ::= { pcnsNMC 1 } -- 1.3.6.1.4.1.318.1.2.3.3.2 -- 1.3.6.1.4.1.318.1.2.3.3.2 pcnsNMCPort OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Port used to connect to all of the Network Management Card(s)." ::= { pcnsNMC 2 } -- 1.3.6.1.4.1.318.1.2.3.3.3 -- 1.3.6.1.4.1.318.1.2.3.3.3 pcnsNMCProtocol OBJECT-TYPE SYNTAX INTEGER { http(1), https(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Web Protocol used to connect to all of the Network Management Card(s)." ::= { pcnsNMC 3 } -- 1.3.6.1.4.1.318.1.2.3.3.4 -- 1.3.6.1.4.1.318.1.2.3.3.4 pcnsNmcTable OBJECT-TYPE SYNTAX SEQUENCE OF PCNSNMCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown." ::= { pcnsNMC 4 } -- 1.3.6.1.4.1.318.1.2.3.3.4.1 -- 1.3.6.1.4.1.318.1.2.3.3.4.1 pcnsNmcEntry OBJECT-TYPE SYNTAX PCNSNMCEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Details of the NMC." INDEX { pcnsNmcIndex } ::= { pcnsNmcTable 1 } PCNSNMCEntry ::= SEQUENCE { pcnsNmcIndex Gauge, pcnsNmcAddr IpAddress, pcnsNmcOutlet Gauge } -- 1.3.6.1.4.1.318.1.2.3.3.4.1.1 -- 1.3.6.1.4.1.318.1.2.3.3.4.1.1 pcnsNmcIndex OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "Index of the NMC within PCNS setup." ::= { pcnsNmcEntry 1 } -- 1.3.6.1.4.1.318.1.2.3.3.4.1.2 -- 1.3.6.1.4.1.318.1.2.3.3.4.1.2 pcnsNmcAddr OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS mandatory DESCRIPTION "The IP address of the NMC." ::= { pcnsNmcEntry 2 } -- 1.3.6.1.4.1.318.1.2.3.3.4.1.3 -- 1.3.6.1.4.1.318.1.2.3.3.4.1.3 pcnsNmcOutlet OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The Outlet Group which PCNS is enrolled with on the NMC." ::= { pcnsNmcEntry 3 } -- 1.3.6.1.4.1.318.1.2.3.4 -- 1.3.6.1.4.1.318.1.2.3.4 pcnsEvents OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 4 } -- the software group -- the powerChuteNetworkShutdown group -- the pcnsEvents group -- 1.3.6.1.4.1.318.1.2.3.4.1 -- 1.3.6.1.4.1.318.1.2.3.4.1 pcnsPowerFailed OBJECT IDENTIFIER ::= { pcnsEvents 1 } -- 1.3.6.1.4.1.318.1.2.3.4.1.1 -- 1.3.6.1.4.1.318.1.2.3.4.1.1 pcnsPowerFailedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsPowerFailed 1 } -- 1.3.6.1.4.1.318.1.2.3.4.1.2 -- 1.3.6.1.4.1.318.1.2.3.4.1.2 pcnsPowerFailedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsPowerFailed 2 } -- 1.3.6.1.4.1.318.1.2.3.4.1.3 -- 1.3.6.1.4.1.318.1.2.3.4.1.3 pcnsPowerFailedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsPowerFailed 3 } -- 1.3.6.1.4.1.318.1.2.3.4.1.4 -- 1.3.6.1.4.1.318.1.2.3.4.1.4 pcnsPowerFailedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsPowerFailed 4 } -- 1.3.6.1.4.1.318.1.2.3.4.1.5 -- 1.3.6.1.4.1.318.1.2.3.4.1.5 pcnsPowerFailedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsPowerFailed 5 } -- 1.3.6.1.4.1.318.1.2.3.4.1.6 -- 1.3.6.1.4.1.318.1.2.3.4.1.6 pcnsPowerFailedEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsPowerFailed 6 } -- 1.3.6.1.4.1.318.1.2.3.4.1.7 -- 1.3.6.1.4.1.318.1.2.3.4.1.7 pcnsPowerFailedShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsPowerFailed 7 } -- 1.3.6.1.4.1.318.1.2.3.4.2 -- 1.3.6.1.4.1.318.1.2.3.4.2 pcnsPowerRestored OBJECT IDENTIFIER ::= { pcnsEvents 2 } -- 1.3.6.1.4.1.318.1.2.3.4.2.1 -- 1.3.6.1.4.1.318.1.2.3.4.2.1 pcnsPowerRestoredDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsPowerRestored 1 } -- 1.3.6.1.4.1.318.1.2.3.4.2.2 -- 1.3.6.1.4.1.318.1.2.3.4.2.2 pcnsPowerRestoredEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsPowerRestored 2 } -- 1.3.6.1.4.1.318.1.2.3.4.2.3 -- 1.3.6.1.4.1.318.1.2.3.4.2.3 pcnsPowerRestoredEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsPowerRestored 3 } -- 1.3.6.1.4.1.318.1.2.3.4.2.4 -- 1.3.6.1.4.1.318.1.2.3.4.2.4 pcnsPowerRestoredCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsPowerRestored 4 } -- 1.3.6.1.4.1.318.1.2.3.4.2.5 -- 1.3.6.1.4.1.318.1.2.3.4.2.5 pcnsPowerRestoredCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsPowerRestored 5 } -- 1.3.6.1.4.1.318.1.2.3.4.3 -- 1.3.6.1.4.1.318.1.2.3.4.3 pcnsOverload OBJECT IDENTIFIER ::= { pcnsEvents 3 } -- 1.3.6.1.4.1.318.1.2.3.4.3.1 -- 1.3.6.1.4.1.318.1.2.3.4.3.1 pcnsOverloadDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsOverload 1 } -- 1.3.6.1.4.1.318.1.2.3.4.3.2 -- 1.3.6.1.4.1.318.1.2.3.4.3.2 pcnsOverloadEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsOverload 2 } -- 1.3.6.1.4.1.318.1.2.3.4.3.3 -- 1.3.6.1.4.1.318.1.2.3.4.3.3 pcnsOverloadEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsOverload 3 } -- 1.3.6.1.4.1.318.1.2.3.4.3.4 -- 1.3.6.1.4.1.318.1.2.3.4.3.4 pcnsOverloadCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsOverload 4 } -- 1.3.6.1.4.1.318.1.2.3.4.3.5 -- 1.3.6.1.4.1.318.1.2.3.4.3.5 pcnsOverloadCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsOverload 5 } -- 1.3.6.1.4.1.318.1.2.3.4.3.6 -- 1.3.6.1.4.1.318.1.2.3.4.3.6 pcnsOverloadEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsOverload 6 } -- 1.3.6.1.4.1.318.1.2.3.4.3.7 -- 1.3.6.1.4.1.318.1.2.3.4.3.7 pcnsOverloadShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsOverload 7 } -- 1.3.6.1.4.1.318.1.2.3.4.4 -- 1.3.6.1.4.1.318.1.2.3.4.4 pcnsOverloadSolved OBJECT IDENTIFIER ::= { pcnsEvents 4 } -- 1.3.6.1.4.1.318.1.2.3.4.4.1 -- 1.3.6.1.4.1.318.1.2.3.4.4.1 pcnsOverloadSolvedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsOverloadSolved 1 } -- 1.3.6.1.4.1.318.1.2.3.4.4.2 -- 1.3.6.1.4.1.318.1.2.3.4.4.2 pcnsOverloadSolvedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsOverloadSolved 2 } -- 1.3.6.1.4.1.318.1.2.3.4.4.3 -- 1.3.6.1.4.1.318.1.2.3.4.4.3 pcnsOverloadSolvedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsOverloadSolved 3 } -- 1.3.6.1.4.1.318.1.2.3.4.4.4 -- 1.3.6.1.4.1.318.1.2.3.4.4.4 pcnsOverloadSolvedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsOverloadSolved 4 } -- 1.3.6.1.4.1.318.1.2.3.4.4.5 -- 1.3.6.1.4.1.318.1.2.3.4.4.5 pcnsOverloadSolvedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsOverloadSolved 5 } -- 1.3.6.1.4.1.318.1.2.3.4.5 -- 1.3.6.1.4.1.318.1.2.3.4.5 pcnsRunTimeExceeded OBJECT IDENTIFIER ::= { pcnsEvents 5 } -- 1.3.6.1.4.1.318.1.2.3.4.5.1 -- 1.3.6.1.4.1.318.1.2.3.4.5.1 pcnsRunTimeExceededDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsRunTimeExceeded 1 } -- 1.3.6.1.4.1.318.1.2.3.4.5.2 -- 1.3.6.1.4.1.318.1.2.3.4.5.2 pcnsRunTimeExceededEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsRunTimeExceeded 2 } -- 1.3.6.1.4.1.318.1.2.3.4.5.3 -- 1.3.6.1.4.1.318.1.2.3.4.5.3 pcnsRunTimeExceededEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsRunTimeExceeded 3 } -- 1.3.6.1.4.1.318.1.2.3.4.5.4 -- 1.3.6.1.4.1.318.1.2.3.4.5.4 pcnsRunTimeExceededCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsRunTimeExceeded 4 } -- 1.3.6.1.4.1.318.1.2.3.4.5.5 -- 1.3.6.1.4.1.318.1.2.3.4.5.5 pcnsRunTimeExceededCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsRunTimeExceeded 5 } -- 1.3.6.1.4.1.318.1.2.3.4.5.6 -- 1.3.6.1.4.1.318.1.2.3.4.5.6 pcnsRunTimeExceededEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsRunTimeExceeded 6 } -- 1.3.6.1.4.1.318.1.2.3.4.5.7 -- 1.3.6.1.4.1.318.1.2.3.4.5.7 pcnsRunTimeExceededShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsRunTimeExceeded 7 } -- 1.3.6.1.4.1.318.1.2.3.4.6 -- 1.3.6.1.4.1.318.1.2.3.4.6 pcnsRunTimeWithinRange OBJECT IDENTIFIER ::= { pcnsEvents 6 } -- 1.3.6.1.4.1.318.1.2.3.4.6.1 -- 1.3.6.1.4.1.318.1.2.3.4.6.1 pcnsRunTimeWithinRangeDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsRunTimeWithinRange 1 } -- 1.3.6.1.4.1.318.1.2.3.4.6.2 -- 1.3.6.1.4.1.318.1.2.3.4.6.2 pcnsRunTimeWithinRangeEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsRunTimeWithinRange 2 } -- 1.3.6.1.4.1.318.1.2.3.4.6.3 -- 1.3.6.1.4.1.318.1.2.3.4.6.3 pcnsRunTimeWithinRangeEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsRunTimeWithinRange 3 } -- 1.3.6.1.4.1.318.1.2.3.4.6.4 -- 1.3.6.1.4.1.318.1.2.3.4.6.4 pcnsRunTimeWithinRangeCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsRunTimeWithinRange 4 } -- 1.3.6.1.4.1.318.1.2.3.4.6.5 -- 1.3.6.1.4.1.318.1.2.3.4.6.5 pcnsRunTimeWithinRangeCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsRunTimeWithinRange 5 } -- 1.3.6.1.4.1.318.1.2.3.4.7 -- 1.3.6.1.4.1.318.1.2.3.4.7 pcnsRunTimeBelowThreshold OBJECT IDENTIFIER ::= { pcnsEvents 7 } -- 1.3.6.1.4.1.318.1.2.3.4.7.1 -- 1.3.6.1.4.1.318.1.2.3.4.7.1 pcnsRunTimeBelowThresholdDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsRunTimeBelowThreshold 1 } -- 1.3.6.1.4.1.318.1.2.3.4.7.2 -- 1.3.6.1.4.1.318.1.2.3.4.7.2 pcnspcnsRunTimeBelowThresholdEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsRunTimeBelowThreshold 2 } -- 1.3.6.1.4.1.318.1.2.3.4.7.3 -- 1.3.6.1.4.1.318.1.2.3.4.7.3 pcnsRunTimeBelowThresholdEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsRunTimeBelowThreshold 3 } -- 1.3.6.1.4.1.318.1.2.3.4.7.4 -- 1.3.6.1.4.1.318.1.2.3.4.7.4 pcnsRunTimeBelowThresholdCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsRunTimeBelowThreshold 4 } -- 1.3.6.1.4.1.318.1.2.3.4.7.6 -- 1.3.6.1.4.1.318.1.2.3.4.7.6 pcnsRunTimeBelowThresholdEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsRunTimeBelowThreshold 6 } -- 1.3.6.1.4.1.318.1.2.3.4.7.8 -- 1.3.6.1.4.1.318.1.2.3.4.7.8 pcnsRunTimeBelowThresholdCommandFileThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "If the Runtime Remaining falls below this (seconds), the command file will run." ::= { pcnsRunTimeBelowThreshold 8 } -- 1.3.6.1.4.1.318.1.2.3.4.7.9 -- 1.3.6.1.4.1.318.1.2.3.4.7.9 pcnsRunTimeBelowThresholdShutdownThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "If the Runtime Remaining falls below this (seconds), the shutdown will begin." ::= { pcnsRunTimeBelowThreshold 9 } -- 1.3.6.1.4.1.318.1.2.3.4.8 -- 1.3.6.1.4.1.318.1.2.3.4.8 pcnsRunTimeAboveThreshold OBJECT IDENTIFIER ::= { pcnsEvents 8 } -- 1.3.6.1.4.1.318.1.2.3.4.8.1 -- 1.3.6.1.4.1.318.1.2.3.4.8.1 pcnsRunTimeAboveThresholdDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsRunTimeAboveThreshold 1 } -- 1.3.6.1.4.1.318.1.2.3.4.8.2 -- 1.3.6.1.4.1.318.1.2.3.4.8.2 pcnsRunTimeAboveThresholdEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsRunTimeAboveThreshold 2 } -- 1.3.6.1.4.1.318.1.2.3.4.8.3 -- 1.3.6.1.4.1.318.1.2.3.4.8.3 pcnsRunTimeAboveThresholdEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsRunTimeAboveThreshold 3 } -- 1.3.6.1.4.1.318.1.2.3.4.8.4 -- 1.3.6.1.4.1.318.1.2.3.4.8.4 pcnsRunTimeAboveThresholdCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsRunTimeAboveThreshold 4 } -- 1.3.6.1.4.1.318.1.2.3.4.8.5 -- 1.3.6.1.4.1.318.1.2.3.4.8.5 pcnsRunTimeAboveThresholdCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsRunTimeAboveThreshold 5 } -- 1.3.6.1.4.1.318.1.2.3.4.10 -- 1.3.6.1.4.1.318.1.2.3.4.10 pcnsBatteryDischarged OBJECT IDENTIFIER ::= { pcnsEvents 10 } -- 1.3.6.1.4.1.318.1.2.3.4.10.1 -- 1.3.6.1.4.1.318.1.2.3.4.10.1 pcnsBatteryDischargedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsBatteryDischarged 1 } -- 1.3.6.1.4.1.318.1.2.3.4.10.2 -- 1.3.6.1.4.1.318.1.2.3.4.10.2 pcnsBatteryDischargedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsBatteryDischarged 2 } -- 1.3.6.1.4.1.318.1.2.3.4.10.3 -- 1.3.6.1.4.1.318.1.2.3.4.10.3 pcnsBatteryDischargedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsBatteryDischarged 3 } -- 1.3.6.1.4.1.318.1.2.3.4.10.4 -- 1.3.6.1.4.1.318.1.2.3.4.10.4 pcnsBatteryDischargedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsBatteryDischarged 4 } -- 1.3.6.1.4.1.318.1.2.3.4.10.5 -- 1.3.6.1.4.1.318.1.2.3.4.10.5 pcnsBatteryDischargedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsBatteryDischarged 5 } -- 1.3.6.1.4.1.318.1.2.3.4.10.6 -- 1.3.6.1.4.1.318.1.2.3.4.10.6 pcnsBatteryDischargedEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsBatteryDischarged 6 } -- 1.3.6.1.4.1.318.1.2.3.4.10.7 -- 1.3.6.1.4.1.318.1.2.3.4.10.7 pcnsBatteryDischargedShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsBatteryDischarged 7 } -- 1.3.6.1.4.1.318.1.2.3.4.11 -- 1.3.6.1.4.1.318.1.2.3.4.11 pcnsBatteryChargeInRange OBJECT IDENTIFIER ::= { pcnsEvents 11 } -- 1.3.6.1.4.1.318.1.2.3.4.11.1 -- 1.3.6.1.4.1.318.1.2.3.4.11.1 pcnsBatteryChargeInRangeDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsBatteryChargeInRange 1 } -- 1.3.6.1.4.1.318.1.2.3.4.11.2 -- 1.3.6.1.4.1.318.1.2.3.4.11.2 pcnsBatteryChargeInRangeEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsBatteryChargeInRange 2 } -- 1.3.6.1.4.1.318.1.2.3.4.11.3 -- 1.3.6.1.4.1.318.1.2.3.4.11.3 pcnsBatteryChargeInRangeEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsBatteryChargeInRange 3 } -- 1.3.6.1.4.1.318.1.2.3.4.11.4 -- 1.3.6.1.4.1.318.1.2.3.4.11.4 pcnsBatteryChargeInRangeCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsBatteryChargeInRange 4 } -- 1.3.6.1.4.1.318.1.2.3.4.11.5 -- 1.3.6.1.4.1.318.1.2.3.4.11.5 pcnsBatteryChargeInRangeCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsBatteryChargeInRange 5 } -- 1.3.6.1.4.1.318.1.2.3.4.12 -- 1.3.6.1.4.1.318.1.2.3.4.12 pcnsFaultBypassEnabled OBJECT IDENTIFIER ::= { pcnsEvents 12 } -- 1.3.6.1.4.1.318.1.2.3.4.12.1 -- 1.3.6.1.4.1.318.1.2.3.4.12.1 pcnsFaultBypassEnabledDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsFaultBypassEnabled 1 } -- 1.3.6.1.4.1.318.1.2.3.4.12.2 -- 1.3.6.1.4.1.318.1.2.3.4.12.2 pcnsFaultBypassEnabledEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsFaultBypassEnabled 2 } -- 1.3.6.1.4.1.318.1.2.3.4.12.3 -- 1.3.6.1.4.1.318.1.2.3.4.12.3 pcnsFaultBypassEnabledEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsFaultBypassEnabled 3 } -- 1.3.6.1.4.1.318.1.2.3.4.12.4 -- 1.3.6.1.4.1.318.1.2.3.4.12.4 pcnsFaultBypassEnabledCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsFaultBypassEnabled 4 } -- 1.3.6.1.4.1.318.1.2.3.4.12.5 -- 1.3.6.1.4.1.318.1.2.3.4.12.5 pcnsFaultBypassEnabledCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsFaultBypassEnabled 5 } -- 1.3.6.1.4.1.318.1.2.3.4.12.6 -- 1.3.6.1.4.1.318.1.2.3.4.12.6 pcnsFaultBypassEnabledEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsFaultBypassEnabled 6 } -- 1.3.6.1.4.1.318.1.2.3.4.12.7 -- 1.3.6.1.4.1.318.1.2.3.4.12.7 pcnsFaultBypassEnabledShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsFaultBypassEnabled 7 } -- 1.3.6.1.4.1.318.1.2.3.4.13 -- 1.3.6.1.4.1.318.1.2.3.4.13 pcnsBypassEnabled OBJECT IDENTIFIER ::= { pcnsEvents 13 } -- 1.3.6.1.4.1.318.1.2.3.4.13.1 -- 1.3.6.1.4.1.318.1.2.3.4.13.1 pcnsBypassEnabledDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsBypassEnabled 1 } -- 1.3.6.1.4.1.318.1.2.3.4.13.2 -- 1.3.6.1.4.1.318.1.2.3.4.13.2 pcnsBypassEnabledEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsBypassEnabled 2 } -- 1.3.6.1.4.1.318.1.2.3.4.13.3 -- 1.3.6.1.4.1.318.1.2.3.4.13.3 pcnsBypassEnabledEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsBypassEnabled 3 } -- 1.3.6.1.4.1.318.1.2.3.4.13.4 -- 1.3.6.1.4.1.318.1.2.3.4.13.4 pcnsBypassEnabledCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsBypassEnabled 4 } -- 1.3.6.1.4.1.318.1.2.3.4.13.5 -- 1.3.6.1.4.1.318.1.2.3.4.13.5 pcnsBypassEnabledCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsBypassEnabled 5 } -- 1.3.6.1.4.1.318.1.2.3.4.13.6 -- 1.3.6.1.4.1.318.1.2.3.4.13.6 pcnsBypassEnabledEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsBypassEnabled 6 } -- 1.3.6.1.4.1.318.1.2.3.4.13.7 -- 1.3.6.1.4.1.318.1.2.3.4.13.7 pcnsBypassEnabledShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsBypassEnabled 7 } -- 1.3.6.1.4.1.318.1.2.3.4.14 -- 1.3.6.1.4.1.318.1.2.3.4.14 pcnsBypassManualEnabled OBJECT IDENTIFIER ::= { pcnsEvents 14 } -- 1.3.6.1.4.1.318.1.2.3.4.14.1 -- 1.3.6.1.4.1.318.1.2.3.4.14.1 pcnsBypassManualEnabledDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsBypassManualEnabled 1 } -- 1.3.6.1.4.1.318.1.2.3.4.14.2 -- 1.3.6.1.4.1.318.1.2.3.4.14.2 pcnsBypassManualEnabledEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsBypassManualEnabled 2 } -- 1.3.6.1.4.1.318.1.2.3.4.14.3 -- 1.3.6.1.4.1.318.1.2.3.4.14.3 pcnsBypassManualEnabledEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsBypassManualEnabled 3 } -- 1.3.6.1.4.1.318.1.2.3.4.14.4 -- 1.3.6.1.4.1.318.1.2.3.4.14.4 pcnsBypassManualEnabledCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsBypassManualEnabled 4 } -- 1.3.6.1.4.1.318.1.2.3.4.14.5 -- 1.3.6.1.4.1.318.1.2.3.4.14.5 pcnsBypassManualEnabledCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsBypassManualEnabled 5 } -- 1.3.6.1.4.1.318.1.2.3.4.14.6 -- 1.3.6.1.4.1.318.1.2.3.4.14.6 pcnsBypassManualEnabledEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsBypassManualEnabled 6 } -- 1.3.6.1.4.1.318.1.2.3.4.14.7 -- 1.3.6.1.4.1.318.1.2.3.4.14.7 pcnsBypassManualEnabledShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsBypassManualEnabled 7 } -- 1.3.6.1.4.1.318.1.2.3.4.15 -- 1.3.6.1.4.1.318.1.2.3.4.15 pcnsBypassDisabled OBJECT IDENTIFIER ::= { pcnsEvents 15 } -- 1.3.6.1.4.1.318.1.2.3.4.15.1 -- 1.3.6.1.4.1.318.1.2.3.4.15.1 pcnsBypassDisabledDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsBypassDisabled 1 } -- 1.3.6.1.4.1.318.1.2.3.4.15.2 -- 1.3.6.1.4.1.318.1.2.3.4.15.2 pcnsBypassDisabledEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsBypassDisabled 2 } -- 1.3.6.1.4.1.318.1.2.3.4.15.3 -- 1.3.6.1.4.1.318.1.2.3.4.15.3 pcnsBypassDisabledEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsBypassDisabled 3 } -- 1.3.6.1.4.1.318.1.2.3.4.15.4 -- 1.3.6.1.4.1.318.1.2.3.4.15.4 pcnsBypassDisabledCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsBypassDisabled 4 } -- 1.3.6.1.4.1.318.1.2.3.4.15.5 -- 1.3.6.1.4.1.318.1.2.3.4.15.5 pcnsBypassDisabledCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsBypassDisabled 5 } -- 1.3.6.1.4.1.318.1.2.3.4.16 -- 1.3.6.1.4.1.318.1.2.3.4.16 pcnsBypassContactorFailed OBJECT IDENTIFIER ::= { pcnsEvents 16 } -- 1.3.6.1.4.1.318.1.2.3.4.16.1 -- 1.3.6.1.4.1.318.1.2.3.4.16.1 pcnsBypassContactorFailedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsBypassContactorFailed 1 } -- 1.3.6.1.4.1.318.1.2.3.4.16.2 -- 1.3.6.1.4.1.318.1.2.3.4.16.2 pcnsBypassContactorFailedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsBypassContactorFailed 2 } -- 1.3.6.1.4.1.318.1.2.3.4.16.3 -- 1.3.6.1.4.1.318.1.2.3.4.16.3 pcnsBypassContactorFailedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsBypassContactorFailed 3 } -- 1.3.6.1.4.1.318.1.2.3.4.16.4 -- 1.3.6.1.4.1.318.1.2.3.4.16.4 pcnsBypassContactorFailedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsBypassContactorFailed 4 } -- 1.3.6.1.4.1.318.1.2.3.4.16.5 -- 1.3.6.1.4.1.318.1.2.3.4.16.5 pcnsBypassContactorFailedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsBypassContactorFailed 5 } -- 1.3.6.1.4.1.318.1.2.3.4.16.6 -- 1.3.6.1.4.1.318.1.2.3.4.16.6 pcnsBypassContactorFailedEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsBypassContactorFailed 6 } -- 1.3.6.1.4.1.318.1.2.3.4.16.7 -- 1.3.6.1.4.1.318.1.2.3.4.16.7 pcnsBypassContactorFailedShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsBypassContactorFailed 7 } -- 1.3.6.1.4.1.318.1.2.3.4.17 -- 1.3.6.1.4.1.318.1.2.3.4.17 pcnsBypassContactorOk OBJECT IDENTIFIER ::= { pcnsEvents 17 } -- 1.3.6.1.4.1.318.1.2.3.4.17.1 -- 1.3.6.1.4.1.318.1.2.3.4.17.1 pcnsBypassContactorOkDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsBypassContactorOk 1 } -- 1.3.6.1.4.1.318.1.2.3.4.17.2 -- 1.3.6.1.4.1.318.1.2.3.4.17.2 pcnsBypassContactorOkEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsBypassContactorOk 2 } -- 1.3.6.1.4.1.318.1.2.3.4.17.3 -- 1.3.6.1.4.1.318.1.2.3.4.17.3 pcnsBypassContactorOkEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsBypassContactorOk 3 } -- 1.3.6.1.4.1.318.1.2.3.4.17.4 -- 1.3.6.1.4.1.318.1.2.3.4.17.4 pcnsBypassContactorOkCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsBypassContactorOk 4 } -- 1.3.6.1.4.1.318.1.2.3.4.17.5 -- 1.3.6.1.4.1.318.1.2.3.4.17.5 pcnsBypassContactorOkCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsBypassContactorOk 5 } -- 1.3.6.1.4.1.318.1.2.3.4.18 -- 1.3.6.1.4.1.318.1.2.3.4.18 pcnsCommunicationLostOnBattery OBJECT IDENTIFIER ::= { pcnsEvents 18 } -- 1.3.6.1.4.1.318.1.2.3.4.18.1 -- 1.3.6.1.4.1.318.1.2.3.4.18.1 pcnsCommunicationLostOnBatteryDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsCommunicationLostOnBattery 1 } -- 1.3.6.1.4.1.318.1.2.3.4.18.2 -- 1.3.6.1.4.1.318.1.2.3.4.18.2 pcnsCommunicationLostOnBatteryEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsCommunicationLostOnBattery 2 } -- 1.3.6.1.4.1.318.1.2.3.4.18.3 -- 1.3.6.1.4.1.318.1.2.3.4.18.3 pcnsCommunicationLostOnBatteryEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsCommunicationLostOnBattery 3 } -- 1.3.6.1.4.1.318.1.2.3.4.18.4 -- 1.3.6.1.4.1.318.1.2.3.4.18.4 pcnsCommunicationLostOnBatteryCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsCommunicationLostOnBattery 4 } -- 1.3.6.1.4.1.318.1.2.3.4.18.5 -- 1.3.6.1.4.1.318.1.2.3.4.18.5 pcnsCommunicationLostOnBatteryCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsCommunicationLostOnBattery 5 } -- 1.3.6.1.4.1.318.1.2.3.4.18.6 -- 1.3.6.1.4.1.318.1.2.3.4.18.6 pcnsCommunicationLostOnBatteryEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsCommunicationLostOnBattery 6 } -- 1.3.6.1.4.1.318.1.2.3.4.18.7 -- 1.3.6.1.4.1.318.1.2.3.4.18.7 pcnsCommunicationLostOnBatteryShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsCommunicationLostOnBattery 7 } -- 1.3.6.1.4.1.318.1.2.3.4.19 -- 1.3.6.1.4.1.318.1.2.3.4.19 pcnsCommunicationLost OBJECT IDENTIFIER ::= { pcnsEvents 19 } -- 1.3.6.1.4.1.318.1.2.3.4.19.1 -- 1.3.6.1.4.1.318.1.2.3.4.19.1 pcnsCommunicationLostDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsCommunicationLost 1 } -- 1.3.6.1.4.1.318.1.2.3.4.19.2 -- 1.3.6.1.4.1.318.1.2.3.4.19.2 pcnsCommunicationLostEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsCommunicationLost 2 } -- 1.3.6.1.4.1.318.1.2.3.4.19.3 -- 1.3.6.1.4.1.318.1.2.3.4.19.3 pcnsCommunicationLostEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsCommunicationLost 3 } -- 1.3.6.1.4.1.318.1.2.3.4.19.4 -- 1.3.6.1.4.1.318.1.2.3.4.19.4 pcnsCommunicationLostCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsCommunicationLost 4 } -- 1.3.6.1.4.1.318.1.2.3.4.19.5 -- 1.3.6.1.4.1.318.1.2.3.4.19.5 pcnsCommunicationLostCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsCommunicationLost 5 } -- 1.3.6.1.4.1.318.1.2.3.4.19.6 -- 1.3.6.1.4.1.318.1.2.3.4.19.6 pcnsCommunicationLostEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsCommunicationLost 6 } -- 1.3.6.1.4.1.318.1.2.3.4.19.7 -- 1.3.6.1.4.1.318.1.2.3.4.19.7 pcnsCommunicationLostShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsCommunicationLost 7 } -- 1.3.6.1.4.1.318.1.2.3.4.20 -- 1.3.6.1.4.1.318.1.2.3.4.20 pcnsNetCommunicationLost OBJECT IDENTIFIER ::= { pcnsEvents 20 } -- 1.3.6.1.4.1.318.1.2.3.4.20.1 -- 1.3.6.1.4.1.318.1.2.3.4.20.1 pcnsNetCommunicationLostDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsNetCommunicationLost 1 } -- 1.3.6.1.4.1.318.1.2.3.4.20.2 -- 1.3.6.1.4.1.318.1.2.3.4.20.2 pcnsNetCommunicationLostEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsNetCommunicationLost 2 } -- 1.3.6.1.4.1.318.1.2.3.4.20.3 -- 1.3.6.1.4.1.318.1.2.3.4.20.3 pcnsNetCommunicationLostEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsNetCommunicationLost 3 } -- 1.3.6.1.4.1.318.1.2.3.4.20.4 -- 1.3.6.1.4.1.318.1.2.3.4.20.4 pcnsNetCommunicationLostCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsNetCommunicationLost 4 } -- 1.3.6.1.4.1.318.1.2.3.4.20.5 -- 1.3.6.1.4.1.318.1.2.3.4.20.5 pcnsNetCommunicationLostCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsNetCommunicationLost 5 } -- 1.3.6.1.4.1.318.1.2.3.4.20.6 -- 1.3.6.1.4.1.318.1.2.3.4.20.6 pcnsNetCommunicationLostEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsNetCommunicationLost 6 } -- 1.3.6.1.4.1.318.1.2.3.4.20.7 -- 1.3.6.1.4.1.318.1.2.3.4.20.7 pcnsNetCommunicationLostShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsNetCommunicationLost 7 } -- 1.3.6.1.4.1.318.1.2.3.4.21 -- 1.3.6.1.4.1.318.1.2.3.4.21 pcnsCommunicationEstablished OBJECT IDENTIFIER ::= { pcnsEvents 21 } -- 1.3.6.1.4.1.318.1.2.3.4.21.1 -- 1.3.6.1.4.1.318.1.2.3.4.21.1 pcnsCommunicationEstablishedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsCommunicationEstablished 1 } -- 1.3.6.1.4.1.318.1.2.3.4.21.2 -- 1.3.6.1.4.1.318.1.2.3.4.21.2 pcnsCommunicationEstablishedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsCommunicationEstablished 2 } -- 1.3.6.1.4.1.318.1.2.3.4.21.3 -- 1.3.6.1.4.1.318.1.2.3.4.21.3 pcnsCommunicationEstablishedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsCommunicationEstablished 3 } -- 1.3.6.1.4.1.318.1.2.3.4.21.4 -- 1.3.6.1.4.1.318.1.2.3.4.21.4 pcnsCommunicationEstablishedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsCommunicationEstablished 4 } -- 1.3.6.1.4.1.318.1.2.3.4.21.5 -- 1.3.6.1.4.1.318.1.2.3.4.21.5 pcnsCommunicationEstablishedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsCommunicationEstablished 5 } -- 1.3.6.1.4.1.318.1.2.3.4.22 -- 1.3.6.1.4.1.318.1.2.3.4.22 pcnsMinRedundancyLost OBJECT IDENTIFIER ::= { pcnsEvents 22 } -- 1.3.6.1.4.1.318.1.2.3.4.22.1 -- 1.3.6.1.4.1.318.1.2.3.4.22.1 pcnsMinRedundancyLostDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsMinRedundancyLost 1 } -- 1.3.6.1.4.1.318.1.2.3.4.22.2 -- 1.3.6.1.4.1.318.1.2.3.4.22.2 pcnsMinRedundancyLostEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsMinRedundancyLost 2 } -- 1.3.6.1.4.1.318.1.2.3.4.22.3 -- 1.3.6.1.4.1.318.1.2.3.4.22.3 pcnsMinRedundancyLostEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsMinRedundancyLost 3 } -- 1.3.6.1.4.1.318.1.2.3.4.22.4 -- 1.3.6.1.4.1.318.1.2.3.4.22.4 pcnsMinRedundancyLostCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsMinRedundancyLost 4 } -- 1.3.6.1.4.1.318.1.2.3.4.22.5 -- 1.3.6.1.4.1.318.1.2.3.4.22.5 pcnsMinRedundancyLostCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsMinRedundancyLost 5 } -- 1.3.6.1.4.1.318.1.2.3.4.22.6 -- 1.3.6.1.4.1.318.1.2.3.4.22.6 pcnsMinRedundancyLostEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsMinRedundancyLost 6 } -- 1.3.6.1.4.1.318.1.2.3.4.22.7 -- 1.3.6.1.4.1.318.1.2.3.4.22.7 pcnsMinRedundancyLostShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsMinRedundancyLost 7 } -- 1.3.6.1.4.1.318.1.2.3.4.23 -- 1.3.6.1.4.1.318.1.2.3.4.23 pcnsMinRedundancyRegained OBJECT IDENTIFIER ::= { pcnsEvents 23 } -- 1.3.6.1.4.1.318.1.2.3.4.23.1 -- 1.3.6.1.4.1.318.1.2.3.4.23.1 pcnsMinRedundancyRegainedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsMinRedundancyRegained 1 } -- 1.3.6.1.4.1.318.1.2.3.4.23.2 -- 1.3.6.1.4.1.318.1.2.3.4.23.2 pcnsMinRedundancyRegainedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsMinRedundancyRegained 2 } -- 1.3.6.1.4.1.318.1.2.3.4.23.3 -- 1.3.6.1.4.1.318.1.2.3.4.23.3 pcnsMinRedundancyRegainedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsMinRedundancyRegained 3 } -- 1.3.6.1.4.1.318.1.2.3.4.23.4 -- 1.3.6.1.4.1.318.1.2.3.4.23.4 pcnsMinRedundancyRegainedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsMinRedundancyRegained 4 } -- 1.3.6.1.4.1.318.1.2.3.4.23.5 -- 1.3.6.1.4.1.318.1.2.3.4.23.5 pcnsMinRedundancyRegainedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsMinRedundancyRegained 5 } -- 1.3.6.1.4.1.318.1.2.3.4.24 -- 1.3.6.1.4.1.318.1.2.3.4.24 pcnsParallelRedundancyLost OBJECT IDENTIFIER ::= { pcnsEvents 24 } -- 1.3.6.1.4.1.318.1.2.3.4.24.1 -- 1.3.6.1.4.1.318.1.2.3.4.24.1 pcnsParallelRedundancyLostDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsParallelRedundancyLost 1 } -- 1.3.6.1.4.1.318.1.2.3.4.24.2 -- 1.3.6.1.4.1.318.1.2.3.4.24.2 pcnsParallelRedundancyLostEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsParallelRedundancyLost 2 } -- 1.3.6.1.4.1.318.1.2.3.4.24.3 -- 1.3.6.1.4.1.318.1.2.3.4.24.3 pcnsParallelRedundancyLostEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsParallelRedundancyLost 3 } -- 1.3.6.1.4.1.318.1.2.3.4.24.4 -- 1.3.6.1.4.1.318.1.2.3.4.24.4 pcnsParallelRedundancyLostCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsParallelRedundancyLost 4 } -- 1.3.6.1.4.1.318.1.2.3.4.24.5 -- 1.3.6.1.4.1.318.1.2.3.4.24.5 pcnsParallelRedundancyLostCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsParallelRedundancyLost 5 } -- 1.3.6.1.4.1.318.1.2.3.4.24.6 -- 1.3.6.1.4.1.318.1.2.3.4.24.6 pcnsParallelRedundancyLostEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsParallelRedundancyLost 6 } -- 1.3.6.1.4.1.318.1.2.3.4.24.7 -- 1.3.6.1.4.1.318.1.2.3.4.24.7 pcnsParallelRedundancyLostShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsParallelRedundancyLost 7 } -- 1.3.6.1.4.1.318.1.2.3.4.25 -- 1.3.6.1.4.1.318.1.2.3.4.25 pcnsParallelRedundancyRegained OBJECT IDENTIFIER ::= { pcnsEvents 25 } -- 1.3.6.1.4.1.318.1.2.3.4.25.1 -- 1.3.6.1.4.1.318.1.2.3.4.25.1 pcnsParallelRedundancyRegainedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsParallelRedundancyRegained 1 } -- 1.3.6.1.4.1.318.1.2.3.4.25.2 -- 1.3.6.1.4.1.318.1.2.3.4.25.2 pcnsParallelRedundancyRegainedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsParallelRedundancyRegained 2 } -- 1.3.6.1.4.1.318.1.2.3.4.25.3 -- 1.3.6.1.4.1.318.1.2.3.4.25.3 pcnsParallelRedundancyRegainedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsParallelRedundancyRegained 3 } -- 1.3.6.1.4.1.318.1.2.3.4.25.4 -- 1.3.6.1.4.1.318.1.2.3.4.25.4 pcnsParallelRedundancyRegainedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsParallelRedundancyRegained 4 } -- 1.3.6.1.4.1.318.1.2.3.4.25.5 -- 1.3.6.1.4.1.318.1.2.3.4.25.5 pcnsParallelRedundancyRegainedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsParallelRedundancyRegained 5 } -- 1.3.6.1.4.1.318.1.2.3.4.26 -- 1.3.6.1.4.1.318.1.2.3.4.26 pcnsMaxInternalTempExceeded OBJECT IDENTIFIER ::= { pcnsEvents 26 } -- 1.3.6.1.4.1.318.1.2.3.4.26.1 -- 1.3.6.1.4.1.318.1.2.3.4.26.1 pcnsMaxInternalTempExceededDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsMaxInternalTempExceeded 1 } -- 1.3.6.1.4.1.318.1.2.3.4.26.2 -- 1.3.6.1.4.1.318.1.2.3.4.26.2 pcnsMaxInternalTempExceededEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsMaxInternalTempExceeded 2 } -- 1.3.6.1.4.1.318.1.2.3.4.26.3 -- 1.3.6.1.4.1.318.1.2.3.4.26.3 pcnsMaxInternalTempExceededEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsMaxInternalTempExceeded 3 } -- 1.3.6.1.4.1.318.1.2.3.4.26.4 -- 1.3.6.1.4.1.318.1.2.3.4.26.4 pcnsMaxInternalTempExceededCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsMaxInternalTempExceeded 4 } -- 1.3.6.1.4.1.318.1.2.3.4.26.5 -- 1.3.6.1.4.1.318.1.2.3.4.26.5 pcnsMaxInternalTempExceededCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsMaxInternalTempExceeded 5 } -- 1.3.6.1.4.1.318.1.2.3.4.26.6 -- 1.3.6.1.4.1.318.1.2.3.4.26.6 pcnsMaxInternalTempExceededEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsMaxInternalTempExceeded 6 } -- 1.3.6.1.4.1.318.1.2.3.4.26.7 -- 1.3.6.1.4.1.318.1.2.3.4.26.7 pcnsMaxInternalTempExceededShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsMaxInternalTempExceeded 7 } -- 1.3.6.1.4.1.318.1.2.3.4.27 -- 1.3.6.1.4.1.318.1.2.3.4.27 pcnsMaxInternalTempInRange OBJECT IDENTIFIER ::= { pcnsEvents 27 } -- 1.3.6.1.4.1.318.1.2.3.4.27.1 -- 1.3.6.1.4.1.318.1.2.3.4.27.1 pcnsMaxInternalTempInRangeDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsMaxInternalTempInRange 1 } -- 1.3.6.1.4.1.318.1.2.3.4.27.2 -- 1.3.6.1.4.1.318.1.2.3.4.27.2 pcnsMaxInternalTempInRangeEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsMaxInternalTempInRange 2 } -- 1.3.6.1.4.1.318.1.2.3.4.27.3 -- 1.3.6.1.4.1.318.1.2.3.4.27.3 pcnsMaxInternalTempInRangeEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsMaxInternalTempInRange 3 } -- 1.3.6.1.4.1.318.1.2.3.4.27.4 -- 1.3.6.1.4.1.318.1.2.3.4.27.4 pcnsMaxInternalTempInRangeCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsMaxInternalTempInRange 4 } -- 1.3.6.1.4.1.318.1.2.3.4.27.5 -- 1.3.6.1.4.1.318.1.2.3.4.27.5 pcnsMaxInternalTempInRangeCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsMaxInternalTempInRange 5 } -- 1.3.6.1.4.1.318.1.2.3.4.28 -- 1.3.6.1.4.1.318.1.2.3.4.28 pcnsMinLoadCapabilityLost OBJECT IDENTIFIER ::= { pcnsEvents 28 } -- 1.3.6.1.4.1.318.1.2.3.4.28.1 -- 1.3.6.1.4.1.318.1.2.3.4.28.1 pcnsMinLoadCapabilityLostDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsMinLoadCapabilityLost 1 } -- 1.3.6.1.4.1.318.1.2.3.4.28.2 -- 1.3.6.1.4.1.318.1.2.3.4.28.2 pcnsMinLoadCapabilityLostEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsMinLoadCapabilityLost 2 } -- 1.3.6.1.4.1.318.1.2.3.4.28.3 -- 1.3.6.1.4.1.318.1.2.3.4.28.3 pcnsMinLoadCapabilityLostEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsMinLoadCapabilityLost 3 } -- 1.3.6.1.4.1.318.1.2.3.4.28.4 -- 1.3.6.1.4.1.318.1.2.3.4.28.4 pcnsMinLoadCapabilityLostCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsMinLoadCapabilityLost 4 } -- 1.3.6.1.4.1.318.1.2.3.4.28.5 -- 1.3.6.1.4.1.318.1.2.3.4.28.5 pcnsMinLoadCapabilityLostCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsMinLoadCapabilityLost 5 } -- 1.3.6.1.4.1.318.1.2.3.4.28.6 -- 1.3.6.1.4.1.318.1.2.3.4.28.6 pcnsMinLoadCapabilityLostEnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsMinLoadCapabilityLost 6 } -- 1.3.6.1.4.1.318.1.2.3.4.28.7 -- 1.3.6.1.4.1.318.1.2.3.4.28.7 pcnsMinLoadCapabilityLostShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsMinLoadCapabilityLost 7 } -- 1.3.6.1.4.1.318.1.2.3.4.29 -- 1.3.6.1.4.1.318.1.2.3.4.29 pcnsMinLoadCapabilityRegained OBJECT IDENTIFIER ::= { pcnsEvents 29 } -- 1.3.6.1.4.1.318.1.2.3.4.29.1 -- 1.3.6.1.4.1.318.1.2.3.4.29.1 pcnsMinLoadCapabilityRegainedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsMinLoadCapabilityRegained 1 } -- 1.3.6.1.4.1.318.1.2.3.4.29.2 -- 1.3.6.1.4.1.318.1.2.3.4.29.2 pcnsMinLoadCapabilityRegainedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsMinLoadCapabilityRegained 2 } -- 1.3.6.1.4.1.318.1.2.3.4.29.3 -- 1.3.6.1.4.1.318.1.2.3.4.29.3 pcnsMinLoadCapabilityRegainedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsMinLoadCapabilityRegained 3 } -- 1.3.6.1.4.1.318.1.2.3.4.29.4 -- 1.3.6.1.4.1.318.1.2.3.4.29.4 pcnsMinLoadCapabilityRegainedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsMinLoadCapabilityRegained 4 } -- 1.3.6.1.4.1.318.1.2.3.4.29.5 -- 1.3.6.1.4.1.318.1.2.3.4.29.5 pcnsMinLoadCapabilityRegainedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsMinLoadCapabilityRegained 5 } -- PCNS Environmental Monitoring Card Events -- 1.3.6.1.4.1.318.1.2.3.4.30 -- 1.3.6.1.4.1.318.1.2.3.4.30 pcnsEnvironmentCommunicationEstablished OBJECT IDENTIFIER ::= { pcnsEvents 30 } -- 1.3.6.1.4.1.318.1.2.3.4.30.1 -- 1.3.6.1.4.1.318.1.2.3.4.30.1 pcnsEnvironmentCommunicationEstablishedDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsEnvironmentCommunicationEstablished 1 } -- 1.3.6.1.4.1.318.1.2.3.4.30.2 -- 1.3.6.1.4.1.318.1.2.3.4.30.2 pcnsEnvironmentCommunicationEstablishedEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsEnvironmentCommunicationEstablished 2 } -- 1.3.6.1.4.1.318.1.2.3.4.30.3 -- 1.3.6.1.4.1.318.1.2.3.4.30.3 pcnsEnvironmentCommunicationEstablishedEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsEnvironmentCommunicationEstablished 3 } -- 1.3.6.1.4.1.318.1.2.3.4.30.4 -- 1.3.6.1.4.1.318.1.2.3.4.30.4 pcnsEnvironmentCommunicationEstablishedCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsEnvironmentCommunicationEstablished 4 } -- 1.3.6.1.4.1.318.1.2.3.4.30.5 -- 1.3.6.1.4.1.318.1.2.3.4.30.5 pcnsEnvironmentCommunicationEstablishedCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsEnvironmentCommunicationEstablished 5 } -- 1.3.6.1.4.1.318.1.2.3.4.31 -- 1.3.6.1.4.1.318.1.2.3.4.31 pcnsEnvironmentCommunicationLost OBJECT IDENTIFIER ::= { pcnsEvents 31 } -- 1.3.6.1.4.1.318.1.2.3.4.31.1 -- 1.3.6.1.4.1.318.1.2.3.4.31.1 pcnsEnvironmentCommunicationLostDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsEnvironmentCommunicationLost 1 } -- 1.3.6.1.4.1.318.1.2.3.4.31.2 -- 1.3.6.1.4.1.318.1.2.3.4.31.2 pcnsEnvironmentCommunicationLostEnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsEnvironmentCommunicationLost 2 } -- 1.3.6.1.4.1.318.1.2.3.4.31.3 -- 1.3.6.1.4.1.318.1.2.3.4.31.3 pcnsEnvironmentCommunicationLostEnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsEnvironmentCommunicationLost 3 } -- 1.3.6.1.4.1.318.1.2.3.4.31.4 -- 1.3.6.1.4.1.318.1.2.3.4.31.4 pcnsEnvironmentCommunicationLostCommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsEnvironmentCommunicationLost 4 } -- 1.3.6.1.4.1.318.1.2.3.4.31.5 -- 1.3.6.1.4.1.318.1.2.3.4.31.5 pcnsEnvironmentCommunicationLostCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsEnvironmentCommunicationLost 5 } -- 1.3.6.1.4.1.318.1.2.3.4.32 -- 1.3.6.1.4.1.318.1.2.3.4.32 pcnsTempInRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 32 } -- 1.3.6.1.4.1.318.1.2.3.4.32.1 -- 1.3.6.1.4.1.318.1.2.3.4.32.1 pcnsTempInRangeProbe1Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsTempInRangeProbe1 1 } -- 1.3.6.1.4.1.318.1.2.3.4.32.2 -- 1.3.6.1.4.1.318.1.2.3.4.32.2 pcnsTempInRangeProbe1EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsTempInRangeProbe1 2 } -- 1.3.6.1.4.1.318.1.2.3.4.32.3 -- 1.3.6.1.4.1.318.1.2.3.4.32.3 pcnsTempInRangeProbe1EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsTempInRangeProbe1 3 } -- 1.3.6.1.4.1.318.1.2.3.4.32.4 -- 1.3.6.1.4.1.318.1.2.3.4.32.4 pcnsTempInRangeProbe1CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsTempInRangeProbe1 4 } -- 1.3.6.1.4.1.318.1.2.3.4.32.5 -- 1.3.6.1.4.1.318.1.2.3.4.32.5 pcnsTempInRangeProbe1CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsTempInRangeProbe1 5 } -- 1.3.6.1.4.1.318.1.2.3.4.33 -- 1.3.6.1.4.1.318.1.2.3.4.33 pcnsTempOutOfRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 33 } -- 1.3.6.1.4.1.318.1.2.3.4.33.1 -- 1.3.6.1.4.1.318.1.2.3.4.33.1 pcnsTempOutOfRangeProbe1Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsTempOutOfRangeProbe1 1 } -- 1.3.6.1.4.1.318.1.2.3.4.33.2 -- 1.3.6.1.4.1.318.1.2.3.4.33.2 pcnsTempOutOfRangeProbe1EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsTempOutOfRangeProbe1 2 } -- 1.3.6.1.4.1.318.1.2.3.4.33.3 -- 1.3.6.1.4.1.318.1.2.3.4.33.3 pcnsTempOutOfRangeProbe1EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsTempOutOfRangeProbe1 3 } -- 1.3.6.1.4.1.318.1.2.3.4.33.4 -- 1.3.6.1.4.1.318.1.2.3.4.33.4 pcnsTempOutOfRangeProbe1CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsTempOutOfRangeProbe1 4 } -- 1.3.6.1.4.1.318.1.2.3.4.33.5 -- 1.3.6.1.4.1.318.1.2.3.4.33.5 pcnsTempOutOfRangeProbe1CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsTempOutOfRangeProbe1 5 } -- 1.3.6.1.4.1.318.1.2.3.4.33.6 -- 1.3.6.1.4.1.318.1.2.3.4.33.6 pcnsTempOutOfRangeProbe1EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsTempOutOfRangeProbe1 6 } -- 1.3.6.1.4.1.318.1.2.3.4.33.7 -- 1.3.6.1.4.1.318.1.2.3.4.33.7 pcnsTempOutOfRangeProbe1ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsTempOutOfRangeProbe1 7 } -- 1.3.6.1.4.1.318.1.2.3.4.34 -- 1.3.6.1.4.1.318.1.2.3.4.34 pcnsHumidityInRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 34 } -- 1.3.6.1.4.1.318.1.2.3.4.34.1 -- 1.3.6.1.4.1.318.1.2.3.4.34.1 pcnsHumidityInRangeProbe1Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsHumidityInRangeProbe1 1 } -- 1.3.6.1.4.1.318.1.2.3.4.34.2 -- 1.3.6.1.4.1.318.1.2.3.4.34.2 pcnsHumidityInRangeProbe1EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsHumidityInRangeProbe1 2 } -- 1.3.6.1.4.1.318.1.2.3.4.34.3 -- 1.3.6.1.4.1.318.1.2.3.4.34.3 pcnsHumidityInRangeProbe1EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsHumidityInRangeProbe1 3 } -- 1.3.6.1.4.1.318.1.2.3.4.34.4 -- 1.3.6.1.4.1.318.1.2.3.4.34.4 pcnsHumidityInRangeProbe1CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsHumidityInRangeProbe1 4 } -- 1.3.6.1.4.1.318.1.2.3.4.34.5 -- 1.3.6.1.4.1.318.1.2.3.4.34.5 pcnsHumidityInRangeProbe1CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsHumidityInRangeProbe1 5 } -- 1.3.6.1.4.1.318.1.2.3.4.35 -- 1.3.6.1.4.1.318.1.2.3.4.35 pcnsHumidityOutOfRangeProbe1 OBJECT IDENTIFIER ::= { pcnsEvents 35 } -- 1.3.6.1.4.1.318.1.2.3.4.35.1 -- 1.3.6.1.4.1.318.1.2.3.4.35.1 pcnsHumidityOutOfRangeProbe1Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsHumidityOutOfRangeProbe1 1 } -- 1.3.6.1.4.1.318.1.2.3.4.35.2 -- 1.3.6.1.4.1.318.1.2.3.4.35.2 pcnsHumidityOutOfRangeProbe1EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsHumidityOutOfRangeProbe1 2 } -- 1.3.6.1.4.1.318.1.2.3.4.35.3 -- 1.3.6.1.4.1.318.1.2.3.4.35.3 pcnsHumidityOutOfRangeProbe1EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsHumidityOutOfRangeProbe1 3 } -- 1.3.6.1.4.1.318.1.2.3.4.35.4 -- 1.3.6.1.4.1.318.1.2.3.4.35.4 pcnsHumidityOutOfRangeProbe1CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsHumidityOutOfRangeProbe1 4 } -- 1.3.6.1.4.1.318.1.2.3.4.35.5 -- 1.3.6.1.4.1.318.1.2.3.4.35.5 pcnsHumidityOutOfRangeProbe1CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsHumidityOutOfRangeProbe1 5 } -- 1.3.6.1.4.1.318.1.2.3.4.35.6 -- 1.3.6.1.4.1.318.1.2.3.4.35.6 pcnsHumidityOutOfRangeProbe1EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsHumidityOutOfRangeProbe1 6 } -- 1.3.6.1.4.1.318.1.2.3.4.35.7 -- 1.3.6.1.4.1.318.1.2.3.4.35.7 pcnsHumidityOutOfRangeProbe1ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsHumidityOutOfRangeProbe1 7 } -- 1.3.6.1.4.1.318.1.2.3.4.36 -- 1.3.6.1.4.1.318.1.2.3.4.36 pcnsTempInRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 36 } -- 1.3.6.1.4.1.318.1.2.3.4.36.1 -- 1.3.6.1.4.1.318.1.2.3.4.36.1 pcnsTempInRangeProbe2Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsTempInRangeProbe2 1 } -- 1.3.6.1.4.1.318.1.2.3.4.36.2 -- 1.3.6.1.4.1.318.1.2.3.4.36.2 pcnsTempInRangeProbe2EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsTempInRangeProbe2 2 } -- 1.3.6.1.4.1.318.1.2.3.4.36.3 -- 1.3.6.1.4.1.318.1.2.3.4.36.3 pcnsTempInRangeProbe2EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsTempInRangeProbe2 3 } -- 1.3.6.1.4.1.318.1.2.3.4.36.4 -- 1.3.6.1.4.1.318.1.2.3.4.36.4 pcnsTempInRangeProbe2CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsTempInRangeProbe2 4 } -- 1.3.6.1.4.1.318.1.2.3.4.36.5 -- 1.3.6.1.4.1.318.1.2.3.4.36.5 pcnsTempInRangeProbe2CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsTempInRangeProbe2 5 } -- 1.3.6.1.4.1.318.1.2.3.4.37 -- 1.3.6.1.4.1.318.1.2.3.4.37 pcnsTempOutOfRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 37 } -- 1.3.6.1.4.1.318.1.2.3.4.37.1 -- 1.3.6.1.4.1.318.1.2.3.4.37.1 pcnsTempOutOfRangeProbe2Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsTempOutOfRangeProbe2 1 } -- 1.3.6.1.4.1.318.1.2.3.4.37.2 -- 1.3.6.1.4.1.318.1.2.3.4.37.2 pcnsTempOutOfRangeProbe2EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsTempOutOfRangeProbe2 2 } -- 1.3.6.1.4.1.318.1.2.3.4.37.3 -- 1.3.6.1.4.1.318.1.2.3.4.37.3 pcnsTempOutOfRangeProbe2EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsTempOutOfRangeProbe2 3 } -- 1.3.6.1.4.1.318.1.2.3.4.37.4 -- 1.3.6.1.4.1.318.1.2.3.4.37.4 pcnsTempOutOfRangeProbe2CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsTempOutOfRangeProbe2 4 } -- 1.3.6.1.4.1.318.1.2.3.4.37.5 -- 1.3.6.1.4.1.318.1.2.3.4.37.5 pcnsTempOutOfRangeProbe2CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsTempOutOfRangeProbe2 5 } -- 1.3.6.1.4.1.318.1.2.3.4.37.6 -- 1.3.6.1.4.1.318.1.2.3.4.37.6 pcnsTempOutOfRangeProbe2EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsTempOutOfRangeProbe2 6 } -- 1.3.6.1.4.1.318.1.2.3.4.37.7 -- 1.3.6.1.4.1.318.1.2.3.4.37.7 pcnsTempOutOfRangeProbe2ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsTempOutOfRangeProbe2 7 } -- 1.3.6.1.4.1.318.1.2.3.4.38 -- 1.3.6.1.4.1.318.1.2.3.4.38 pcnsHumidityInRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 38 } -- 1.3.6.1.4.1.318.1.2.3.4.38.1 -- 1.3.6.1.4.1.318.1.2.3.4.38.1 pcnsHumidityInRangeProbe2Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsHumidityInRangeProbe2 1 } -- 1.3.6.1.4.1.318.1.2.3.4.38.2 -- 1.3.6.1.4.1.318.1.2.3.4.38.2 pcnsHumidityInRangeProbe2EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsHumidityInRangeProbe2 2 } -- 1.3.6.1.4.1.318.1.2.3.4.38.3 -- 1.3.6.1.4.1.318.1.2.3.4.38.3 pcnsHumidityInRangeProbe2EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsHumidityInRangeProbe2 3 } -- 1.3.6.1.4.1.318.1.2.3.4.38.4 -- 1.3.6.1.4.1.318.1.2.3.4.38.4 pcnsHumidityInRangeProbe2CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsHumidityInRangeProbe2 4 } -- 1.3.6.1.4.1.318.1.2.3.4.38.5 -- 1.3.6.1.4.1.318.1.2.3.4.38.5 pcnsHumidityInRangeProbe2CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsHumidityInRangeProbe2 5 } -- 1.3.6.1.4.1.318.1.2.3.4.39 -- 1.3.6.1.4.1.318.1.2.3.4.39 pcnsHumidityOutOfRangeProbe2 OBJECT IDENTIFIER ::= { pcnsEvents 39 } -- 1.3.6.1.4.1.318.1.2.3.4.39.1 -- 1.3.6.1.4.1.318.1.2.3.4.39.1 pcnsHumidityOutOfRangeProbe2Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsHumidityOutOfRangeProbe2 1 } -- 1.3.6.1.4.1.318.1.2.3.4.39.2 -- 1.3.6.1.4.1.318.1.2.3.4.39.2 pcnsHumidityOutOfRangeProbe2EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsHumidityOutOfRangeProbe2 2 } -- 1.3.6.1.4.1.318.1.2.3.4.39.3 -- 1.3.6.1.4.1.318.1.2.3.4.39.3 pcnsHumidityOutOfRangeProbe2EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsHumidityOutOfRangeProbe2 3 } -- 1.3.6.1.4.1.318.1.2.3.4.39.4 -- 1.3.6.1.4.1.318.1.2.3.4.39.4 pcnsHumidityOutOfRangeProbe2CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsHumidityOutOfRangeProbe2 4 } -- 1.3.6.1.4.1.318.1.2.3.4.39.5 -- 1.3.6.1.4.1.318.1.2.3.4.39.5 pcnsHumidityOutOfRangeProbe2CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsHumidityOutOfRangeProbe2 5 } -- 1.3.6.1.4.1.318.1.2.3.4.39.6 -- 1.3.6.1.4.1.318.1.2.3.4.39.6 pcnsHumidityOutOfRangeProbe2EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsHumidityOutOfRangeProbe2 6 } -- 1.3.6.1.4.1.318.1.2.3.4.39.7 -- 1.3.6.1.4.1.318.1.2.3.4.39.7 pcnsHumidityOutOfRangeProbe2ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsHumidityOutOfRangeProbe2 7 } -- 1.3.6.1.4.1.318.1.2.3.4.40 -- 1.3.6.1.4.1.318.1.2.3.4.40 pcnsContactFault1 OBJECT IDENTIFIER ::= { pcnsEvents 40 } -- 1.3.6.1.4.1.318.1.2.3.4.40.1 -- 1.3.6.1.4.1.318.1.2.3.4.40.1 pcnsContactFault1Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactFault1 1 } -- 1.3.6.1.4.1.318.1.2.3.4.40.2 -- 1.3.6.1.4.1.318.1.2.3.4.40.2 pcnsContactFault1EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactFault1 2 } -- 1.3.6.1.4.1.318.1.2.3.4.40.3 -- 1.3.6.1.4.1.318.1.2.3.4.40.3 pcnsContactFault1EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactFault1 3 } -- 1.3.6.1.4.1.318.1.2.3.4.40.4 -- 1.3.6.1.4.1.318.1.2.3.4.40.4 pcnsContactFault1CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactFault1 4 } -- 1.3.6.1.4.1.318.1.2.3.4.40.5 -- 1.3.6.1.4.1.318.1.2.3.4.40.5 pcnsContactFault1CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactFault1 5 } -- 1.3.6.1.4.1.318.1.2.3.4.40.6 -- 1.3.6.1.4.1.318.1.2.3.4.40.6 pcnsContactFault1EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsContactFault1 6 } -- 1.3.6.1.4.1.318.1.2.3.4.40.7 -- 1.3.6.1.4.1.318.1.2.3.4.40.7 pcnsContactFault1ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsContactFault1 7 } -- 1.3.6.1.4.1.318.1.2.3.4.41 -- 1.3.6.1.4.1.318.1.2.3.4.41 pcnsContactFault2 OBJECT IDENTIFIER ::= { pcnsEvents 41 } -- 1.3.6.1.4.1.318.1.2.3.4.41.1 -- 1.3.6.1.4.1.318.1.2.3.4.41.1 pcnsContactFault2Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactFault2 1 } -- 1.3.6.1.4.1.318.1.2.3.4.41.2 -- 1.3.6.1.4.1.318.1.2.3.4.41.2 pcnsContactFault2EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactFault2 2 } -- 1.3.6.1.4.1.318.1.2.3.4.41.3 -- 1.3.6.1.4.1.318.1.2.3.4.41.3 pcnsContactFault2EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactFault2 3 } -- 1.3.6.1.4.1.318.1.2.3.4.41.4 -- 1.3.6.1.4.1.318.1.2.3.4.41.4 pcnsContactFault2CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactFault2 4 } -- 1.3.6.1.4.1.318.1.2.3.4.41.5 -- 1.3.6.1.4.1.318.1.2.3.4.41.5 pcnsContactFault2CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactFault2 5 } -- 1.3.6.1.4.1.318.1.2.3.4.41.6 -- 1.3.6.1.4.1.318.1.2.3.4.41.6 pcnsContactFault2EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsContactFault2 6 } -- 1.3.6.1.4.1.318.1.2.3.4.41.7 -- 1.3.6.1.4.1.318.1.2.3.4.41.7 pcnsContactFault2ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsContactFault2 7 } -- 1.3.6.1.4.1.318.1.2.3.4.42 -- 1.3.6.1.4.1.318.1.2.3.4.42 pcnsContactFault3 OBJECT IDENTIFIER ::= { pcnsEvents 42 } -- 1.3.6.1.4.1.318.1.2.3.4.42.1 -- 1.3.6.1.4.1.318.1.2.3.4.42.1 pcnsContactFault3Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactFault3 1 } -- 1.3.6.1.4.1.318.1.2.3.4.42.2 -- 1.3.6.1.4.1.318.1.2.3.4.42.2 pcnsContactFault3EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactFault3 2 } -- 1.3.6.1.4.1.318.1.2.3.4.42.3 -- 1.3.6.1.4.1.318.1.2.3.4.42.3 pcnsContactFault3EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactFault3 3 } -- 1.3.6.1.4.1.318.1.2.3.4.42.4 -- 1.3.6.1.4.1.318.1.2.3.4.42.4 pcnsContactFault3CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactFault3 4 } -- 1.3.6.1.4.1.318.1.2.3.4.42.5 -- 1.3.6.1.4.1.318.1.2.3.4.42.5 pcnsContactFault3CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactFault3 5 } -- 1.3.6.1.4.1.318.1.2.3.4.42.6 -- 1.3.6.1.4.1.318.1.2.3.4.42.6 pcnsContactFault3EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsContactFault3 6 } -- 1.3.6.1.4.1.318.1.2.3.4.42.7 -- 1.3.6.1.4.1.318.1.2.3.4.42.7 pcnsContactFault3ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsContactFault3 7 } -- 1.3.6.1.4.1.318.1.2.3.4.43 -- 1.3.6.1.4.1.318.1.2.3.4.43 pcnsContactFault4 OBJECT IDENTIFIER ::= { pcnsEvents 43 } -- 1.3.6.1.4.1.318.1.2.3.4.43.1 -- 1.3.6.1.4.1.318.1.2.3.4.43.1 pcnsContactFault4Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactFault4 1 } -- 1.3.6.1.4.1.318.1.2.3.4.43.2 -- 1.3.6.1.4.1.318.1.2.3.4.43.2 pcnsContactFault4EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactFault4 2 } -- 1.3.6.1.4.1.318.1.2.3.4.43.3 -- 1.3.6.1.4.1.318.1.2.3.4.43.3 pcnsContactFault4EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactFault4 3 } -- 1.3.6.1.4.1.318.1.2.3.4.43.4 -- 1.3.6.1.4.1.318.1.2.3.4.43.4 pcnsContactFault4CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactFault4 4 } -- 1.3.6.1.4.1.318.1.2.3.4.43.5 -- 1.3.6.1.4.1.318.1.2.3.4.43.5 pcnsContactFault4CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactFault4 5 } -- 1.3.6.1.4.1.318.1.2.3.4.43.6 -- 1.3.6.1.4.1.318.1.2.3.4.43.6 pcnsContactFault4EnableShutdown OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Perform a graceful shutdown of the server when this event occurs." ::= { pcnsContactFault4 6 } -- 1.3.6.1.4.1.318.1.2.3.4.43.7 -- 1.3.6.1.4.1.318.1.2.3.4.43.7 pcnsContactFault4ShutdownDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before performing a graceful shutdown of the server (seconds)." ::= { pcnsContactFault4 7 } -- 1.3.6.1.4.1.318.1.2.3.4.44 -- 1.3.6.1.4.1.318.1.2.3.4.44 pcnsContactNormal1 OBJECT IDENTIFIER ::= { pcnsEvents 44 } -- 1.3.6.1.4.1.318.1.2.3.4.44.1 -- 1.3.6.1.4.1.318.1.2.3.4.44.1 pcnsContactNormal1Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactNormal1 1 } -- 1.3.6.1.4.1.318.1.2.3.4.44.2 -- 1.3.6.1.4.1.318.1.2.3.4.44.2 pcnsContactNormal1EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactNormal1 2 } -- 1.3.6.1.4.1.318.1.2.3.4.44.3 -- 1.3.6.1.4.1.318.1.2.3.4.44.3 pcnsContactNormal1EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactNormal1 3 } -- 1.3.6.1.4.1.318.1.2.3.4.44.4 -- 1.3.6.1.4.1.318.1.2.3.4.44.4 pcnsContactNormal1CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactNormal1 4 } -- 1.3.6.1.4.1.318.1.2.3.4.44.5 -- 1.3.6.1.4.1.318.1.2.3.4.44.5 pcnsContactNormal1CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactNormal1 5 } -- 1.3.6.1.4.1.318.1.2.3.4.45 -- 1.3.6.1.4.1.318.1.2.3.4.45 pcnsContactNormal2 OBJECT IDENTIFIER ::= { pcnsEvents 45 } -- 1.3.6.1.4.1.318.1.2.3.4.45.1 -- 1.3.6.1.4.1.318.1.2.3.4.45.1 pcnsContactNormal2Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactNormal2 1 } -- 1.3.6.1.4.1.318.1.2.3.4.45.2 -- 1.3.6.1.4.1.318.1.2.3.4.45.2 pcnsContactNormal2EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactNormal2 2 } -- 1.3.6.1.4.1.318.1.2.3.4.45.3 -- 1.3.6.1.4.1.318.1.2.3.4.45.3 pcnsContactNormal2EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactNormal2 3 } -- 1.3.6.1.4.1.318.1.2.3.4.45.4 -- 1.3.6.1.4.1.318.1.2.3.4.45.4 pcnsContactNormal2CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactNormal2 4 } -- 1.3.6.1.4.1.318.1.2.3.4.45.5 -- 1.3.6.1.4.1.318.1.2.3.4.45.5 pcnsContactNormal2CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactNormal2 5 } -- 1.3.6.1.4.1.318.1.2.3.4.46 -- 1.3.6.1.4.1.318.1.2.3.4.46 pcnsContactNormal3 OBJECT IDENTIFIER ::= { pcnsEvents 46 } -- 1.3.6.1.4.1.318.1.2.3.4.46.1 -- 1.3.6.1.4.1.318.1.2.3.4.46.1 pcnsContactNormal3Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactNormal3 1 } -- 1.3.6.1.4.1.318.1.2.3.4.46.2 -- 1.3.6.1.4.1.318.1.2.3.4.46.2 pcnsContactNormal3EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactNormal3 2 } -- 1.3.6.1.4.1.318.1.2.3.4.46.3 -- 1.3.6.1.4.1.318.1.2.3.4.46.3 pcnsContactNormal3EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactNormal3 3 } -- 1.3.6.1.4.1.318.1.2.3.4.46.4 -- 1.3.6.1.4.1.318.1.2.3.4.46.4 pcnsContactNormal3CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactNormal3 4 } -- 1.3.6.1.4.1.318.1.2.3.4.46.5 -- 1.3.6.1.4.1.318.1.2.3.4.46.5 pcnsContactNormal3CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactNormal3 5 } -- 1.3.6.1.4.1.318.1.2.3.4.47 -- 1.3.6.1.4.1.318.1.2.3.4.47 pcnsContactNormal4 OBJECT IDENTIFIER ::= { pcnsEvents 47 } -- 1.3.6.1.4.1.318.1.2.3.4.47.1 -- 1.3.6.1.4.1.318.1.2.3.4.47.1 pcnsContactNormal4Desc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The Description of the event." ::= { pcnsContactNormal4 1 } -- 1.3.6.1.4.1.318.1.2.3.4.47.2 -- 1.3.6.1.4.1.318.1.2.3.4.47.2 pcnsContactNormal4EnableLogging OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Log occurrences of this event in PCNS log." ::= { pcnsContactNormal4 2 } -- 1.3.6.1.4.1.318.1.2.3.4.47.3 -- 1.3.6.1.4.1.318.1.2.3.4.47.3 pcnsContactNormal4EnableCommandFile OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Execute a command file when this event occurs." ::= { pcnsContactNormal4 3 } -- 1.3.6.1.4.1.318.1.2.3.4.47.4 -- 1.3.6.1.4.1.318.1.2.3.4.47.4 pcnsContactNormal4CommandFilePath OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Path of command file to execute when this event occurs." ::= { pcnsContactNormal4 4 } -- 1.3.6.1.4.1.318.1.2.3.4.47.5 -- 1.3.6.1.4.1.318.1.2.3.4.47.5 pcnsContactNormal4CommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long to wait after event occurs before executing command file (seconds)." ::= { pcnsContactNormal4 5 } -- 1.3.6.1.4.1.318.1.2.3.5 -- 1.3.6.1.4.1.318.1.2.3.5 pcnsShutdown OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 5 } -- the software group -- the powerChuteNetworkShutdown group -- the pcnsShutdown group -- 1.3.6.1.4.1.318.1.2.3.5.1 -- 1.3.6.1.4.1.318.1.2.3.5.1 pcnsShutdownCommandFileEnabled OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Run a shutdown command file before performing graceful shutdown." ::= { pcnsShutdown 1 } -- 1.3.6.1.4.1.318.1.2.3.5.2 -- 1.3.6.1.4.1.318.1.2.3.5.2 pcnsShutdownCommandFileDelay OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long in seconds to wait before running a shutdown command file before graceful shutdown." ::= { pcnsShutdown 2 } -- 1.3.6.1.4.1.318.1.2.3.5.3 -- 1.3.6.1.4.1.318.1.2.3.5.3 pcnsShutdownCommandFile OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Full name of the shutdown command file to run before graceful shutdown." ::= { pcnsShutdown 3 } -- 1.3.6.1.4.1.318.1.2.3.5.4 -- 1.3.6.1.4.1.318.1.2.3.5.4 pcnsShutdownCommandFileDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long in seconds shutdown command file takes to run." ::= { pcnsShutdown 4 } -- 1.3.6.1.4.1.318.1.2.3.5.5 -- 1.3.6.1.4.1.318.1.2.3.5.5 pcnsTurnOffUps OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Turn off the UPS when performing a graceful shutdown." ::= { pcnsShutdown 5 } -- 1.3.6.1.4.1.318.1.2.3.5.6 -- 1.3.6.1.4.1.318.1.2.3.5.6 pcnsTurnOffSOG OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Turn off the Outlet Group on the UPS when performing a graceful shutdown." ::= { pcnsShutdown 6 } -- 1.3.6.1.4.1.318.1.2.3.5.7 -- 1.3.6.1.4.1.318.1.2.3.5.7 pcnsRuntimeRemainingThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "This defines a threshold for runtime remaining. When the UPS is running on battery power and the runtime remaining on the UPS drops below the threshold, PowerChute will trigger a shutdown sequence." ::= { pcnsShutdown 7 } -- 1.3.6.1.4.1.318.1.2.3.5.8 -- 1.3.6.1.4.1.318.1.2.3.5.8 pcnsRuntimeRemainingCmdFileThreshold OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "This defines a threshold for runtime remaining. When runtime remaining drops below this threshold, PowerChute will execute the command file." ::= { pcnsShutdown 8 } -- 1.3.6.1.4.1.318.1.2.3.5.9 -- 1.3.6.1.4.1.318.1.2.3.5.9 pcnsAdvancedShutdownTable OBJECT-TYPE SYNTAX SEQUENCE OF PCNSAdvancedShutdownEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown." ::= { pcnsShutdown 9 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1 -- 1.3.6.1.4.1.318.1.2.3.5.9.1 pcnsAdvancedShutdownEntry OBJECT-TYPE SYNTAX PCNSAdvancedShutdownEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "Details of the NMC." INDEX { pcnsAdvancedGroupNo } ::= { pcnsAdvancedShutdownTable 1 } PCNSAdvancedShutdownEntry ::= SEQUENCE { pcnsAdvancedGroupNo Gauge, pcnsAdvancedGroupName DisplayString, pcnsAdvancedGroupNMC DisplayString, pcnsAdvancedShutdownUPSRequiredForLoad INTEGER, pcnsAdvancedShutdownCommandFileEnabled INTEGER, pcnsAdvancedShutdownCommandFile DisplayString, pcnsAdvancedShutdownCommandFileDuration INTEGER, pcnsAdvancedShutdownPowerchuteServer INTEGER, pcnsAdvancedShutdownOnLostRedundancy INTEGER, pcnsAdvancedTurnOffUps INTEGER, pcnsAdvancedTurnOffSOG INTEGER } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.1 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.1 pcnsAdvancedGroupNo OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "Index of the Advanced Shutdown Group." ::= { pcnsAdvancedShutdownEntry 1 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.2 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.2 pcnsAdvancedGroupName OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-write STATUS mandatory DESCRIPTION "Name of the Advanced Shutdown Group." ::= { pcnsAdvancedShutdownEntry 2 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.3 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.3 pcnsAdvancedGroupNMC OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "List of NMCs in the Advanced Shutdown Group." ::= { pcnsAdvancedShutdownEntry 3 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.4 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.4 pcnsAdvancedShutdownUPSRequiredForLoad OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "Number of UPS's required to power load." ::= { pcnsAdvancedShutdownEntry 4 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.5 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.5 pcnsAdvancedShutdownCommandFileEnabled OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Run a shutdown command file before performing graceful shutdown." ::= { pcnsAdvancedShutdownEntry 5 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.6 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.6 pcnsAdvancedShutdownCommandFile OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Full name of the shutdown command file to run before graceful shutdown." ::= { pcnsAdvancedShutdownEntry 6 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.7 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.7 pcnsAdvancedShutdownCommandFileDuration OBJECT-TYPE SYNTAX INTEGER ACCESS read-write STATUS mandatory DESCRIPTION "How long in seconds shutdown command file takes to run." ::= { pcnsAdvancedShutdownEntry 7 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.8 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.8 pcnsAdvancedShutdownPowerchuteServer OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Shut down PowerChute Server." ::= { pcnsAdvancedShutdownEntry 8 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.9 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.9 pcnsAdvancedShutdownOnLostRedundancy OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Shut down if Redundancy lost." ::= { pcnsAdvancedShutdownEntry 9 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.10 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.10 pcnsAdvancedTurnOffUps OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Turn off the UPS when performing a graceful shutdown." ::= { pcnsAdvancedShutdownEntry 10 } -- 1.3.6.1.4.1.318.1.2.3.5.9.1.11 -- 1.3.6.1.4.1.318.1.2.3.5.9.1.11 pcnsAdvancedTurnOffSOG OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Turn off the Outlet Group on the UPS when performing a graceful shutdown." ::= { pcnsAdvancedShutdownEntry 11 } -- 1.3.6.1.4.1.318.1.2.3.6 -- 1.3.6.1.4.1.318.1.2.3.6 pcnsAlarms OBJECT IDENTIFIER ::= { powerChuteNetworkShutdown 6 } -- the software group -- the powerChuteNetworkShutdown group -- the pcnsAlarms group -- 1.3.6.1.4.1.318.1.2.3.6.1 -- 1.3.6.1.4.1.318.1.2.3.6.1 pcnsCriticalFlag OBJECT-TYPE SYNTAX INTEGER { active(1), clear(2) } ACCESS read-only STATUS mandatory DESCRIPTION "PowerChute Network Shutdown has begun a safe shutdown of the host." ::= { pcnsAlarms 1 } -- 1.3.6.1.4.1.318.1.2.3.6.2 -- 1.3.6.1.4.1.318.1.2.3.6.2 pcnsCriticalCause OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "The reason PowerChute Network Shutdown has begun a safe shutdown." ::= { pcnsAlarms 2 } -- 1.3.6.1.4.1.318.1.2.3.6.3 -- 1.3.6.1.4.1.318.1.2.3.6.3 pcnsNetComsLostFlag OBJECT-TYPE SYNTAX INTEGER { active(1), clear(2) } ACCESS read-only STATUS mandatory DESCRIPTION "PowerChute cannot communicate with NMC." ::= { pcnsAlarms 3 } -- 1.3.6.1.4.1.318.1.2.3.6.4 -- 1.3.6.1.4.1.318.1.2.3.6.4 pcnsNMCComsLostFlag OBJECT-TYPE SYNTAX INTEGER { active(1), clear(2) } ACCESS read-only STATUS mandatory DESCRIPTION "NMC cannot communicate with UPS." ::= { pcnsAlarms 4 } -- 1.3.6.1.4.1.318.1.2.3.6.5 -- 1.3.6.1.4.1.318.1.2.3.6.5 pcnsUpdateAvailableFlag OBJECT-TYPE SYNTAX INTEGER { active(1), clear(2) } ACCESS read-only STATUS mandatory DESCRIPTION "PowerChute has detected that a newer version is available." ::= { pcnsAlarms 5 } -- 1.3.6.1.4.1.318.1.2.3.6.6 -- 1.3.6.1.4.1.318.1.2.3.6.6 pcnsUpdateDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "Details of the newer version of PowerChute." ::= { pcnsAlarms 6 } -- 1.3.6.1.4.1.318.1.2.3.7 -- 1.3.6.1.4.1.318.1.2.3.7 pcnsLoggingLevel OBJECT-TYPE SYNTAX DisplayString (SIZE (0..6)) ACCESS read-write STATUS mandatory DESCRIPTION "Override the Root Logging level for PCNS. Possible Values: CLEAR, DEBUG" ::= { powerChuteNetworkShutdown 7 } -- 1.3.6.1.4.1.318.1.2.4 -- 1.3.6.1.4.1.318.1.2.4 powerChuteBusinessEdition OBJECT IDENTIFIER ::= { software 4 } -- 1.3.6.1.4.1.318.1.2.4.1 -- 1.3.6.1.4.1.318.1.2.4.1 pcbeIdent OBJECT IDENTIFIER ::= { powerChuteBusinessEdition 1 } -- the software group -- the powerChuteBusinessEdition group -- the pcbeIdent group -- 1.3.6.1.4.1.318.1.2.4.1.1 -- 1.3.6.1.4.1.318.1.2.4.1.1 pcbeHostname OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The hostname of the PCBE instance." ::= { pcbeIdent 1 } -- 1.3.6.1.4.1.318.1.2.4.1.2 -- 1.3.6.1.4.1.318.1.2.4.1.2 pcbeVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of PCBE installed. x.x.x" ::= { pcbeIdent 2 } -- 1.3.6.1.4.1.318.1.2.4.1.3 -- 1.3.6.1.4.1.318.1.2.4.1.3 pcbeOS OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of OS PCBE is installed on." ::= { pcbeIdent 3 } -- 1.3.6.1.4.1.318.1.2.4.1.4 -- 1.3.6.1.4.1.318.1.2.4.1.4 pcbeJavaVersion OBJECT-TYPE SYNTAX DisplayString (SIZE (0..32)) ACCESS read-only STATUS mandatory DESCRIPTION "The version of Java PCBE is running on." ::= { pcbeIdent 4 } -- 1.3.6.1.4.1.318.1.2.4.1.5 -- 1.3.6.1.4.1.318.1.2.4.1.5 pcbeUIProtocol OBJECT-TYPE SYNTAX INTEGER { http(1), https(2) } ACCESS read-only STATUS mandatory DESCRIPTION "Web Protocol used to connect to the PCBE UI." ::= { pcbeIdent 5 } -- 1.3.6.1.4.1.318.1.2.4.1.6 -- 1.3.6.1.4.1.318.1.2.4.1.6 pcbeHttpPort OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Port used for PCBE http UI." ::= { pcbeIdent 6 } -- 1.3.6.1.4.1.318.1.2.4.1.7 -- 1.3.6.1.4.1.318.1.2.4.1.7 pcbeHttpsPort OBJECT-TYPE SYNTAX INTEGER (0..65535) ACCESS read-only STATUS mandatory DESCRIPTION "Port used for PCBE https UI." ::= { pcbeIdent 7 } -- Deliberately leaving gap in the numbers so they are consistant with PCNS -- 1.3.6.1.4.1.318.1.2.4.6 -- 1.3.6.1.4.1.318.1.2.4.6 pcbeAlarms OBJECT IDENTIFIER ::= { powerChuteBusinessEdition 6 } -- the software group -- the powerChuteBusinessEdition group -- the pcbeAlarms group -- 1.3.6.1.4.1.318.1.2.4.6.1 -- 1.3.6.1.4.1.318.1.2.4.6.1 pcbeCriticalFlag OBJECT-TYPE SYNTAX INTEGER { active(1), clear(2) } ACCESS read-only STATUS mandatory DESCRIPTION "PowerChute Business Edition has begun a safe shutdown of the host." ::= { pcbeAlarms 1 } -- 1.3.6.1.4.1.318.1.2.4.6.2 -- 1.3.6.1.4.1.318.1.2.4.6.2 pcbeCriticalCause OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "The reason PowerChute Business Edition has begun a safe shutdown." ::= { pcbeAlarms 2 } -- 1.3.6.1.4.1.318.1.2.4.6.3 -- 1.3.6.1.4.1.318.1.2.4.6.3 pcbeComsLostFlag OBJECT-TYPE SYNTAX INTEGER { active(1), clear(2) } ACCESS read-only STATUS mandatory DESCRIPTION "If active (1), PowerChute cannot communicate with UPS" ::= { pcbeAlarms 3 } -- pcbeAlarms 4 is deliberately skipped to make this consistent with PCNS -- 1.3.6.1.4.1.318.1.2.4.6.5 -- 1.3.6.1.4.1.318.1.2.4.6.5 pcbeUpdateAvailableFlag OBJECT-TYPE SYNTAX INTEGER { active(1), clear(2) } ACCESS read-only STATUS mandatory DESCRIPTION "PowerChute has detected that a newer version is available." ::= { pcbeAlarms 5 } -- 1.3.6.1.4.1.318.1.2.4.6.6 -- 1.3.6.1.4.1.318.1.2.4.6.6 pcbeUpdateDesc OBJECT-TYPE SYNTAX DisplayString (SIZE (0..255)) ACCESS read-only STATUS mandatory DESCRIPTION "Details of the newer version of PowerChute." ::= { pcbeAlarms 6 } -- 1.3.6.1.4.1.318.1.3 -- 1.3.6.1.4.1.318.1.3 system OBJECT IDENTIFIER ::= { products 3 } -- 1.3.6.1.4.1.318.1.3.4 -- 1.3.6.1.4.1.318.1.3.4 masterSwitch OBJECT IDENTIFIER ::= { system 4 } -- 1.3.6.1.4.1.318.1.3.4.1 -- 1.3.6.1.4.1.318.1.3.4.1 masterSwitchV1 OBJECT IDENTIFIER ::= { masterSwitch 1 } -- 1.3.6.1.4.1.318.1.3.4.2 -- 1.3.6.1.4.1.318.1.3.4.2 masterSwitchV2 OBJECT IDENTIFIER ::= { masterSwitch 2 } -- 1.3.6.1.4.1.318.1.3.4.3 -- 1.3.6.1.4.1.318.1.3.4.3 masterSwitchVM OBJECT IDENTIFIER ::= { masterSwitch 3 } -- 1.3.6.1.4.1.318.1.3.4.4 -- 1.3.6.1.4.1.318.1.3.4.4 masterSwitchMSP OBJECT IDENTIFIER ::= { masterSwitch 4 } -- 1.3.6.1.4.1.318.1.3.4.5 -- 1.3.6.1.4.1.318.1.3.4.5 masterSwitchrPDU OBJECT IDENTIFIER ::= { masterSwitch 5 } -- 1.3.6.1.4.1.318.1.3.4.6 -- 1.3.6.1.4.1.318.1.3.4.6 masterSwitchrPDU2 OBJECT IDENTIFIER ::= { masterSwitch 6 } -- 1.3.6.1.4.1.318.1.3.4.7 -- 1.3.6.1.4.1.318.1.3.4.7 masterSwitchsPDU OBJECT IDENTIFIER ::= { masterSwitch 7 } -- 1.3.6.1.4.1.318.1.3.4.8 -- 1.3.6.1.4.1.318.1.3.4.8 masterSwitchrPDUB OBJECT IDENTIFIER ::= { masterSwitch 8 } -- 1.3.6.1.4.1.318.1.3.4.9 -- 1.3.6.1.4.1.318.1.3.4.9 masterSwitchePDU OBJECT IDENTIFIER ::= { masterSwitch 9 } -- 1.3.6.1.4.1.318.1.4 -- 1.3.6.1.4.1.318.1.4 experimental OBJECT IDENTIFIER ::= { products 4 } -- 1.3.6.1.4.1.318.2 -- 1.3.6.1.4.1.318.2 mgmt OBJECT IDENTIFIER ::= { PDU 2 } -- 1.3.6.1.4.1.318.2.1 -- 1.3.6.1.4.1.318.2.1 mconfig OBJECT IDENTIFIER ::= { mgmt 1 } -- object types -- the products group -- the experimental group -- the mgmt group -- the mconfig group -- 1.3.6.1.4.1.318.2.1.1 -- 1.3.6.1.4.1.318.2.1.1 mconfigNumTrapReceivers OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "The number of managers to send traps to." ::= { mconfig 1 } -- 1.3.6.1.4.1.318.2.1.2 -- 1.3.6.1.4.1.318.2.1.2 mconfigTrapReceiverTable OBJECT-TYPE SYNTAX SEQUENCE OF MconfigTrapReceiverEntry ACCESS not-accessible STATUS current DESCRIPTION "A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers." ::= { mconfig 2 } -- 1.3.6.1.4.1.318.2.1.2.1 -- 1.3.6.1.4.1.318.2.1.2.1 mconfigTrapReceiverEntry OBJECT-TYPE SYNTAX MconfigTrapReceiverEntry ACCESS not-accessible STATUS current DESCRIPTION "The managers to send traps to." INDEX { trapIndex } ::= { mconfigTrapReceiverTable 1 } MconfigTrapReceiverEntry ::= SEQUENCE { trapIndex INTEGER, receiverAddr IpAddress, communityString DisplayString, severity INTEGER, acceptThisReceiver INTEGER, receiveTrapType INTEGER } -- 1.3.6.1.4.1.318.2.1.2.1.1 -- 1.3.6.1.4.1.318.2.1.2.1.1 trapIndex OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "The index to a trap receiver entry." ::= { mconfigTrapReceiverEntry 1 } -- 1.3.6.1.4.1.318.2.1.2.1.2 -- 1.3.6.1.4.1.318.2.1.2.1.2 receiverAddr OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS current DESCRIPTION "The IP address of the manager to send a trap to." ::= { mconfigTrapReceiverEntry 2 } -- 1.3.6.1.4.1.318.2.1.2.1.3 -- 1.3.6.1.4.1.318.2.1.2.1.3 communityString OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS current DESCRIPTION "The community name to use in the trap when sent to the manager." ::= { mconfigTrapReceiverEntry 3 } -- 1.3.6.1.4.1.318.2.1.2.1.4 -- 1.3.6.1.4.1.318.2.1.2.1.4 severity OBJECT-TYPE SYNTAX INTEGER { information(1), warning(2), severe(3) } ACCESS read-only STATUS obsolete DESCRIPTION "The severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager." ::= { mconfigTrapReceiverEntry 4 } -- 1.3.6.1.4.1.318.2.1.2.1.5 -- 1.3.6.1.4.1.318.2.1.2.1.5 acceptThisReceiver OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-write STATUS current DESCRIPTION "The value of yes(1) indicates that trap generation for this manager is enabled. The value of no(2) indicates that trap generation for this manager is disabled" ::= { mconfigTrapReceiverEntry 5 } -- 1.3.6.1.4.1.318.2.1.2.1.6 -- 1.3.6.1.4.1.318.2.1.2.1.6 receiveTrapType OBJECT-TYPE SYNTAX INTEGER { powernet(1), ietf(2), both(3) } ACCESS read-only STATUS obsolete DESCRIPTION "Type of trap." ::= { mconfigTrapReceiverEntry 6 } -- 1.3.6.1.4.1.318.2.1.3 -- 1.3.6.1.4.1.318.2.1.3 mconfigBOOTPEnabled OBJECT-TYPE SYNTAX INTEGER { yes(1), no(2) } ACCESS read-only STATUS current DESCRIPTION "The value of yes(1) indicates the PowerNet Adapter is configured to obtain its IP configuration parameters from a BOOTP server. The value of no(2) indicates adapter will assume IP configuration parameters values saved in adapter's eeprom, which was originally configured at local console." ::= { mconfig 3 } -- 1.3.6.1.4.1.318.2.1.4 -- 1.3.6.1.4.1.318.2.1.4 mconfigTFTPServerIP OBJECT-TYPE SYNTAX IpAddress ACCESS read-write STATUS current DESCRIPTION "The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address is provided by BOOTP server and not allowed to be modified; otherwise, this IP address can be modified. Before using TFTP to load new code image, the image file should be placed in proper directory of the specified TFTP server. This OID is only supported by Network Management Cards." ::= { mconfig 4 } -- 1.3.6.1.4.1.318.2.1.5 -- 1.3.6.1.4.1.318.2.1.5 newCodeAuthentViaTFTP OBJECT-TYPE SYNTAX INTEGER { unknown(1), validNewAgentCodeImage(2), sameAgentCodeImage(3), invalidAgentCodeImage(4) } ACCESS read-only STATUS current DESCRIPTION "Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will start to load the remote image file, for authentication only, instead of saving the code into flash memory. Only if a validNewAgentCodeImage (1) is found will the agent reboot the PowerNet adapter and invoke the loader to load and save new code into the flash memory. Otherwise, the current agent code will continue to run. This OID shows the result of the above authentication process. validNewAgentCodeImage (1) means the code image on TFTP server is a valid agent code and is different version from the current agent. Once agent identifies this, loader will start to update flash memory with the new agent code. sameAgentCodeImage (2) means the code image on TFTP server is exactly the same as the currently running agent. Currently running agent will not invoke loader to load the same again. invalidAgentCodeImage (3) means the code image on TFTP server is NOT a valid agent code. Thus, current agent will not load it into the flash memory. The value of this OID will be associated with TRAP codeImageAuthentDone. This OID is only supported by Network Management Cards." ::= { mconfig 5 } -- 1.3.6.1.4.1.318.2.1.6 -- 1.3.6.1.4.1.318.2.1.6 mconfigClock OBJECT IDENTIFIER ::= { mconfig 6 } -- 1.3.6.1.4.1.318.2.1.6.1 -- 1.3.6.1.4.1.318.2.1.6.1 mconfigClockDate OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS current DESCRIPTION "The current date in the mm/dd/yyyy format. Example: 01/01/2000." ::= { mconfigClock 1 } -- 1.3.6.1.4.1.318.2.1.6.2 -- 1.3.6.1.4.1.318.2.1.6.2 mconfigClockTime OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS current DESCRIPTION "The current time in the hh:mm:ss am/pm format. Example: 12:00:00 am." ::= { mconfigClock 2 } -- 1.3.6.1.4.1.318.2.2 -- 1.3.6.1.4.1.318.2.2 mcontrol OBJECT IDENTIFIER ::= { mgmt 2 } -- 1.3.6.1.4.1.318.2.2.1 -- 1.3.6.1.4.1.318.2.2.1 mcontrolRestartAgent OBJECT-TYPE SYNTAX INTEGER { restartCurrentAgent(1), continueCurrentAgent(2), loadAndExecuteNewAgent(3), restartWithoutAgent(4), resetNetworkAndRestart(5), resetNetworkLeaveModeAndRestart(6) } ACCESS read-write STATUS current DESCRIPTION "Setting this OID to restartCurrentAgent (1) will restart the same SNMP agent code currently saved in flash memory. Setting this OID to loadAndExecuteNewAgent (3) will enable adapter to load a new agent code into the flash memory and start to execute this new agent code. Bootp/tftp is the default protocol. loadAndExecuteNewAgent is only supported by Network Management Cards. Setting this OID to restartWithoutAgent (4) will restart the system and not start the agent. The subsequent time the system restarts the agent will also automatically restart. Setting this OID to resetNetworkAndRestart (5) will set the Boot Mode, IP Address, Subnet Mask, and Default Gateway to defaults, expire any existing DHCP lease and then restart the system. Setting this OID to resetNetworkLeaveModeAndRestart (6) will leave the Boot Mode at the current setting, set the IP Address, Subnet Mask, and Default Gateway to defaults, expire any existing DHCP lease and then restart the system." ::= { mcontrol 1 } -- 1.3.6.1.4.1.318.2.3 -- 1.3.6.1.4.1.318.2.3 mtrapargs OBJECT IDENTIFIER ::= { mgmt 3 } -- The mtrapargs group -- These OIDs allows traps to be sent with additional arguments -- which may not be defined in the MIB. -- 1.3.6.1.4.1.318.2.3.1 -- 1.3.6.1.4.1.318.2.3.1 mtrapargsInteger OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 1 } -- 1.3.6.1.4.1.318.2.3.2 -- 1.3.6.1.4.1.318.2.3.2 mtrapargsIpAddress OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0." ::= { mtrapargs 2 } -- 1.3.6.1.4.1.318.2.3.3 -- 1.3.6.1.4.1.318.2.3.3 mtrapargsString OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 3 } -- 1.3.6.1.4.1.318.2.3.4 -- 1.3.6.1.4.1.318.2.3.4 mtrapargsGauge OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 4 } -- 1.3.6.1.4.1.318.2.3.5 -- 1.3.6.1.4.1.318.2.3.5 mtrapargsTimeTicks OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 5 } -- 1.3.6.1.4.1.318.2.3.6 -- 1.3.6.1.4.1.318.2.3.6 mtrapargsInteger02 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 6 } -- 1.3.6.1.4.1.318.2.3.7 -- 1.3.6.1.4.1.318.2.3.7 mtrapargsInteger03 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 7 } -- 1.3.6.1.4.1.318.2.3.8 -- 1.3.6.1.4.1.318.2.3.8 mtrapargsIpAddress02 OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0." ::= { mtrapargs 8 } -- 1.3.6.1.4.1.318.2.3.9 -- 1.3.6.1.4.1.318.2.3.9 mtrapargsIpAddress03 OBJECT-TYPE SYNTAX IpAddress ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0." ::= { mtrapargs 9 } -- 1.3.6.1.4.1.318.2.3.10 -- 1.3.6.1.4.1.318.2.3.10 mtrapargsString02 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 10 } -- 1.3.6.1.4.1.318.2.3.11 -- 1.3.6.1.4.1.318.2.3.11 mtrapargsString03 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 11 } -- 1.3.6.1.4.1.318.2.3.12 -- 1.3.6.1.4.1.318.2.3.12 mtrapargsGauge02 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 12 } -- 1.3.6.1.4.1.318.2.3.13 -- 1.3.6.1.4.1.318.2.3.13 mtrapargsGauge03 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 13 } -- 1.3.6.1.4.1.318.2.3.14 -- 1.3.6.1.4.1.318.2.3.14 mtrapargsTimeTicks02 OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 14 } -- 1.3.6.1.4.1.318.2.3.15 -- 1.3.6.1.4.1.318.2.3.15 mtrapargsTimeTicks03 OBJECT-TYPE SYNTAX TimeTicks ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 15 } -- 1.3.6.1.4.1.318.2.3.16 -- 1.3.6.1.4.1.318.2.3.16 mtrapargsString04 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 16 } -- 1.3.6.1.4.1.318.2.3.17 -- 1.3.6.1.4.1.318.2.3.17 mtrapargsString05 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 17 } -- 1.3.6.1.4.1.318.2.3.18 -- 1.3.6.1.4.1.318.2.3.18 mtrapargsInteger04 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 18 } -- 1.3.6.1.4.1.318.2.3.19 -- 1.3.6.1.4.1.318.2.3.19 mtrapargsInteger05 OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0." ::= { mtrapargs 19 } -- 1.3.6.1.4.1.318.2.3.20 -- 1.3.6.1.4.1.318.2.3.20 mtrapargsString06 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 20 } -- 1.3.6.1.4.1.318.2.3.21 -- 1.3.6.1.4.1.318.2.3.21 mtrapargsString07 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 21 } -- 1.3.6.1.4.1.318.2.3.22 -- 1.3.6.1.4.1.318.2.3.22 mtrapargsString08 OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 22 } -- 1.3.6.1.4.1.318.2.3.23 -- 1.3.6.1.4.1.318.2.3.23 mtrapargsOctetString OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 23 } -- 1.3.6.1.4.1.318.2.3.24 -- 1.3.6.1.4.1.318.2.3.24 mtrapargsOctetString02 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 24 } -- 1.3.6.1.4.1.318.2.3.25 -- 1.3.6.1.4.1.318.2.3.25 mtrapargsOctetString03 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 25 } -- 1.3.6.1.4.1.318.2.3.26 -- 1.3.6.1.4.1.318.2.3.26 mtrapargsOctetString04 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 26 } -- 1.3.6.1.4.1.318.2.3.27 -- 1.3.6.1.4.1.318.2.3.27 mtrapargsOctetString05 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 27 } -- 1.3.6.1.4.1.318.2.3.28 -- 1.3.6.1.4.1.318.2.3.28 mtrapargsOctetString06 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 28 } -- 1.3.6.1.4.1.318.2.3.29 -- 1.3.6.1.4.1.318.2.3.29 mtrapargsOctetString07 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 29 } -- 1.3.6.1.4.1.318.2.3.30 -- 1.3.6.1.4.1.318.2.3.30 mtrapargsOctetString08 OBJECT-TYPE SYNTAX OCTET STRING ACCESS read-only STATUS current DESCRIPTION "This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string." ::= { mtrapargs 30 } -- 1.3.6.1.4.1.318.2.4 -- 1.3.6.1.4.1.318.2.4 mfiletransfer OBJECT IDENTIFIER ::= { mgmt 4 } -- 1.3.6.1.4.1.318.2.4.1 -- 1.3.6.1.4.1.318.2.4.1 mfiletransferStatus OBJECT IDENTIFIER ::= { mfiletransfer 1 } -- the mfiletransfer group -- the mfiletransferStatus group -- 1.3.6.1.4.1.318.2.4.1.1 -- 1.3.6.1.4.1.318.2.4.1.1 mfiletransferStatusLastTransferResult OBJECT-TYPE SYNTAX INTEGER { lastFileTransferResultSuccessful(1), lastFileTransferResultNotAvailable(2), lastFileTransferResultFailureUnknown(3), lastFileTransferResultFailureServerInaccessible(4), lastFileTransferResultFailureServerAccessDenied(5), lastFileTransferResultFailureFileNotFound(6), lastFileTransferResultFailureFileTypeUnknown(7), lastFileTransferResultFailureFileCorrupted(8) } ACCESS read-only STATUS deprecated DESCRIPTION "This OID has been deprecated. Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer a file transfer of mfiletransferConfigSettingsFilename will be attempted from either a TFTP or FTP server. This OID shows the last attempted file transfer result. lastFileTransferResultSuccessful (1) means the file transfer was successful. lastFileTransferResultNotAvailable (2) means that there have been no previous file transfers. lastFileTransferResultFailureUnknown (3) means that the last file transfer failed for an unknown reason. lastFileTransferResultFailureServerInaccessible (4) means that the TFTP or FTP server could not be found on the network. lastFileTransferResultFailureServerAccessDenied (5) means that the TFTP or FTP server denied access. lastFileTransferResultFailureFileNotFound (6) means that the file could not be located. lastFileTransferResultFailureFileTypeUnknown (7) means the file was examined, but the contents were unknown. lastFileTransferResultFailureFileCorrupt (8) means the transferred file was corrupt." ::= { mfiletransferStatus 1 } -- 1.3.6.1.4.1.318.2.4.2 -- 1.3.6.1.4.1.318.2.4.2 mfiletransferConfig OBJECT IDENTIFIER ::= { mfiletransfer 2 } -- 1.3.6.1.4.1.318.2.4.2.1 -- 1.3.6.1.4.1.318.2.4.2.1 mfiletransferConfigSettings OBJECT IDENTIFIER ::= { mfiletransferConfig 1 } -- the mfiletransferConfig group -- the mfiletransferConfigSettings group -- 1.3.6.1.4.1.318.2.4.2.1.1 -- 1.3.6.1.4.1.318.2.4.2.1.1 mfiletransferConfigSettingsFilename OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS deprecated DESCRIPTION "This OID has been deprecated. The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID. If the file to transfer exists in the default server directory then the path may be omitted." ::= { mfiletransferConfigSettings 1 } -- 1.3.6.1.4.1.318.2.4.2.2 -- 1.3.6.1.4.1.318.2.4.2.2 mfiletransferConfigTFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 2 } -- the mfiletransferConfigTFTP group -- 1.3.6.1.4.1.318.2.4.2.2.1 -- 1.3.6.1.4.1.318.2.4.2.2.1 mfiletransferConfigTFTPServerAddress OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS deprecated DESCRIPTION "This OID has been deprecated. The IP Address in dotted decimal notation of the TFTP server involved in the file transfer." ::= { mfiletransferConfigTFTP 1 } -- 1.3.6.1.4.1.318.2.4.2.3 -- 1.3.6.1.4.1.318.2.4.2.3 mfiletransferConfigFTP OBJECT IDENTIFIER ::= { mfiletransferConfig 3 } -- the mfiletransferConfigFTP group -- 1.3.6.1.4.1.318.2.4.2.3.1 -- 1.3.6.1.4.1.318.2.4.2.3.1 mfiletransferConfigFTPServerAddress OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS deprecated DESCRIPTION "This OID has been deprecated. The IP Address in dotted decimal notation of the FTP server involved in the file transfer." ::= { mfiletransferConfigFTP 1 } -- 1.3.6.1.4.1.318.2.4.2.3.2 -- 1.3.6.1.4.1.318.2.4.2.3.2 mfiletransferConfigFTPServerUser OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS deprecated DESCRIPTION "This OID has been deprecated. The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress." ::= { mfiletransferConfigFTP 2 } -- 1.3.6.1.4.1.318.2.4.2.3.3 -- 1.3.6.1.4.1.318.2.4.2.3.3 mfiletransferConfigFTPServerPassword OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS deprecated DESCRIPTION "This OID has been deprecated. The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress." ::= { mfiletransferConfigFTP 3 } -- 1.3.6.1.4.1.318.2.4.3 -- 1.3.6.1.4.1.318.2.4.3 mfiletransferControl OBJECT IDENTIFIER ::= { mfiletransfer 3 } -- the mfiletransferControl group -- 1.3.6.1.4.1.318.2.4.3.1 -- 1.3.6.1.4.1.318.2.4.3.1 mfiletransferControlInitiateFileTransfer OBJECT-TYPE SYNTAX INTEGER { doNotInitiateFileTransfer(1), initiateFileTransferDownloadViaTFTP(2), initiateFileTransferDownloadViaFTP(3) } ACCESS read-write STATUS deprecated DESCRIPTION "This OID has been deprecated. Setting this OID to doNotInitiateFileTransfer (1) will do nothing. Setting this OID to initiateFileTransferDownloadViaTFTP (2) will attempt to transfer the file named in mfiletransferConfigSettingsFilename from the TFTP Server identified in mfiletransferConfigTFTPAddress. Setting this OID to initiateFileTransferDownloadViaFTP (3) will attempt to transfer the file named in mfiletransferConfigSettingsFilename from the FTP Server identified in mfiletransferConfigFTPAddress using mfiletransferConfigFTPUser and mfiletransferConfigFTPPassword for the FTP Server login process." ::= { mfiletransferControl 1 } -- -- Trap definitions -- -- Trap definitions -- -- Traps -- Annotations are provided for Novell's NMS product -- -- Each trap has at least one variable (mtrapargsString) which always appears -- as the last variable in the list. This variable contains either a static -- or dynamically-constructed string which provides an enhanced description of -- the trap's purpose and any pertinent information about the trap. -- rPDU2g Trap Section -- #TYPE "RPDU: A critical condition has been detected." -- #SUMMARY "A critical condition has been detected." -- #SEVERITY SEVERE -- #TIMEINDEX 1 -- #HELP "" -- #HELPTAG 0 -- #STATE DEGRADED rpduCriticalCondition TRAP-TYPE ENTERPRISE PDU VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString } DESCRIPTION "SEVERE: A RPDU critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message." ::= 750 -- #TYPE "RPDU: A critical condition has been cleared." -- #SUMMARY "A critical condition has been cleared." -- #SEVERITY INFORMATIONAL -- #TIMEINDEX 1 -- #HELP "" -- #HELPTAG 0 -- #STATE OPERATIONAL rpduCriticalConditionCleared TRAP-TYPE ENTERPRISE PDU VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString } DESCRIPTION "INFORMATIONAL: A RPDU critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message." ::= 751 -- #TYPE "RPDU: A warning condition has been detected." -- #SUMMARY "A warning condition has been detected." -- #SEVERITY WARNING -- #TIMEINDEX 1 -- #HELP "" -- #HELPTAG 0 -- #STATE DEGRADED rpduWarningCondition TRAP-TYPE ENTERPRISE PDU VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString } DESCRIPTION "WARNING: A RPDU warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message." ::= 752 -- #TYPE "RPDU: A warning condition has been cleared." -- #SUMMARY "A warning condition has been cleared." -- #SEVERITY INFORMATIONAL -- #TIMEINDEX 1 -- #HELP "" -- #HELPTAG 0 -- #STATE OPERATIONAL rpduWarningConditionCleared TRAP-TYPE ENTERPRISE PDU VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString } DESCRIPTION "WARNING: A RPDU warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message." ::= 753 -- #TYPE "RPDU: Informational condition detected." -- #SUMMARY "An informational condition has been detected." -- #SEVERITY INFORMATIONAL -- #TIMEINDEX 1 -- #HELP "" -- #HELPTAG 0 -- #STATE OPERATIONAL rpduInformationalCondition TRAP-TYPE ENTERPRISE PDU VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString } DESCRIPTION "INFORMATIONAL: A RPDU informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message." ::= 754 -- #TYPE "RPDU: Informational condition cleared." -- #SUMMARY "An informational condition has been cleared." -- #SEVERITY INFORMATIONAL -- #TIMEINDEX 1 -- #HELP "" -- #HELPTAG 0 -- #STATE OPERATIONAL rpduInformationalConditionCleared TRAP-TYPE ENTERPRISE PDU VARIABLES { mtrapargsString02, mtrapargsString03, mtrapargsInteger, mtrapargsInteger02, mtrapargsInteger03, mtrapargsString } DESCRIPTION "INFORMATIONAL: A RPDU informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message." ::= 755 END -- -- PowerNet-PDU.mib --